• No se han encontrado resultados

El acto de habla y su interpretación como unidad comunicativa del discurso

CAPÍTULO 1. EL ESTUDIO DE LA ENTONACIÓN EN EL DISCURSO

1.4. La función comunicativa de la entonación

1.4.1. El acto de habla y su interpretación como unidad comunicativa del discurso

12.8.1 Role of Grounding

With poor grounding, lightning strikes to distribution lines subject more equipment to possibly damaging surges due to ground potential rise. Light- ning current must flow to ground somewhere. If the pole ground near the strike point has high impedance, more of the surge flows in the line, exposing more equipment to possible overvoltages. At the point of a direct stroke to a distribution conductor, the huge voltages flash over the insulation, shorting the phase to the neutral. From there, the lightning travels to the closest ground. If there is no proper pole ground nearby, the next most likely path is down a guy wire. If the path to ground is poor, the phase conductor and neutral wire all rise up in voltage together. This surge (on both the phase and neutral) travels down the circuit. When the surge reaches another ground point, current drains off the neutral wire, which increases the voltage between the phase and the neutral. The voltage across the insulation grows until a surge arrester conducts more current to ground or another insulation flashover occurs. Figure 12.29 shows a drawing describing the ground poten- tial effect, and Figure 12.1 shows a photograph of a direct strike that caused another flashover remote from the flash point.

Good grounding helps confine possible lightning damage to the immediate vicinity of the strike. If the distribution insulation flashes over, the short circuit acts as an arrester and helps protect other equipment on the circuit (as long as grounds are good).

Normally, the ground resistance right at a piece of equipment protected with an arrester does not impact the primary-side protection. The primary surge arrester is between the phase and ground. For a lightning hit to the primary, the arrester conducts the current to ground and limits the voltage across the equipment insulation (even though the potential of all conductors may rise with poor grounding).

Grounding does play a role for transformers, as they are vulnerable to surge current entering through the secondary. Poor grounding pushes more current into the transformer on the secondary side and increases the possi- bility of failure. Poor grounding also forces more current to flow into the secondary system to houses connected to the transformer. And, poor ground- ing may also push more current into telephone and cable television systems.

12.8.2 Burndowns

The lightning arc itself can pass enough charge to burn small primary and secondary wires although sometimes it is hard to tell whether it is the lightning or the fault arc that does most of the damage. Normally, it is the power frequency arc that does the most damage. Chisholm et al. (2001) cites

a damage rate on Hydro-One’s primary distribution system of 0.13/100 mi/ year (0.08/100 km/year) for an area with a ground flash density of about 1 flash/km2/year. This is about 1% of the lightning flashes hitting circuits.

The lightning arc causes damage the same way that a fault current arc (and also an arc welder) does: the heat of the arc melts conductor strands. Damage is mainly a function of the charge in the flash. Lightning tends to be more damaging than the equivalent ac fault arc. A negative direct current is about 50% more damaging than an alternating current passing equal coulombs. Negative flashes are more destructive than positive flashes; it takes about three times the charge for a positive stroke to cause the same damage as a negative stroke. Lightning also tends to stay in one place more than an arc because it does not have the motoring effect.

12.8.3 Crossarm and Pole Damage and Bonding

Although service experience indicates that lightning rarely damages poles or crossarms; in high-lightning areas, concern is warranted. Darveniza (1980) cites a survey by Zastrow published in 1966 that found poles failing from lightning in the range of 0.008 to 0.023% annually (versus an overall failure rate of 0.344 to 1.074% with more than half of these due to decay). Other surveys summarized by Darveniza also found minimal lightning-caused damage. Lightning overvoltages damage and shatter poles and crossarms when the wood breaks down internally rather than along the surface. If the wood is green and wet, internal breakdowns and damage are more likely. Damage within the first year of service is more likely.

If historical records show that wood damage is a problem, bonding the insulators (grounding the base of each insulator) protects the wood, but this shorts out the insulation capability provided by the wood. Better are surface electrodes fitted near the insulator pin, including wire-wraps, bands, or other metal extensions attached near the insulator in the likely direction of flashover. This local bonding encourages breakdown near the surface rather than internally.

Preventative measures for lightning damage to wood also reduce the likelihood of pole-top fires. Leakage current arcs at metal-to-wood inter- faces start fires (Darveniza, 1980; Ross, 1947). Local bonding using wire bands or wraps helps prevent pole damage. Bonding bridges the metal-to- wood contacts where fires are most likely to start. Local bonding is better than completely bonding the insulators because the insulation level is not compromised.

