External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
960 1056 0.66 1090 0.71 1123 0.78 1156 0.84 1188 0.90
1080 1096 0.76 1128 0.82 1159 0.88 1190 0.94 1220 1.00
1200 1135 0.87 1168 0.93 1199 1.00 1229 1.07 1259 1.13
1320 1177 0.98 1209 1.06 1241 1.14 1270 1.21 1299 1.28
1440 1217 1.10 1250 1.18 1281 1.27 1311 1.35 1339 1.43
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-85. Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table PD-88 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK69 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-59 — Belt Drive Evaporator Fan Performance — 3 Ton — YHC036A3,A4,AW*H — High Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive
Low Static Drive (1)
960 563 0.13 639 0.18 707 0.23 766 0.28 817 0.33 864 0.39 908 0.44 947 0.49 985 0.55 1020 0.60
1080 611 0.18 685 0.23 748 0.28 806 0.34 858 0.39 905 0.45 947 0.51 988 0.58 1026 0.64 1061 0.70
1200 660 0.23 732 0.29 792 0.34 847 0.40 899 0.46 945 0.53 989 0.59 1029 0.66 1066 0.73 1102 0.80
1320 711 0.29 781 0.36 838 0.42 890 0.48 940 0.55 986 0.61 1029 0.68 1070 0.76 1106 0.83 1142 0.90
1440 762 0.37 829 0.44 885 0.51 935 0.57 983 0.64 1028 0.71 1070 0.79 1111 0.86 1148 0.94 1183 1.02
Performance
Data
(4 Ton)
High Efficiency
Table PD-60 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive Low Static Drive (1)
1280 614 0.22 675 0.26 733 0.31 787 0.37 834 0.42 878 0.48 919 0.53 959 0.59 997 0.65 1034 0.71 1440 676 0.30 731 0.34 784 0.39 835 0.46 883 0.52 925 0.58 965 0.64 1003 0.70 1039 0.76 1075 0.83 1600 739 0.40 789 0.45 838 0.50 885 0.56 931 0.63 973 0.70 1012 0.77 1049 0.84 1085 0.91 1118 0.97 1760 803 0.51 850 0.57 894 0.63 938 0.69 981 0.76 1021 0.83 1061 0.92 1097 0.99 1131 1.07 1164 1.14 1920 867 0.65 911 0.72 952 0.78 993 0.84 1033 0.91 1071 0.99 1110 1.07 1145 1.16 1180 1.25 1213 1.33
Table PD-60 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1069 0.77 1104 0.83 1138 0.90 1170 0.97 1203 1.04
1440 1109 0.89 1141 0.96 1175 1.03 1205 1.10 1236 1.17
1600 1151 1.04 1183 1.11 1215 1.19 1246 1.26 1275 1.33
1760 1197 1.21 1227 1.29 1258 1.36 1287 1.44 — —
1920 1243 1.41 1274 1.49 — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-89 to determine additional static pressure drop due to other options/accessoriesdue to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-61 — Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*H — High Heat — Downflow Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Field Supplied 1-HP Standard Motor & Drive Low Static Drive (1)
1280 627 0.23 688 0.27 745 0.32 797 0.38 844 0.43 887 0.49 928 0.54 967 0.60 1006 0.66 1042 0.72 1440 691 0.31 746 0.36 798 0.41 848 0.47 894 0.54 936 0.60 975 0.66 1012 0.72 1049 0.78 1085 0.85 1600 756 0.41 806 0.47 854 0.52 901 0.58 945 0.66 987 0.73 1025 0.79 1061 0.86 1096 0.93 1129 1.00 1760 822 0.54 868 0.60 912 0.65 955 0.71 997 0.79 1038 0.87 1076 0.95 1111 1.02 1145 1.10 1178 1.17 1920 889 0.69 931 0.75 972 0.81 1012 0.88 1051 0.95 1090 1.03 1127 1.11 1162 1.20 1196 1.29 1228 1.37
Table PD-61 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1077 0.78 1112 0.85 1145 0.91 1178 0.98 1210 1.05
1440 1118 0.91 1150 0.98 1183 1.05 1214 1.12 1244 1.19
1600 1162 1.06 1193 1.13 1225 1.21 1255 1.28 1285 1.36
1760 1208 1.24 1239 1.32 1268 1.39 1297 1.47 — —
1920 1258 1.45 — — — — — — — —
1-HP Standard Motor & Field Supplied High Static Drive (2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.
2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
(4 Ton)
High Efficiency
Performance
Data
Table PD-62— Belt Drive Evaporator Fan Performance — 4 Ton — YHC048A3,A4,AW*L,M — Low and Medium Heat — Horizontal Airflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor &
Field Supplied Low Static Drive (1) 1-HP Standard Motor & Drive
1280 681 0.26 755 0.32 816 0.38 870 0.45 921 0.51 968 0.58 1013 0.65 1053 0.72 1091 0.79 1127 0.86
1440 748 0.36 817 0.43 876 0.49 927 0.56 976 0.63 1022 0.70 1065 0.78 1106 0.85 1144 0.93 1180 1.01
1600 816 0.47 879 0.55 937 0.62 987 0.70 1033 0.78 1076 0.85 1119 0.93 1158 1.01 1197 1.10 1233 1.18
1760 885 0.61 943 0.69 999 0.78 1049 0.86 1093 0.94 1135 1.03 1174 1.11 1213 1.20 1250 1.29 1286 1.38
1920 956 0.77 1009 0.86 1062 0.96 1110 1.05 1154 1.14 1195 1.23 1232 1.32 1269 1.41 1304 1.50 — —
For Standard Evaporator Fan Speed (RPM), reference Table PD-86. Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table PD-89 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary. 2. Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
1-HP Standard Motor & Field Supplied High Static Drive (2)
Table PD-62 — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-HP Standard Motor & Drive
1280 1162 0.94 1193 1.01 1225 1.09 1255 1.16 1284 1.23
1440 1214 1.09 1247 1.18 1278 1.26 1309 1.35 1337 1.43
1600 1268 1.27 1300 1.35 1332 1.45 — — — —
1760 1320 1.47 — — — — — — — —
1920 — — — — — — — — — —