The following alarms are specific to the PAMC I/O pack.

38

Description Flash disk error: Unable to revert to flash configuration after remote access. Possible Cause The permanent configuration data on PAMC is corrupted.

Solution

• Build and download the firmware and configuration to the PAMC. • Replace the PAMC UCSA.

41-58

Description Sig [ ]: Open Circuit Test Failure.

Possible Cause An open circuit for a specified terminal board signal has been detected. Solution

• Check the wiring and sensor. • Replace the BAPA.

• Replace the terminal board.

61-78

Description Sig [ ]: Excessive DC Bias. Possible Cause

• Configuration does not match the sensor type.

• DC bias (DC offset) designated for the sensor type is outside the range detected for the sensor.

Solution

Check the sensor type in the configuration parameter InputUse. • Check the dc voltage on the signal. Refer to the PAMC documentation.

81-98

Description Sig [ ]: Input Signal exceeds HW limit.

Possible Cause The peak input voltage exceeds the HW limit for the input. Solution

Decrease the configuration parameter Gain for the designated signal. • Check the sensor for issues.

101-118

Description Sig [ ]: Sensor Limit Exceeded.

Possible Cause The peak input voltage exceeds the limit for the selected sensor type. Solution

Check the sensor type in the configuration parameter InputUse. • Check the sensor for issues.

121-138

Description BAPA Chan [ ]: ADC calibration failure.

Possible Cause The BAPA failed the calibration test when powered on. Solution Replace the BAPA.

139-156

Description BAPA Chan [ ]: DAC calibration failure.

Possible Cause the BAPA failed the calibration test when powered on. Solution Replace the BAPA.

157-174

Description BAPA Chan [ ]: DC test failure.

Possible Cause The BAPA failed the DC test during the manually invoked self-test. Solution Replace the BAPA.

175-192

Description BAPA Chan [ ]: Analog gain test failure.

Possible Cause The BAPA failed the gain test during the manually invoked self-test. Solution Replace the BAPA.

193-210

Description BAPA Chan [ ]: AC FFT test failure.

Possible Cause The BAPA failed the AC FFT test during the manually invoked self-test. Solution Replace the BAPA.

212

Description HSSL Comm link [ ] Communication Failure, Code [ ].

Possible Cause The PAMC/UCSA cannot communicate with the remote acquisition hardware (terminal board and BAPA)

through the High-Speed Serial Link (HSSL) cable. The code indicates a specific failure type. Common codes include:

• 51xxxxxx: Remote acquisition target returning bad id • 52xxxxxx: Download to BAPA failed

• 53xxxxxx: Link loss detected

• 54xxxxxx: Receive packet error detected

• 55xxxxxx: Transmit packet error (excessive naks) • 57xxxxxx: No data received from BAPA in 5 seconds

Solution

• Verify that the BAPA is connected to the SL1 connector on the PAMC UCSA. • Check the HSSL cables. If a problem still exists, replace the PAMC UCSA module. • Check the power on the BAPA.

Description HSSL Comm link [ ] Initialization Failure.

Possible Cause The PAMC UCSA cannot properly initialize the BAPA through the HSSL. Solution

• Verify that the BAPA is connected to the appropriate HSSL connector on the PAMC UCSA. • Check the HSSL cables. If a problem still exists, replace the PAMC UCSA module. • Check the power on the BAPA.

• Replace the BAPA.

214

Description HSSL Comm link [ ] Configuration Failure, Code [ ].

Possible Cause The PAMC UCSA interface to the HSSL failed to initialize properly. Solution Replace the PAMC UCSA.

215

Description BAPA plugged into wrong SAMx connector on HSSL [ ].

Possible Cause The SAMB or SAMC connector that the BAPA is plugged into does not agree with HSSL connector

configured in the ToolboxST application.

Solution

• Verify that the HSSL cable is plugged into the PAMC UCSA SL1 connector. • Verify that the HSSL cable is plugged into the correct BAPA.

• Verify that the SAMC/SAMB configured connections in the ToolboxST application match the BAPA connection to the terminal board.

216

Description BICA (JA1) On Board power supply failure, expected [ ] V, read [ ] V. Possible Cause The BICA power supply failed.

Solution Replace the BICA plugged into the JA1 connector.

217

Description BICA (JB1) On Board power supply failure, expected [ ] V, read [ ] V. Possible Cause The BICA power supply failed.

Solution Replace the BICA plugged into the JB1 connector.

218

Description Bad power supply on connector P28 [ ](1=A,2=B,3=C) in charge amp junction box. Possible Cause There is no 28 volt power connected to the P28B or the P28C in the junction box. Solution

Parameter JuncBox is set for the wrong type.

• Verify the power supply connection to the P28B or the P28C in the junction box. • Replace the power supply cable/connector.

219

Description Bad power supply on connector P28B or P28C in charge amplifier junction box. Possible Cause The junction box power supply is faulty.

Solution

Parameter JuncBox is set for the wrong type.

• Verify the power supply connections to both the P28B and the P28C in the junction box. • Replace the power supply cable/connector.

• Replace the power supply.

220

Description SAMC terminal board failure in charge amplifier junction box.

Possible Cause The power supply status on the SAMC terminal board indicates an SAMC failure. Solution Replace the SAMC in the junction box.

221

Description BICA (JA1) to BAPA communications error.

Possible Cause The power supply status in the BICA is not being updated. Solution

• Replace the BICA on the JA1 connector in the junction box. • Replace the BAPA in the junction box.

222

Description BICA (JB1) to BAPA communications error.

Possible Cause The power supply status in the BICA is not being updated. Solution

• Replace the BICA on the JB1 connector in the junction box. • Replace the BAPA in the junction box.

230-247

Description BAPA Chan [ ]: Anti alias rolloff test failure.

Possible Cause The BAPA failed the anti-alias test during the manually invoked self-test. Solution Replace the BAPA.