12.8.4 Arc Quenching of Wood

Wood poles and crossarms can prevent faults from forming after lightning flashes across the wood (Armstrong et al., 1967; Darveniza et al., 1967). Whether this arc quenching occurs depends mainly on the power frequency

voltage gradient along the arc at the time of the flashover. If the power- frequency voltage happens to be near a zero crossing when the lightning strikes, the lightning-caused arc is likely to extinguish rather than becoming a power-frequency fault.

The voltage gradient for an arc inside wood is much higher than an arc voltage gradient in the air. Darveniza (1980) found voltage gradients in wood on the order of 1000 V/in. (400 V/cm) through wood compared to about 30 V/in. (12 V/cm) for arcs in air. When dry wood insulation arcs, the path is often just barely below the surface (about a millimeter); and the arc is sur- rounded by wood fibers, so the arc-suppression action occurs. Wood fibers raise the arc voltage primarily by cooling it and absorbing ionized particles (similar to the arc-absorbing action of fuses). The arc voltage gradient is lower for wet wood (flashovers are no longer fully contained and tend to arc on the surface rather than just below the surface). There is considerable variability in the arc voltage, especially for wet wood. To transition from a lightning arc to a power-frequency fault, the power-frequency voltage must be higher than the arc voltage to keep the arc conducting.

Darveniza calculated several probabilities for arc quenching based on the arc voltage gradients (see Figure 12.30). Arc quenching is less likely on wet wood and when multiple phases flash over (even if the flashovers are on the same phase). To achieve significant benefit, voltage gradients must be kept less than 3 kV/ft (10 kV/m) of wood. For a 12.47Y/7.2-kV system, this is at least 2.4 ft (7.2/3 = 2.4 ft or 0.7 m) of wood in the phase-to-ground flashover paths and at least 4.1 ft (1.2 m) of wood in the phase-to-phase

FIGURE 12.30

Probability of a power-frequency fault due to a lightning-caused flashover over wet wood crossarms with different numbers of flashover paths. (Adapted from Darveniza, M., Electrical

Properties of Wood and Line Design, University of Queensland Press, 1980. With permission.)

1f, 1 path 3f, 6 paths 3f, 3 paths 1f, 3 paths 0 5 10 15 0.0 0.2 0.4 0.6 0.8 1.0

Voltage gradient, kVrms per foot of wood

Probability of a power arc

flashover paths. And, if we really want to count on this effect, we should at least double these lengths.

References

Anderson, R. B. and Eriksson, A. J., “Lightning Parameters for Engineering Appli- cations,” Electra, no. 69, pp. 65–102, March 1980a.

Anderson, R. B. and Eriksson, A. J., “A Summary of Lightning Parameters for Engi- neering Applications,” CIGRE Paper No. 33–06, 1980b.

ANSI C84.1-1995, American National Standards for Electric Power Systems and Equipment — Voltage Ratings (60 Hz).

ANSI/IEEE C62.11-1987, IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits, American National Standards Institute, Institute of Electrical and Elec- tronics Engineers, Inc.

Armstrong, H. R., Stoetling, H. O., and Veverka, E. F., “Impulse Studies on Distribu- tion Line Construction,” IEEE Transactions on Power Apparatus and Systems, vol. 86, pp. 206–14, 1967.

AT&T Technologies Inc., “Telecommunication Electrical Protection.” Select code 350- 060, 1985.

Barker, P. P., “Voltage Quadrupling on a UD Cable,” IEEE Transactions on Power Delivery, vol. 5, no. 1, pp. 498–501, January 1990.

Barker, P. P. and Burns, C. W., “Photography Helps Solve Distribution Lightning Problems,” IEEE Power Engineering Review, vol. 13, no. 6, June 1993.

Barker, P. P., Mancao, R. T., Kvaltine, D. J., and Parrish, D. E., “Characteristics of Lightning Surges Measured at Metal Oxide Distribution Arresters,” IEEE Trans- actions on Power Delivery, vol. 8, no. 1, pp. 301–10, January 1993.

Barker, P. P. and Short, T. A., “Lightning Effects Studied — The Underground Cable Program,” Transmission & Distribution World, vol. 48, no. 5, May 1996. Barker, P. P., Short, T. A., Eybert, B. A. R., and Berlandis, J. P., “Induced Voltage

Measurements on an Experimental Distribution Line During Nearby Rocket Triggered Lightning Flashes,” IEEE Transactions on Power Delivery, vol. 11, no. 2, pp. 980–95, April 1996.

