Select option 3 from the Event Log menu, the following type of screen will be displayed:
It is possible to view and to print the events of single categories. The category is selected by pressing the appropriate option number. It is also possible to select several categories, the selected categories are denoted by a ‘+’ sign.
Press F4 to view the selected categorie(s) as described in Section 3.8.1 or F5 to print the selected category(s) as described in Section 3.8.2.
Lowest Priority Information Only
. Level 2
. Expected Events
. Isolates
. Warnings
. Visible Isolate
. Other Faults
. Critical Faults
. Gas Alert
. Alarm Threshold
. Non-Life Risk
. Level 12
. Life Risk Alarms
Highest Priority General Alarm
1 Fire
Allows the following options to be viewed/printed. On networked systems, the status of any panel on the network may be viewed/printed:
Points Isolated
Points Untested/Failed (during Walk Test)
Point Values
View Faults (no print option)
Loop Point Counters (no print option)
Select option 6 from the Main menu, the following type of screen will be displayed:
4.10.1 VIEW/PRINT POINTS ISOLATED
Select option 1 from the View/Print Status menu, the following type of screen will be displayed:
If the panel is part of a networked system, another screen is displayed before the above screen where the panel number may be selected.
1 - Points Isolated 2 - Pts Unt./Failed 3 - Point Values 4 - View Faults 5 - Loop Point Ctrs 7 - Active Points 8 - By Function
Press F5 ‘Print’ to print a list of all isolated points.
The F2 Key selects either isolated inputs or isolated outputs.
Points which are completely isolated (input and output) will be shown in both lists.
4.10.2 VIEW/PRINT POINTS UNTESTED/
FAILED
This option only works whilst still in Walktest.
Select option 2 from the View/Print Status menu, the following type of screen will be displayed:
If the panel is part of a networked system, another screen is displayed before the above screen where the panel number may be selected.
Press F5 to print the Untested/Failed points.
Points which are not tested or points which return the wrong condition are then listed.
Total : 004 Zone 001 -001 B Point Text
---Zone 001 -002 B Point Text
MX Panel Thu, 26-Jul-07 14:15 Company Name
General
Back
Pts Untested/Failed
4.10.3 VIEW/PRINT POINT VALUES
Select option 3 from the View/Print Status menu, the following type of screen will be displayed:
Select the panel number (if the panel is part of a networked system), loop and point number required.
‘>>’ - next field
‘_’ - the number is decremented
‘+’ - the number is incremented
Pressing F5 displays the following screen:
Press F5 to print the Point Values of the selected loop (not only the displayed point).
Panel 02
Loop Point A 002 MX Panel
Thu, 26-Jul-07 14:15 Company Name
General
Back
Point Values
Enter
>> - +
Zone 002 B002 South Building 1st Floor Corridoor Room 117
801H
Real: 801 H (020) Mode: 1 Sens.: 0 20 C (032) MX Panel
Thu, 26-Jul-07 14:15 Company Name
General
Back
Point Values
o
4.10.4 VIEW FAULTS
Select option 4 from the View/Print Status menu, the following type of screen will be displayed:
This option is view only.
4.10.5 VIEW LOOP POINT COUNTERS
This option is view only. Select option 5 from the View/Print Status menu, the following screen will be displayed:
Only the Loop will be shown if the panel is not networked.
Select the required panel (only if the panel is networked) and loop, then press the Enter key. The following message is displayed:
Please Wait...
for approximately 2 minutes until the count is complete, if no faults are found, the following type of screen will be displayed:
Total : 002 Zone 000 R10 Zone 000 R12 MX Panel
Wed, 01-Jan-08 14:15 Company Name
Flt P 002
General
Back
View Faults
Panel 02 Loop A MX Panel
Thu, 26-Jul-07 14:15 Company Name
General
Back
Loop Point Counters
>> - + Enter
Configured - the number of points configured.
Conditions for ‘PASSED’
The number of configured points is equal the detected count of points on the loop.
There are no unconfigured points.
Detected points from left, right and both sides are equal.
If all conditions are not satisfied, the ‘ATTENTION’ screen will be displayed showing the relevant counters.
Configured - the number of points configured.
Conf & Ident - shows how many points are connected, identified and configured on the loop.
Not Conf. - shows how many points were identified on the loop but not configured.
Both Sides/Left Side/Right Side - Shows how many points on the loop are recognised by the panel. ‘Left Side’ and ‘Right Side’ is the count from both sides. ‘Both Sides’ means the detection of a closed loop.
If the value of ‘Conf & Ident’ is different to the number of installed devices, multiple reserved address may be the cause.
