Testing the 2-LCD To test the 2-LCD:
1. Verify that the 2-LCD is properly mounted and secured. 2. Verify the proper seating of the ribbon cable between the 2-
LCD and the Main Controller Module.
3. Verify that the 2-LCD displays the correct date and time and that its Power LED is on.
4. Press the Trouble Silence and Alarm Silence switches simultaneously to perform the lamp test function. 5. Verify that each function switch performs according to
specification.
Note: See the System Operations Manual for 2-LCD switch functions.
Verifying the installation of panel components
To verify the proper installation of panel components:
1. Make sure that all ribbon cables are firmly seated in their connectors and that all wiring is secure.
2. Verify that all components are installed according to the specifications of the job.
Verifying 2-LCD message queues
During this phase of the system test, you will need to initiate several off-normal conditions. The off-normal conditions will test the 2-LCD’s handling of messages in its queue. The message queue test requires:
• 4 Alarm tests
• 1 Monitor condition test • 2 Supervisory condition tests • 2 Trouble condition tests
To run the first fire alarm test:
1. Initiate a fire alarm.
2. Check the 2-LCD to see if the internal buzzer sounds and the Alarm LED flashes.
3. Verify that the 2-LCD message for the alarm matches the programmed message in the 2-SDU.
4. Press the Local Silence switch to verify that it silences the buzzer, stops the Alarm LED from flashing (but keeps it lit), and turns on the Local Silence LED.
5. Press the Alarm Review switch to verify that you can scroll through all the messages in the alarm queue.
6. Press the Alarm Silence switch to verify that it silences the active notification appliances.
7. Print a history report to verify that all of the information appears on the printer.
To run the second fire alarm test:
1. Initiate a second fire alarm.
2. Check the 2-LCD to see if the internal buzzer sounds and the Alarm LED turns on.
3. Verify that the 2-LCD message for the alarm matches the programmed message in the 2-SDU.
4. Press the Local Silence switch to verify that it silences the buzzer, stops the Alarm LED from flashing (but keeps it lit), and turns on the Local Silence LED.
5. Press the Alarm Review switch to verify that you can scroll through all the messages in the alarm queue.
To run the third fire alarm test:
1. Initiate a third fire alarm.
2. Check the 2-LCD to see if the internal buzzer sounds and the Alarm LED turns on.
3. Verify that the 2-LCD message for the alarm matches the programmed message in the 2-SDU.
4. Press the Local Silence switch to verify that it silences the buzzer, stops the Alarm LED from flashing (but keeps it lit), and turns on the Local Silence LED.
5. Press the Alarm Review switch to verify that you can scroll through all the messages in the alarm queue.
6. Press the Reset switch.
7. Verify that all initiating devices reset and all panel indicators clear except the green Power LED.
To run a monitor condition test:
1. Initiate a monitor condition.
2. Verify that the 2-LCD Monitor LED turns on. 3. Verify that the internal buzzer does not sound. 4. Restore the monitor point.
To run a trouble test:
1. Initiate an active trouble condition.
2. Check the 2-LCD to see if the internal buzzer sounds and the Trouble LED flashes.
3. Verify that the 2-LCD message for the trouble condition matches the programmed message in the 2-SDU.
4. Press the Local Silence switch to verify that it silences the buzzer, stops the Trouble LED from flashing (but keeps it lit), and turns on the Local Silence LED.
5. Press the Trouble Review switch to verify that you can scroll through all the messages in the trouble queue. 6. Restore the trouble condition.
7. Press the Reset switch at the 2-LCD.
To complete the trouble test:
1. Initiate a second active trouble condition.
2. Verify that the second trouble message appears in the display.
3. Restore the trouble point.
4. Press the Reset switch at the 2-LCD.
To run a supervisory test:
1 Initiate an active supervisory condition.
2. Check the 2-LCD to see if the internal buzzer sounds and the Supervisory LED flashes.
3. Verify that the 2-LCD message for the supervisory condition matches the programmed message in the 2-SDU.
4. Press the Local Silence switch to verify that it silences the buzzer, stops the Supervisory LED from flashing (but keeps it lit), and turns on the Local Silence LED.
5. Press the Supervisory Review switch to verify that you can scroll through all the messages in the supervisory queue. 6. Restore the supervisory condition.
7. Press the Reset switch at the 2-LCD.
To complete the supervisory test:
1. Initiate a second active supervisory condition.
2. Verify that the second supervisory message appears in the display.
3. Restore the supervisory point. 4. Press the Reset switch at the 2-LCD.
To run the fourth fire alarm test:
1. Initiate a fourth fire alarm.
2. Check the 2-LCD to see if the internal buzzer sounds and the Alarm LED turns on.
3. Verify that the 2-LCD message for the alarm matches the programmed message in the 2-SDU.
4. Press the Local Silence switch to verify that it silences the buzzer, stops the Alarm LED from flashing (but keeps it lit), and turns on the Local Silence LED.
5. Press the Alarm Review switch to verify that you can scroll through all the messages in the alarm queue.
6. Press the Reset switch.
7. Verify that all initiating devices reset and all panel indicators clear except the green Power LED.