Berger, K., Anderson, R. B., and Kröninger, H., “Parameters of Lightning Flashes,” Electra, no. 41, pp. 23–37, July 1975.

Burke, J. J. and Sakshaug, E. C., “The Application of Gapless Arresters on Under- ground Distribution Systems,” IEEE Transactions on Power Apparatus and Sys- tems, vol. PAS-100, no. 3, pp. 1234–43, March 1981.

Campos, M. L. B., Coelho, V. L., et al., “Evaluation of the Sealing System and of the Electric Performance of the Distribution Lightning Arresters,” CIRED, June 1997.

CEA 160 D 597, Effect of Lightning on the Operating Reliability of Distribution Systems, Canadian Electrical Association, Montreal, Quebec, 1998.

Chisholm, W. A., Beattie, J., and Janischewskyj, W., “Analysis of the Optical Transient Detector Measurements of Lightning over North and South America,” Proceed- ings of V International Symposium on Lightning Protection (SIPDA), Sào Pau- lo, Brazil, May 1999.

Chisholm, W. A., Levine, J. P., and Pon, C., “Lightning Protection Aspects for Ap- plications of Optical Fibre Ground Wire,” International Symposium on Light- ning Protection (SIPDA), Santos, Brazil, 2001.

Cigre, “Guide to Procedures for Estimating the Lightning Performance of Transmis- sion Lines,” Working group 01 (lightning) of study committee 33 (overvoltages and insulation co-ordination), 1991.

Darveniza, M., Electrical Properties of Wood and Line Design, University of Queensland Press, 1980.

Darveniza, M., Limbourn, G. J., and Prentice, S. A., “Line Design and Electrical Properties of Wood,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-86, pp. 1344–56, 1967.

Darveniza, M., Mercer, D. R., and Watson, R. M., “An Assessment of the Reliability of In-Service Gapped Silicon-Carbide Distribution Surge Arresters,” IEEE Transactions on Power Delivery, vol. 11, no. 4, pp. 1789–97, October 1996. Darveniza, M., Roby, D., and Tumma, L. R., “Laboratory and Analytical Studies of

the Effects of Multipulse Lightning Current on Metal Oxide Arresters,” IEEE Transactions on Power Delivery, vol. 9, no. 2, pp. 764–71, April 1994.

Darveniza, M., Saha, T. K., and Wright, S., “Comparisons of In-Service and Laboratory Failure Modes of Metal-Oxide Distribution Surge Arresters,” IEEE/PES Winter Power Meeting, October 2000.

Darveniza, M., Tumma, L. R., Richter, B., and Roby, D. A., “Multipulse Lightning Currents and Metal-Oxide Arresters,” IEEE Transactions on Power Delivery, vol. 12, no. 3, pp. 1168–75, July 1997.

Dommel, H. W., “Electromagnetic Transients Program Reference Manual (EMTP Theory Book),” prepared for Bonneville Power Administration, 1986.

EPRI, Transmission Line Reference Book: 345 kV and Above, 2nd ed., Electric Power Research Institute, Palo Alto, CA, 1982.

EPRI. Lightning Protection Design Workstation version 5.0 CFlash online help: Elec- tric Power Research Institute, Palo Alto, CA, 1999.

EPRI TR-000530, Lightning Protection Design Workstation Seminar Notes, Electric Power Research Institute, Palo Alto, CA, 1992.

EPRI TR-100218, Characteristics of Lightning Surges on Distribution Lines. Second Phase — Final Report, Electric Power Research Institute, Palo Alto, CA, 1991. Eriksson, A. J., “The Incidence of Lightning Strikes to Power Lines,” IEEE Transactions

on Power Delivery, vol. PWRD-2, no. 3, pp. 859–70, July 1987.

Goedde, G. L., Dugan, R. C., and Rowe, L. D., “Full Scale Lightning Surge Tests of Distribution Transformers and Secondary Systems,” IEEE Transactions on Power Delivery, vol. 7, no. 3, pp. 1592–600, July 1992.

Henning, W. R., Hernandez, A. D., and Lien, W. W., “Fault Current Capability of Distribution Transformers with Under-Oil Arresters,” IEEE Transactions on Pow- er Delivery, vol. 4, no. 1, pp. 405–12, January 1989.

Hu, H. and Mashikian, M. S., “Modeling of Lightning Surge Protection in Branched Cable Distribution Network,” IEEE Transactions on Power Delivery, vol. 5, no. 2, pp. 846–53, April 1990.

IEEE C2-1997, National Electrical Safety Code.