Counter
Back Details Scan
Counter Loop : A
A T T E N T I O N Configured : 010 Conf. & Ident: 009 MX Panel
Loop Point Counters
Details Scan
4.10.5.1 DETAILS
Press the ‘Details’ key (F2), the following type of screen will be displayed:
All 250 addresses may be displayed using the ‘>>’ key.
The connection detail of each point is shown by the following symbols:
Function key F2 scrolls through the loop.
4.10.5.2 SCAN
Press the ‘Scan’ key (F3), the following type of screen will be displayed:
The points are shown which were detected from both sides (Left/Right).
They are displayed as follows:
o OK: point connected, configured and identified (eg, point 33 and points 60 to 64) Point was configured but not connected or identified (eg, point 21)
Point was not configured but connected (eg, point 6)
Loop Point Counters
>>
Details Loop : A
Point 0123456789 0 : ...u...
Loop Point Counters
>>
Left / Right Scan Loop : A
Point 0123456789
0 : ....l ...
Function key F2 scrolls through the loop.
4.10.6 ACTIVE POINTS
Select option 7 from the View/Print Status Menu. The following type of screen will be displayed:
4.10.6.1 FIRE INPUTS
Select option 1 from the Active Points menu, the following screen will be displayed:
Empty (not used)
OK: detected from both sides (eg, points 33 and 82)
Only detected from left side (eg, points 4 and 21)
Only detected from right side (eg, 60 to 64) .
* l r
1 - Fire Inputs 2 - Non-Fire Inputs 3 - Loop Outputs 4 - Sounders MX Panel
Wed, 01-Jan-08 14:15 Company Name
General
Back
Active Points
MX Panel Wed, 21-Aug-07 08:01 Company Name
General
Back
Active Points
Current active pts.
Total : 0
Iso&Act Print
Pressing Iso&Act (F2) will display the following screen:
Pressing Iso&For (F2) will display the following screen:
4.10.7 BY FUNCTION
Select option 8 from the View/Print Status Menu. The following type of screen will be displayed:
Screens for options 2, 3 and 4 are the same type as for option 1 Fire Inputs.
MX Panel Isolated active pts Total : 0 Isolated active pts Total : 0 2 - Non-Fire Inputs 3 - Loop Outputs 4 - Sounders
5 - Protection Eqp.
6 - Plant Equipment
4.10.7.1 FIRE INPUTS
Select option 1 from the By Function menu, the following screen will be displayed:
Select option 1 from the Fire Inputs menu, the following screen will be displayed:
Select option 2 from the Fire Inputs menu, the following screen will be displayed:
Select option 3 from the Fire Inputs menu, the following screen will be displayed: 3 - Isolated
MX Panel
Active Fire IPs
Fire IPs in Fault
Panel: 1 Total : 0 Page : 0/ 0
4.11 SERVICE
Press 7 from the Main menu. The following type of screen will be displayed:
The Maintenance and Diagnostics options are only available at Customer Manager level and will not be displayed for lower levels.
4.11.1 WALK TEST
When selected, this option allows single or multiple points to be tested without an alarm being raised.
Press 1 from the Service menu.
Only one Walk Test session can be active at one time.
MX Panel Wed, 21-Aug-07 08:01 Company Name
General
Back
Isolated Fire IPs
Panel: 1 Total : 0 Page : 0/ 0
1 - Walk Test 2 - Maintenance MX Panel
Wed, 09-Aug-08 00:01 Company Name
General
Back
Service
Use the ‘>>’, ‘-’ and ‘+’ keys to select the required options. The Panel number is only displayed when it is part of a networked system.
Depending on the selected settings, the display will change. The following screen is an example of ‘Area’ selected as ‘Point’.
To start the Walk Test press F5.
Possible Settings Panel
Panel selection is only available for panels that are in a networked system.
Area
All Walk Test of all elements of a specific type.
(Selection in the field ‘Type’ eg, callpoints).
Zone Walk Test of all elements of a specific type in a special zone.
Point Walk Test of the input of a single point.
Panel : 01 Area : All Type : Input Loop : All
Mode : MANUAL Multisensor : Part MX Panel Multisensor : Part MX Panel
Type
Loop
Only with Area as ‘All’ or ‘Zone’.
Walk Test of all loops or of a specific loop (A, B, C or D).
Location
Only with Area selected as ‘Point’.
Zone
Only with Area selected as ‘Point’.
Point
Only with Area selected as ‘Point’.
Selection of a specific zone is possible.
Mode MANUAL
Detectors to be tested manually.
AUTOMATIC
Only if type selected is ‘detector’
813P
This mode is only available if an 813P detector is configured. If an 813P detector fails this test, it must be manually tested to confirm the failure.
