Description

The NBG-12LX Addressable pull station is a non-coded, dual- action manual pull station with a key-lock reset feature. It provides NOTIFIER intelligent control panels with one addres- sable alarm initiating input. The addressable module is housed inside the pull station. The NBG-12LX is compatible with all Notifier intelligent panels and will automatically operate in either FlashScan™ or CLIP (Classic Loop Interface Protocol) mode. FlashScan™ is a patented (U.S. Pat. No. 5,539,389) High Speed Communications Protocol. Refer to the FACP Installation Manual to determine if FlashScan™ protocol is supported. FlashScan™ or CLIP operating mode must be selected in the FACP. (This selection is not available or required in FACPs that do not support FlashScan™, therefore CLIP mode is enabled by default.) No selection is required in the Pull Station. The NBG-12LX meets the ADA requirement for a 5-lb. maximum pull force to activate the pull station. Operating instructions are molded into the pull station handle along with Braille text. Molded Terminal numbers are also present.

Ratings

Normal Operating Voltage: 24 VDC.

Average Operating Current (LED Flash): 300 µA. Temperature Range: 32o F - 120o F (0o C - 49o C). Relative Humidity Range: 10% - 93% non-condensing.

Document 51093 Revision A2 ECN: 01-293 09/14/01

Installation

The NBG-12LX Addressable pull station can be surface mounted to a NOTIFIER SB-10 surface backbox or semi-flush mounted on a standard single-gang, double-gang or 4” (10.16 cm) square electrical box. The optional BG-TR trim ring can be used if the NBG-12LX is to be semi-flush mounted.

‘mpul’. If you have an older system that does not support the ‘mpul’ software type, the software type ‘mon’ may be used.

If, during mounting of the pull station, the door becomes de- tached, complete the following steps to reattach the door to the backplate. The door cannot be connected to the pull station if the unit is mounted to the backbox.

1) Position the door and backplate side by side in the full open position. (i.e. 180-degrees with respect to each other.) 2) With the backplate position fixed, move the door behind the

backplate, as shown in the illustration, part A.

3) Align the hinge posts and holes by bringing the door up to meet the backplate, paying particular attention to the ‘keying’ that occurs when the door’s post hole is aligned to the backplate’s hinge post. Refer to the illustration, part B. 4) With the two pieces aligned and ‘keyed’ together, slide the holes

down onto the posts. Refer to the illustration, part C. 5) Holding the backplate, close the door slightly to lock the door

and backplate together.

To use the NBG-12LX with panels capable of supporting up to 159 addresses, pry off the ‘break-away’ address block using a flat- bladed screwdriver. The break-away piece is illustrated below.

ROTARY ADDRESS SWITCHES LED

LOOP

N O T I F I E R

NBG - 12 Series

NON-C ODED FIRE ALARM BOX LISTED

23424 REFER TO DOC UMENT

Made in U. S. A.

M AD DRESS

L U

PRODUCT IDENTIFICATION LABEL

ro t s w itc h 9- 13 .c dr , l ab el _1 .cd r, ro ta ry b ox.c dr N B G 12-F ac e2 .cd r

www.PDF-Zoo.com

P/N 50997 REV. REFER TO DOCUMENT NUMBER 51015 REV. LOOP ADDRESS    ! P/N 50997 REV. REFER TO DOCUMENT NUMBER 51015 REV. LOOP ADDRE SS    ! " ' + * ) POST

DOOR ‘KEYS’ INTO BACKPLATE AT THIS POINT

POST POST

HOLE

HOLE

Operation

Push in and pull down the handle where indicated to activate the station. The NBG-12LX manual fire alarm pull station includes one SPST (Single Pole, Single Throw) N/O (normally-open) switch and the addressable module located inside the station. Pushing in and pulling down the dual action handle causes the N/O alarm switch to close. The word ‘ACTIVATED’ is displayed on the top of the handle when the pull station handle is pushed in and pulled down. The activated handle can not be reset without employing the key-lock reset. To reset the NBG-12LX pull station: 1) Insert the key and turn counterclockwise, 2) Open the door until the handle moves back into the ‘NORMAL’ position, 3) Close the door and lock it. Closing the door automatically resets the switch to the ‘NORMAL’ position.

ACTIVATED NBG-12LX PULL

STATION

CAUTION!

Install the Notifier NBG-12LX manual pull station in accordance with these instructions, applicable NFPA standards, national and local Fire and Electrical codes and the re- quirements of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conducted in accordance with the appropriate NFPA standards. Failure to fol- low these directions may result in failure of the device to report an alarm condition. Notifier is not responsible for devices that have been improperly installed, tested or maintained.

For ADA compliance, if the clear floor space only allows forward approach to an object, the maximum forward reach height allowed is 48 in. (1,220 mm). If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach height allowed is 54 in. (1,370 mm).

Document 51093 Revision A2 ECN 01-293 09/14/01

Note - Opening the pull station door will not activate or deac- tivate the alarm switch.

DOOR ATTACHMENT

DOOR MATED TO BACKPLATE

STRIP GAUGE  !" 7 5 2 )6 """ ''

With the door and backplate aligned and ‘keyed’ together, slide the holes down onto the posts.

Closing the door slightly locks the door and backplate together.

2) Mount the backbox before wiring to the pull station.

3) Before mounting the station, pull all necessary wiring through the backbox and optional trim ring.