IEEE C57.12.00-2000, IEEE Standard General Requirements for Liquid-Immersed Distri- bution, Power, and Regulating Transformers.

IEEE C62.92.4-1991, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems, Part IV - Distribution.

IEEE Std. 386-1995, IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600 V.

IEEE Std. 1410-1997, IEEE Guide for Improving the Lightning Performance of Electric Power Overhead Distribution Lines.

IEEE Std. C62.22-1997, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems.

IEEE Task Force Report, “Secondary (Low-Side) Surges in Distribution Transform- ers,” IEEE Transactions on Power Delivery, vol. 7, no. 2, pp. 746–56, April 1992. Ishii, M. Discussion to (Barker et al., 1996), 1996.

Ishii, M., Michishita, K., Hongo, Y., and Oguma, S., “Lightning-Induced Voltage on An Overhead Wire Dependent on Ground Conductivity,” IEEE Transactions on Power Delivery, vol. 9, no. 1, pp. 109–18, January 1994.

Jacob, P. B., Grzybowski, S., and Ross, E. R. J., “An Estimation of Lightning Insulation Level of Overhead Distribution Lines,” IEEE Transactions on Power Delivery, vol. 6, no. 1, pp. 384–90, January 1991.

Kannus, K., Lahti, K., and Nousiainen, K., “Effects of Impulse Current Stresses on the Durability and Protection Performance of Metal Oxide Surge Arresters,” High Voltage Engineering Symposium, August 22–27, 1999.

Kershaw, S. S., Jr., “Surge Protection for High Voltage Underground Distribution Circuits,” Conference on Underground Distribution, Detroit, MI, September 27–October 1, 1971.

Lahti, K., Kannus, K., and Nousiainen, K., “Behaviour of the DC Leakage Currents of Polymeric Metal Oxide Surge Arresters in Water Penetration Tests,” IEEE Transactions on Power Delivery, vol. 13, no. 2, pp. 459–64, April 1998.

Lahti, K., Kannus, K., and Nousiainen, K., “A Comparison Between the DC Leakage Currents of Polymer Housed Metal Oxide Surge Arresters in Very Humid Ambient Conditions and in Water Immersion Tests,” IEEE Transactions on Power Delivery, vol. 14, no. 1, pp. 163–8, January 1999.

Lahti, K., Kannus, K., and Nousiainen, K., “The Durability and Performance of Polymer Housed Metal Oxide Surge Arresters Under Impulse Current Stress- es,” CIRED, 2001.

Lat, M. V. and Kortschinski, J., “Distribution Arrester Research,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 7, pp. 3496–505, July 1981. MacGorman, D. R., Maier, M. W., and Rust, W. D., “Lightning Strike Density for the

Contiguous United States from Thunderstorm Duration Records.” Report to the U.S. Nuclear Regulatory Commission, # NUREG/CR-3759, 1984.

Marz, M. B., Royster, T. E., and Wahlgren, C. M., “A Utility’s Approach to the Appli- cation of Scout Arresters for Overvoltage Protection of Underground Distribu- tion Circuits,” IEEE/PES Transmission and Distribution Conference, 1994. McDaniel, J., “Line Arrester Application Field Study,” IEEE/PES Transmission and

Distribution Conference and Exposition, 2001.

McDermott, T. E., Short, T. A., and Anderson, J. G., “Lightning Protection of Distri- bution Lines,” IEEE Transactions on Power Delivery, vol. 9, no. 1, pp. 138–52, January 1994.

Owen, R. E. and Clinkenbeard, C. R., “Surge Protection of UD Cable Systems. I. Cable Attenuation and Protection Constraints,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-97, no. 4, pp. 1319–27, 1978.

Parrish, D. E., “Lightning-Caused Distribution Circuit Breaker Operations,” IEEE Transactions on Power Delivery, vol. 6, no. 4, pp. 1395–401, October 1991.

Parrish, D. E. and Kvaltine, D. J., “Lightning Faults on Distribution Lines,” IEEE Transactions on Power Delivery, vol. 4, no. 4, pp. 2179–86, October 1989. Powell, R. W., Thwaites, H. L., and Stys, R. D., “Estimating Lightning Performance

of Spacer-Cable Systems,” IEEE Transactions on Power Apparatus and Systems, vol. 84, pp. 315–9, April 1965.

REA Bulletin 50-3, Specifications and Drawings for 12.5/7.2-kV Line Construction, United States Department of Agriculture, Rural Electrification Administration, 1983. Ringler, K. G., Kirkby, P., Erven, C. C., Lat, M. V., and Malkiewicz, T. A., “The Energy

Absorption Capability and Time-to-Failure of Varistors Used in Station-Class Metal-Oxide Surge Arresters,” IEEE Transactions on Power Delivery, vol. 12, no. 1, pp. 203–12, January 1997.