Multisensor
It is only possible to select either ‘Automatic’, ‘Lasertest’ or
‘Multisensor. The panel itself prevents selection of more than one option.
Input Walk Test of all inputs.
Detectors Walk Test of detectors.
Alarm I/Ps Walk Test of default inputs covered by supergroup ‘Fire Alarm Inputs SG’.
Call Points Walk Test of call points.
Sounders Walk Test of sounders by loop or all loops plus FIM sounders.
Loop A point on the loop.
Loop Selection of a specific zone is possible.
Self test will be carried out by detectors.
The following detectors support the self test function:
801PH 801CH 801I
801PHEx 801CHEx
Full
Part
(eg, both heat and optical mode for 801PH).
If ‘Part’ Walk Test is selected, the detector has to be activated in the mode in which it is operating (eg, for 801PH optical and heat, both modes active, then activation of either the optical or heat will activate the processing. If only the heat mode is active, then only activation of the heat mode will create an alarm.
4.11.1.1 ALL INPUTS Select the following settings:
Area: All
Type: Input
Loop: All
Press F5 to start the Walk Test.
The following screen shows an example for the Walk Test ‘All Inputs’ option:
Press F3 to display selected settings.
Press F5 to end Walk Test.
CAUTION:
THE FINISHING OF A WALK TEST IS ONLY POSSIBLE IF ALL POINTS IN THE WALK TEST ARE INACTIVE.
Selected: Number of points selected by the test.
Excluded: Number of Points not in Walk Test (ie, points isolated).
Been Active: Number of points which have been activated during Walk Test.
Been Clear: Number of points which were not active when starting Walk Test.
Successful: Number of tested points.
Curr.Active: Points which are currently active.
TestZ: Number of zones which are in Walk Test. The pointer is only counted if all points in a zone are in Walk Test.
All Inputs
Select ‘Sounders’ in the Type field.
No results will be shown on the display. The selected sounders will be activated in a pulsing mode.
4.11.1.3 POINT
Select the following settings:
Press F5 to start the Walk Test.
The following screen shows an example for the Walk Test of ‘Point Input’:
Press F3 for a display of selected settings.
Press F5 to end Walk Test.
CAUTION:
THE FINISHING OF A WALK TEST IS ONLY POSSIBLE IF ALL POINTS IN THE WALK TEST ARE INACTIVE.
Area: Point.
Type: Input (appears automatically).
Location: Loop (appears automatically).
Zone: Required number.
Point: Required number.
Selected: 1, if point is in Walk test.
Excluded: 1, if point is not in Walk Test (ie, if point is isolated).
Activations: 1, if point was activated during Walk Test.
Curr.Active: Yes, if point is currently active.
TestZ 001 Number of zones which are in Walk Test. (The pointer is only counted if all points of a zone are in Walk Test. If one detector on the zone is switched off, the pointer is not decreased. In the case of Walk Test for one point, the pointer is only decreased if that point is the only point on the zone).
Point I/P only Zone 006 A007 Zone 06
Call alarm in room CP820
4.11.2 MAINTENANCE
Press 2 from the Service menu. The following type of screen will be displayed:
4.11.2.1 VIEW FIRE ALARM CYCLE COUNT
When selected, the number of Alarm sequences may be viewed.
Press 1 from the Maintenance menu. The following type of screen will be displayed:
4.11.2.2 VIEW/PRINT MAINTENANCE REQUEST
When selected, this option displays a list of detectors which are near the limit of their threshold compensation limit.
Press 3 from the Maintenance menu. The following type of screen will be displayed:
1 - Fire Cycle Count 3 - Maint. Request 4 - Battery Test 6 - Project Numbers 7 - S/W Versions 9 - Menu Points MX Panel
Wed, 01-Mar-08 14:15 Company Name
General
Back
Maintenance
Count : 0025 MX Panel
Wed, 01-Mar-08 14:15 Company Name
General
Back
Fire AL.Cycle Count
Press F5 to print the Maintenance Request.
4.11.2.3 BATTERY TEST
When selected, this option allows the state of the battery and the charger current to be displayed.
Press 4 from the Maintenance menu. The following type of screen will be displayed:
4.11.2.4 PROJECT NUMBERS
When selected, this option allows the project and MX CONSYS information to be displayed.
Press 6 from the Maintenance menu. The following type of screen will be displayed:
Battery Voltage : 20.764 V
Charger Current : 00.500 A
Queen El. Hospital Consys: V10.0 Version: 34 Created:
21-Jul-07 10:18 Downloaded:
4.11.2.5 SOFTWARE VERSIONS
When selected, the software versions of the following are displayed:
Firmware
Local I/O
Each Loop
Each MPM
Network card (if fitted)
Press 7 from the Maintenance menu. The following type of screen will be displayed:
Press F5(+) for additional details of the software versions.
