4.10.1Acc/Dec Time Based on Maximum Frequency

Acc/Dec time values can be set based on maximum frequency, not on inverter operation frequency. To set Acc/Dec time values based on maximum frequency, set bA. 08 (Acc/Dec reference) in the Basic group to 0 (Max Freq).

Acceleration time set at the ACC (Acceleration time) code in the Operation group (dr.03 in an LCD keypad) refers to the time required for the inverter to reach the maximum frequency from a stopped (0Hz) state. Likewise, the value set at the dEC (deceleration time) code in the Operation group (dr.04 in an LCD keypad) refers to the time required to return to a stopped state (0Hz) from the maximum frequency.

Group Code Name LCD Display Parameter Setting Setting Range Unit Operation

ACC Acceleration time Acc Time 20.0 0.0–600.0 sec dEC Deceleration time Dec Time 30.0 0.0–600.0 sec 20 Maximum

frequency Max Freq 60.00 40.00–400.00 Hz

bA 08

Acc/Dec reference

frequency Ramp T Mode 0 Max Freq 0–1 - 09 Time scale Time scale 1 0.1sec 0–2 -

Acc/Dec Time Based on Maximum Frequency – Setting Details

Code Description

bA.08 Ramp T Mode

Set the parameter value to 0 (Max Freq) to setup Acc/Dec time based on maximum frequency.

Configuration Description

0 Max Freq Set the Acc/Dec time based on maximum frequency.

1 Delta Freq Set the Acc/Dec time based on operating frequency.

If, for example, maximum frequency is 60.00Hz, the Acc/Dec times are set to 5 seconds, and the frequency reference for operation is set at 30Hz (half of 60Hz), the time required to reach 30Hz therefore is 2.5 seconds (half of 5 seconds).

bA.09 Time scale

Use the time scale for all time-related values. It is particularly useful when a more accurate Acc/Dec times are required because of load characteristics, or when the maximum time range needs to be extended.

Configuration Description

0 0.01sec Sets 0.01 second as the minimum unit. 1 0.1sec Sets 0.1 second as the minimum unit. 2 1sec Sets 1 second as the minimum unit.

Note that the range of maximum time values may change automatically when the units are changed. If for example, the acceleration time is set at 6000 seconds, a time scale change from 1 second to 0.01 second will result in a modified acceleration time of 60.00 seconds.

Max. Freq.

Frequency Run cmd

4.10.2Acc/Dec Time Based on Operation Frequency

Acc/Dec times can be set based on the time required to reach the next step frequency from the existing operation frequency. To set the Acc/Dec time values based on the existing operation frequency, set bA. 08 (acc/dec reference) in the Basic group to 1 (Delta Freq).

Group Code Name LCD Display Parameter Setting Setting Range Unit Operation ACC Acceleration time Acc Time 20.0 0.0–600.0 sec

dEC Deceleration time Dec Time 30.0 0.0–600.0 sec bA 08 Acc/Dec reference Ramp T Mode 1 Delta Freq 0–1 -

Acc/Dec Time Based on Operation Frequency – Setting Details

Code Description

bA.08 Ramp T Mode

Set the parameter value to 1 (Delta Freq) to set Acc/Dec times based on Maximum frequency.

Configuration Description

0 Max Freq Set the Acc/Dec time based on Maximum frequency.

1 Delta Freq Set the Acc/Dec time based on Operation frequency.

If Acc/Dec times are set to 5 seconds, and multiple frequency references are used in the operation in 2 steps, at 10Hz and 30 Hz, each acceleration stage will take 5 seconds (refer to the graph below).

4.10.3Multi-step Acc/Dec Time Configuration

Acc/Dec times can be configured via a multi-function terminal by setting the ACC (acceleration time) and dEC (deceleration time) codes in the Operation group.

Group Code Name LCD Display Parameter Setting Setting Range Unit Operation ACC Acceleration time Acc Time 20.0 0.0–600.0 sec

dEC Deceleration time Dec Time 30.0 0.0–600.0 sec

bA

70–82 Multi-step

acceleration time1–7 Acc Time 1–7 x.xx 0.0–600.0 sec 71–83 Multi-step

deceleration time1–7 Dec Time 1–7 x.xx 0.0–600.0 sec

In 65–69 Px terminal configuration Px Define (Px: P1–P5) 11 XCEL-L 0~54 - 12 XCEL-M 49 XCEL-H 89 Multi-step command

delay time In Check Time 1 1–5000 ms

Acc/Dec Time Setup via Multi-function Terminals – Setting Details

Code Description

bA. 70–82 Acc Time 1–7 Set multi-step acceleration time1–7. bA.71–83 Dec Time 1–7 Set multi-step deceleration time1–7.

In.65–69

Px Define (P1–P5)

Choose and configure the terminals to use for multi-step Acc/Dec time inputs.

Configuration Description

11 XCEL-L Acc/Dec command-L 12 XCEL-M Acc/Dec command-M 49 XCEL-H Acc/Dec command-H

Acc/Dec commands are recognized as binary code inputs and will control the acceleration and deceleration based on parameter values set with bA.70–82 and bA.71–83.

If, for example, the P4 and P5 terminals are set as XCEL-L and XCEL respectively, the following operation will be available.

Code Description Acc/Dec time P5 P4 0 - - 1 -  2  - 3  

In.89 In Check Time

Set the time for the inverter to check for other terminal block inputs. If In.89 is set to 100ms and a signal is supplied to the P4 terminal, the inverter searches for other inputs over the next 100ms. When the time expires, the Acc/Dec time will be set based on the input received at P4.

4.10.4Configuring Acc/Dec Time Switch Frequency

You can switch between two different sets of Acc/Dec times (Acc/Dec gradients) by configuring the switch frequency without configuring the multi-function terminals.

Group Code Name LCD Display Parameter Setting Setting Range Unit Operation ACC Acceleration time Acc Time 10.0 0.0–600.0 sec

dEC Deceleration time Dec Time 10.0 0.0–600.0 sec bA

70 Multi-step

acceleration time1 Acc Time-1 20.0 0.0–600.0 sec 71 Multi-step

deceleration time1 Dec Time-1 20.0 0.0–600.0 sec Ad 60 Acc/Dec time switch

frequency Xcel Change Frq 30.00 0–Maximum frequency Hz P4 P5 Frequency Acc0 Acc1 Acc2 Acc3 Dec0 Dec1 Dec2 Dec3 Run cmd

Acc/Dec Time Switch Frequency Setting Details

Code Description

Ad.60 Xcel Change Fr

After the Acc/Dec switch frequency has been set, Acc/Dec gradients configured at bA.70 and 71 will be used when the inverter’s operation frequency is at or below the switch frequency. If the operation frequency exceeds the switch frequency, the configured gradient level, configured for the ACC and dEC codes, will be used. If you configure the P1–P5 multi-function input terminals for multi-step Acc/Dec gradients (XCEL-L, XCEL-M, XCEL-H), the inverter will operate based on the Acc/Dec inputs at the terminals instead of the Acc/Dec switch frequency configurations.