Ros, W. J., “Neutral-to-Ground Impulse Voltage Effects on URD Cable,” IEEE Rural Electric Power Conference, 1993.

Ross, E. R. and Grzybowski, S., “Application of the Extended CFO Added Method to Overhead Distribution Configurations,” IEEE Transactions on Power Delivery, vol. 6, no. 4, pp. 1573–8, October 1991.

Ross, P. M., “Burning of Wood Structures by Leakage Currents,” AIEE Transactions, vol. 66, pp. 279–87, 1947.

Rusck, S., “Induced Lightning Overvoltages on Power Transmission Lines With Spe- cial Reference to the Overvoltage Protection of Low Voltage Networks,” Trans- actions of the Royal Institute of Technology, no. 120, 1958.

Rusck, S., “Protection of Distribution Lines,” in Lightning, R. H. Golde, ed., London, Academic Press, 1977.

Short, T. A. and Ammon, R. H., “Monitoring Results of the Effectiveness of Surge Arrester Spacings on Distribution Line Protection,” IEEE Transactions on Power Delivery, vol. 14, no. 3, pp. 1142–50, July 1999.

Short, T. A., Burke, J. J., and Mancao, R. T., “Application of MOVs in the Distribution Environment,” IEEE Transactions on Power Delivery, vol. 9, no. 1, pp. 293–305, January 1994.

Sunde, E. D., Earth Conduction Effects in Transmission Systems, Dover Publications, New York, 1968.

Task force of eight utility companies and the General Electric Company, “Investiga- tion and Evaluation of Lightning Protective Methods for Distribution Circuit. I. Model Study and Analysis,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-88, no. 8, pp. 1232–8, August 1969a.

Task force of eight utility companies and the General Electric Company, “Investiga- tion and Evaluation of Lightning Protective Methods for Distribution Circuits. II. Application and Evaluation,” IEEE Transactions on Power Apparatus and Sys- tems, vol. PAS-88, no. 8, pp. 1239–47, August 1969b.

Thottappillil, R., Rakov, V. A., Uman, M. A., Beasley, W. H., Master, M. J., and Shelukhin, D. V., “Lightning Subsequent-Stroke Electric Field Peak Greater Than the First Stroke Peak and Multiple Ground Terminations,” Journal of Geophysical Research, vol. 97, no. D7, pp. 7503–9, May 20, 1992.

Wagner, C. F., “Application of Predischarge Currents of Parallel Electrode Gaps,” IEEE Transactions on Power Apparatus and Systems, vol. 83, pp. 931–44, September 1964.

Wagner, C. F. and Hileman, A. R., “Effect of Predischarge Currents Upon Line Per- formance,” IEEE Transactions on Power Apparatus and Systems, vol. 82, pp. 117–31, April 1963.

Wagner, C. F. and Hileman, A. R., “Predischarge Current Characteristics of Parallel Electrode Gaps,” IEEE Transactions on Power Apparatus and Systems, vol. 83, pp. 1236–42, December 1964.

Walling, R. A., Hartana, R. K., Reckard, R. M., Sampat, M. P., and Balgie, T. R., “Performance of Metal-Oxide Arresters Exposed to Ferroresonance in Pad- mount Transformers,” IEEE Transactions on Power Delivery, vol. 9, no. 2, pp. 788–95, April 1994.

Ward, D. J., “Evaluating Product Reliability Costs,” IEEE Transactions on Power De- livery, vol. 5, no. 2, pp. 724–9, 1990.

Williams, C. W., “Findings of Low-Voltage Surge Effect on the Florida Power Corp. System,” Presented to the Task Force on Low-Side Surge Requirements for Distribution Transformers, IEEE Transformers Committee, Washington, DC, April 1988. As cited by IEEE Task Force Report (1992).

Zhou, L.-M. and Boggs, S. A., “Effect of Shielded Distribution Cables on Lightning- Induced Overvoltages in a Distribution System,” IEEE Transactions on Power Delivery, vol. 17, no. 2, pp. 569–574, April 2002.

Check the top of your arrester and make sure you have the proper size for the voltage. Some times they look alike. Don't assume, it ain’t good for your Fruit of the Looms.

Anonymous poster, on a near miss when a 3-kV arrester was mistakenly installed instead of a 10-kV arrester (7.2 kV line to ground)