4.11.2.6 MENU POINTS
When selected, this option allows any configured point displayed to be operated by pressing the appropriate number button, this will toggle from OFF to ON and ON to OFF.
Press 9 from the Maintenance menu. The following type of screen will be displayed:
Press 8 from the Main menu. The following screen will be displayed:
‘Menu option 9- Restart’ will only be displayed if text has been changed and the changes saved.
RESTRICTIONS ON THE USE OF THE FOLLOWING OPTION
When using Configuration menu option 1, ALWAYS commit configuration changes by using ‘Menu option 9 - Restart’ before leaving the panel.
Avoid ‘inactivity’ timeouts.
NEVER use the ‘Back’ option from the configuration menu if ‘Menu option 9 - Restart’ is showing.
If you do not want to commit changes, by using ‘Menu option 9 - Restart’, option, turn the keyswitch to ‘OFF’ position to avoid a timeout situation, do NOT USE the ‘Back’ option.
Configuration changes across a network are possible, but changes to more than one panel at a time MUST NOT be attempted within one
session. When a panels configuration has been changed, it must be restarted using menu option 9 ‘Restart’.
Failure to comply with these restrictions may lead to unpredictable effects or system instability.
4.11.3.1 CHANGE TEXT
Press 1 from the Configuration menu. The following screen will be displayed:
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Configuration 1 - Change Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Change Text
1 - Point Text
2 - Zone Text
3 - Sector Text
4 - Panel Text
5 - Info Text
4.11.3.2 POINT TEXT MODIFY
Press 1 from the Change Text menu. The following screen will be displayed:
Select the required loop and point then press Enter. The following type of screen will be displayed:
‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.
Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter.
Pressing the scroll up key allows text to be entered in upper case.
Pressing the scroll down key changes to lower case text.
The message ‘Save Data?’ appears and the functions change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed.
Selecting F4 ‘Yes’ displays the message:
Please wait...
then the following screen is displayed:
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Point Text Modify Loop : A Point : 001
>> - + Enter
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Point Text Modify Zone 255 -007 A Old text
Callp. alarm room New text
>> - + Enter
It is now possible to change the text for another Point.
Selecting F1 ‘Back’ will display the following screen:
Only ‘Change Text’ and ‘Restart’ are available allowing more points to be changed or using ‘Restart’ to allow the changes to take effect.
4.11.3.3 ZONE TEXT MODIFY
Press 2 from the Configuration menu. The following screen will be displayed:
Select the required and press Enter. The following type of screen will be displayed:
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Change Text 1 - Point Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Configuration 1 - Change Text
9 - Restart
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Zone Text Modify
Zone : 001
- + Enter
‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.
Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter.
The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed.
Selecting F4 ‘Yes’ displays the message:
Please wait...
then the following screen is displayed:
It is now possible to change the text for another Zone.
Selecting F1 ‘Back’ will display the following screen:
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Zone : 001 Old text
Zone 01 New text
>> - + Enter
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Change Text 2 - Zone Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Configuration 1 - Change Text
9 - Restart
Only ‘Change Text’ and ‘Restart’ are available allowing more points to be changed or using ‘Restart’ to allow the changes to take effect.
4.11.3.4 SECTOR TEXT MODIFY
Press 3 from the Configuration menu. The following screen will be displayed:
Select the required sector, then press Enter. The following type of screen will be displayed:
‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.
Modify the old text or insert new text using the alphanumeric keypad, when finished press Enter.
The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and F5 to ‘No’. Selecting F5 allows the text modifications to be changed.
Selecting F4 ‘Yes’ displays the message:
Please wait...
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Sector Text Modify
Sector : 001
- + Enter
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Sector Text Modify Sector 001 Old text
Sector 01 New text
>> - + Enter
then the following screen is displayed:
It is now possible to change the text for another Sector.
Selecting F1 ‘Back’ will display the following screen:
4.11.3.5 PANEL TEXT MODIFY
Press 4 from the Configuration menu. The following screen will be displayed:
Select the required Panel.
‘>>’ - copies the ‘old text’ to the ‘New text’ position.
‘-’ moves the cursor back one position.
‘+’ moves the cursor forward one position.
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Change Text
3 - Sector Text
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Configuration 1 - Change Text
9 - Restart
MX Panel Wed, 01-Mar-08 14:15 Company Name
General
Back
Panel Text Modify Panel 00 Old Text
ADT New Text
Enter
>> - +
finished press Enter.
The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and
The message ‘Save Data?’ appears and the function change F4 to ‘Yes’ and