4) Remove the correct amount of wire insulation. The pull station backplate is molded with a strip gauge to measure the amount of insulation to be removed. 5) Connect the wiring from the addressable fire alarm control panel’s Signaling Line Circuit (SLC) to Terminals 1(-) and 2(+) on the NBG-12LX addressable pull station. SLC polarity is critical for this connection.

6) Connect the wiring going to the next device on the SLC to Terminals 1 and 2, again being certain to observe polarity.

7) If using a single-gang or SB-10 box for mounting, open the pull station door; align the mounting holes of the pull station backplate to the backbox and screw into place. Tighten both top and bottom screws.

8) Set the address as described in ‘Setting the NBG-12LX Address’ and write the address in the space provided on the label.

9) Close and lock the pull station door.

12 LXW irin g.c dr 12L X D oor M ount .c dr NB G1 2- A cti ve .w m f

www.PDF-Zoo.com

N200-02-00 8 I56-1571-006R

1. Remove the two sensor board mounting screws. 2. Pull gently on the board to remove it.

3. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place. 4. Secure board with the two mounting screws.

[10.2] Power Board Replacement

1. Disconnect wiring from the terminal block. 2. Remove the two power board mounting screws. 3. Pull gently on the board to remove it.

4. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.

5. Secure board with the two mounting screws. 6. Re-connect wiring to terminal block.

[12] Model FSD-751RP Air Duct Smoke Detector Specifications Operating Temperature +32° to +131°F (0° to +55°C) Storage Temperature –22° to +158°F (–30° to +70°C) Humidity Range 10% to 93% (non-condensing)

Air Velocity 500 to 4000 ft/min (2.54 to 20.32 m/sec.) Dimensions 143⁄8

″ L x 51⁄2″ W x 23⁄4

″ D (37 cm L x 14 cm W x 7 cm D)

Programming Specifications/Requirements for Intelligent System Control Panels

There are a limited number of devices that can have their LEDs programmed to illuminate. The actual number of devices is determined by the control panel and its ability to supply LED current. Refer to the Control Panel Installation Manual for details.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

– Reorient or relocate the receiving antenna.

– Increase the separation between the equipment and receiver.

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component of that system which fails shall be repaired or replaced as soon as possible.

Current Requirements (using no accessories)

Power supply voltage: 20-30 VDC 24 VAC, 50-60 Hz 120 VAC, 50-60Hz 220/240 VAC, 50-60Hz Max. standby current: 26 mA 65 mA RMS 44 mA RMS 25 mA RMS Max. alarm current: 87 mA 182 mA RMS 52 mA RMS 30 mA RMS Alarm resonse time: 3 to 10 Sec. 3 to 10 Sec. 3 to 10 Sec. 3 to 10 Sec. Power up time: 2 Sec. 2 Sec. 2 Sec. 2 Sec.

Accessories Part No.

Remote LED RA400Z Magnetic Remote Test RTS451 Key-Activated Remote Test RTS451KEY Replacement Filters F36-09-11 Replacement Test Magnet M02-04-00

Accessories Part No.

Replacement Photo Insect Screen S08-39-01 Replacement End Cap for Plastic Sampling Tube P48-61-00 Replacement End Cap for Metal Sampling Tubes P48-21-00 Replacement Photoelectric Sensor Board A5053FS Replacement Power Board (w/relay) A5060

Accessory Current Loads at 24 VDC Device Standby Alarm PA400 0 mA 15 mA Max. RA400Z 0 mA 12 mA Max. RTS451/RTS451KEY 0 mA 10 mA Max. Contact Ratings

Alarm auxiliary contacts* (DPDT) 10 A @ 30 VDC

10 A @ 277 VAC (.75 power factor) 240 VA @ 249 VAC (0.4 power factor) 1/8 HP @ 120 VAC

1/4 HP @ 240 VAC Supervisory contact (SPST) 2.0 A @ 30 VDC (resistive)

*Minimum switching current for auxiliary contact must be 100 mA DC minimum @ 5 VDC.

N200-02-00 1 I56-1571-006R Notifier, 12 Clintonville Road, Northford, CT 06472, (203) 484-7161

Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037). NFPA Standards 72 and 90A should also be referenced for detailed information.

NOTICE: This manual shall be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector

should be cleaned at least once a year. GENERAL DESCRIPTION

An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct system is distributed to the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.

The FSD-751RP air duct smoke detector is a photoelectric detector. This smoke detection method combines with an efficient housing design that samples air passing through a duct and allows detection of a developing hazardous condi- tion. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans, blowers and change over air handling systems, etc. This can prevent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system.

Two LEDs on each detector may illuminate, if programmed by the system control panel, to provide a local alarm indica- tion. There is also a remote alarm output for use with auxiliary devices. The FSD-751RP has remote test capability with the RTS451/RTS451KEY Remote Test Station.

The FSD751RP incorporates a cover tamper feature. When the cover is removed for more than 20 minutes, the unit loses communication at the panel, a trouble is indicated at the panel and the alarm relay switches states thereby shutting down fans, dampers and blowers. In the case when the sensor is removed or when there is no power to the unit, only a trouble is indicated at the panel (alarm relay does not work any longer).

Figure 1. Exploded view of duct smoke detector components: CONTENTS OF THE DUCT SMOKE DETECTOR HOUSING KIT The FSD-751RP Duct Smoke Detector consists of the following items (See Figure 1.):

FSD-751RP INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR