Abstract-- Most of the time transformers work under balanced supplying conditions. However, after some fault conditions or anomalous switching operations, zero sequence component in excitation may be expectable. Transformers behavior under zero sequence excitation may be very different from usual behavior and might become dangerous.

Some simulations are performed with the Alternative Transients Program (ATP), representing a three-legged core type three-phase transformer with a model available in the ATP library.

Results show overvoltages and high saturated currents on the unloaded transformer. The proper use of the three-legged core type transformer model, enables to evidence the influence of the characteristics of zero sequence transformer on the development of such overvoltages and high transformer currents.

Besides, regardless load conditions, important homopolar currents are observed flowing to ground from the transformer high voltage neutral. The resultant homopolar fluxes could cause heating and damage in a three-legged core type transformer.

Keywords -- transformer cores, ferroresonance.

I. NOMENCLATURE

LV: Low Voltage HV: High Voltage

II. INTRODUCTION

he zero sequence behavior of a transformer, which can be excited under unbalanced conditions, depends mainly on core configuration and winding connections.

Grounded-wye connected windings always provide a path for zero sequence current. That is why a grounded-wye to grounded-wye transformer presents a finite homopolar impedance from either sides. The impedance value depends, among other things, on core configuration.

A five-legged core form or a shell form configuration, always provide zero sequence fluxes with a path totally placed inside the iron of the core. Consequently, the zero sequence magnetizing inductance for these core configurations is very high and similar to the positive sequence inductance.

This work was supported in part by the IITREE-UNLP (Instituto de Investigaciones Tecnológicas para Redes y Equipos Eléctricos-Universidad Nacional de La Plata) and the rest by the School of Engineering at UNLP, La Plata, Argentina.

J. Z. Vernieri is with IITREE-UNLP (e-mail: jvernier@ing.unlp.edu.ar). M. B. Barbieri is with IITREE-UNLP (e-mail: barbieri@ing.unlp.edu.ar). P. L. Arnera is with IITREE-UNLP (e-mail: parnera@ing.unlp.edu.ar).

On the other hand, in a three-legged core type, zero sequence fluxes cannot circulate exclusively in the core, and are forced to return through the insulation surrounding the core and through the transformer tank. As this path presents a high reluctance, the zero sequence magnetizing inductance is much lower than the positive sequence magnetizing inductance.

III. CASE STUDY

The case studied, based on a real case, consists of a three-legged core type, grounded-wye to grounded-wye, three-phase distribution transformer, fed through an underground cable. Two circuit breakers exist at each end of the cable. A simplified equivalent circuit is depicted in Fig. 1.

3 PHASE SOURCE UNDERGROUND

CABLE TRANSFORMER MAIN BREAKER 3-LEG CORE TYPE

TRANSFORMER

LOAD

CIRCUIT BREAKER

[image:1.612.335.537.384.460.2]

Xsource

Fig. 1 - Simplified circuit representation.

The three phase equivalent source and its inductance, represent the 50Hz, 132 kV power system. The cable length is 13.5 km and its positive and zero sequence capacitance is 0.404 µF/km.

The following information about the transformer is known: 1. Rated power - 40 MVA (three-phase)

2. Rated voltages - 132 kV/13.86 kV (line to line values) 3. Two winding transformer: wye to

grounded-wye connection (YNyn0)

Table 1 shows transformer specifications data from positive sequence tests. Table 2 shows positive sequence saturation curve obtained from excitation test at LV side (13.86 kV line to line). Table 3 shows transformer zero sequence parameters.

TABLE I

TRANSFORMER POSITIVE SEQUENCE PARAMETERS

Excitation losses 24 kW Excitation current 0.15 % Short-circuit losses 176 kW Short-circuit impedance 13.3 %

Consequence of an unbalanced supplying

condition on a distribution transformer

Julieta Z. Vernieri, M. Beatriz Barbieri,

Member, IEEE

, and Patricia L. Arnera,

Member, IEEE.

T

Paper accepted for presentation at PPT 2001 2001 IEEE Porto Power Tech Conference 10th –13th September, Porto, Portugal

Figure

Fig. 1 - Simplified circuit representation.

Referencias

Documento similar

The dialogs acquired with the automatic generation technique are statistically shorter, as they provide 1.17 actions per user turn instead of the 1.06 actions provided by the real

In this paper, we introduce a new algorithm for the generation of random data from covariance matrices of random structure, where the user only decides the data dimension and the

• Para cumplir nuestras promesas a Dios y a los demás, necesitamos que el Señor nos bendiga, que el Señor nos guarde, que el Señor nos dé gracia, que el Señor se dé a sí

For the first phase of 24 weeks, CP treatment was applied with a constant current density of 15 mA/m² relative to exposed concrete or anode surface (25.5 mA/m 2 relative to the steel

On the other hand, the larvae from 18 ovipostions that were kept in the laboratory at ambient temperatu- re emerged between two and four days after they were collected in the

A la placenta se le viste con una camisa, un cinturón y un sombrero y se la cuelga de un árbol, para devolverla a uno de los elementos: el viento.. Hay que devolver a la naturaleza

Que o Espírito Santo, promessa de Cristo que não nos deixaria órfãos infunda em nós o dom do entendimento para compreendermos as verdades da fé e os ensinamentos de Jesus.A

The Dome of the Rock does attest the existence, at the end of the seventh century, of materials immediately recognisable as Koranic in a text that not infrequently