• No se han encontrado resultados

Metodo cualitativo

In document info:eu-repo/semantics/bachelorthesis (página 32-0)

CAPÍTULO 3: DISEÑO DE LA INVESTIGACIÓN

3.2   Metodología

3.2.1 Metodo cualitativo

Welcome to Danfoss Drives

Many frequency inverters use this type of switching pattern

Also called “sine coded” or “sine weighted” PWM

Main limitation of Standard PWM is that the maximum output voltage to the motor is limited to 87% of the inverter’s input voltage:

Welcome to Danfoss Drives

.

Motor

V = V = (V x √2) Phase-to-Phase

(rms) input voltage:

Vin = (Vpeak / √2)

Maximum phase to earth peak output voltage = V2dc Therefore maximum phase to earth rms output

voltage Vpout = (V2dc / √2)

Therefore, maximum phase-to-phase rms output voltage = (√3 x V )

Welcome to Danfoss Drives

“YES!!”

Effect of voltage variation on induction motor characteristics

-20

Percent change in motor performance

Full Load Amps Power Factor Efficiency

Starting and Maximum Torque Starting Amps

Welcome to Danfoss Drives

For a motor operating from a fixed supply frequency (50Hz), to

produce motor nameplate rated shaft torque when the mains supply is -10% below motor nameplate rated voltage results in the following:

21% increase in slip to produce rated torque, 2% decrease in efficiency,

9.5% increase in full load amps, 6 - 7°C temperature rise,

for every +10°C. temperature riserise above rated, the lifelife of the motor is reducedreduced 50%50%

Welcome to Danfoss Drives

Switching pattern modulation index can be increased or third harmonic injection can be used to increase output voltage from standard PWM frequency inverters

Both methods increase fundamental output voltage however but also increase harmonic voltages = limitations

Theoretically it is possible to achieve a fundamental output

voltage 95% of the input voltage however this still means motor operates at best in a 5% under voltage condition

If try to increase output voltage any further increases harmonic frequencies in motor = increased motor temperature + torque ripple + acoustic noise = reduced motor performance and

efficiency

Welcome to Danfoss Drives

In reality what happens if using a standard PWM frequency inverter to control a motor?

The motor must be derated

It cannot be used for full load output power/torque (e.g. a 15kW motor can only be used for a load which requires maximum 13kW shaft power)

Due to over-design of systems and selection of standard frame size motors this might be OK for some applications but this is a serious limitation of standard PWM – what if you need full flow, full power, full torque for only 5% of the time?

Frequency inverter supplier relies on fact that motor has over design built in as part of the motor’s service factor (i.e. lifetime)

Welcome to Danfoss Drives

Not all frequency inverters use Standard PWM switching pattern today

Some frequency inverters have used an

enhanced version of PWM (e.g. Danfoss VVCplus) for many years, others are now introducing this

Enhanced PWM (e.g. VVCplus) = improved performance

Full motor voltage

Sinusoidal output current

Minimizes motor heating = same motor temp rise as on mains supply

Maximizes inverter efficiency

Many frequency inverters still use Standard

PWM and rely on the over design in the system, over sizing of the motor, or result in reduced performance or lifetime of the motor

Welcome to Danfoss Drives

• Unlike sine weighted PWM, VVC is based on a digital generation of the output voltage.

• Ensures output voltage

reaches rated value of input voltage, motor current is sinusoidal and the motor operates as it does on the mains.

Welcome to Danfoss Drives

• Enhanced PWM (e.g. VVC

plus

)

• Standard PWM

14%

Welcome to Danfoss Drives

A motor controlled by a frequency inverter using “enhanced”

PWM switching technique:

With rated mains supply voltage applied to the drive input, full rated fundamental output voltage is applied to the motor at rated frequency.

The motor is able to develop its rated power and torque at rated voltage, current, and speed.

The motor operates within its rated temperature rise

allowing full thermal life of the motor to be maintained.

Harmonics in the motor are minimized

Welcome to Danfoss Drives

• All frequency inverters are non-linear loads resulting in harmonic currents in the mains supply

• Most frequency inverters have one or two basic solutions to reduce harmonics

DC link reactor OR AC input reactor

Welcome to Danfoss Drives

Both DC reactors and AC reactors give similar reduction in harmonics

HARMONIC CURRENT ANALYSIS ---Fund. Current 36.22 A

THD 42.51%

RMS current 39.47 A 5’th Harmonic 12.91 A 7’th Harmonic 7.03 A 11’th Harmonic 3.06 A 13’th Harmonic 2.10 A ---HARMONIC CURRENT ANALYSIS ---Fund. Current 36.22 A

THD 42.51%

RMS current 39.47 A 5’th Harmonic 12.91 A 7’th Harmonic 7.03 A 11’th Harmonic 3.06 A 13’th Harmonic 2.10 A

---• DC reactors

HARMONIC CURRENT ANALYSIS ---Fund. Current 36.84 A

THD 43.84%

RMS current 40.22 A 5’th Harmonic 14.71 A 7’th Harmonic 5.74 A 11’th Harmonic 2.66 A 13’th Harmonic 1.34 A ---HARMONIC CURRENT ANALYSIS ---Fund. Current 36.84 A

THD 43.84%

RMS current 40.22 A 5’th Harmonic 14.71 A 7’th Harmonic 5.74 A 11’th Harmonic 2.66 A 13’th Harmonic 1.34 A

---• AC reactors

Welcome to Danfoss Drives

BUT – AC reactors result in a lower DC link voltage and therefore lower voltage available to the motor

How much lower voltage?

Example, a 3% AC reactor for an 11kW frequency inverter with a rated current of 25 amps may have an impedance of 1.2mH

On 60Hz supply this has an impedance XL=2x∏xfxL = 0.45 ohms

At 25 amps this equates to a voltage drop across reactor of:

V = I x XL = 11.3 volts = 3% of 380V

Voltage drop across reactor is 90 degrees out of phase with supply voltage so not full 3% drop (Note: DC reactor has no voltage drop)

But AC chokes also increase diode commutation time

Typically results reduction in DC link voltage = 0.5 x % inductance

e.g. 3% AC reactor = 1.5% reduction in DC link voltage, harmonic filter solutions

Welcome to Danfoss Drives

BUT – AC reactors result in a lower DC link voltage and therefore lower voltage available to the motor

How much lower voltage?

Example, a 3% AC reactor for an 11kW frequency inverter with a rated current of 25 amps may have an impedance of 1.2mH

On 60Hz supply this has an impedance XL=2x∏xfxL = 0.45 ohms

At 25 amps this equates to a voltage drop across reactor of:

V = I x XL = 11.3 volts = 3% of 380V

Voltage drop across reactor is 90 degrees out of phase with supply voltage so not full 3% drop (Note: DC reactor has no voltage drop)

But AC chokes also increase diode commutation time

Typically results reduction in DC link voltage = 0.5 x

% inductance ~ 1 2 3

Statement in inverter supplier’s manual

Welcome to Danfoss Drives

4 pole 4kW and 5.5kW motor nominal full load torque

0 5 10 15 20 25 30

0 300 600 900 1200 1500 1800

Speed rpm

Torque Nm

Motor Nominal Torque (4 pole, 4kW) Nm

Motor Nominal Torque (4 pole, 5.5kW) Nm

Welcome to Danfoss Drives

Standard PWM

Example of available 4kW and 5.5kW motor shaft torque

0

0 300 600 900 1200 1500 1800

Speed rpm

Torque Nm

Motor Nominal Torque (4 pole, 4kW) Nm

Full torque at full speed/full load not available w ith Standard PWM frequency inverters - typically best max 90% FLT available (especially if AC input reactors used for harmonic reduction)

Welcome to Danfoss Drives

Standard PWM

Example of available 4kW and 5.5kW motor shaft torque

0

0 300 600 900 1200 1500 1800

Speed rpm

Torque Nm

Motor Nominal Torque (4 pole, 4kW) Nm Motor Nominal Torque (4 pole, 5.5kW) Nm

Motor Torque available (4 pole, 5.5kW) with Standard PWM Frequency Inverter Nm (Supplier A) Motor Torque available (4 pole, 4kW) with Standard PWM Frequency Inverter Nm (Supplier A)

Full torque at full speed/full load not available w ith Standard PWM frequency inverters - typically best max 90% FLT available (especially if AC input reactors used for harmonic reduction)

Welcome to Danfoss Drives

Standard PWM

Centrifugal Pump or Fan Application

Requirement to oversize frequency inverter and motor depending on full flow torque requirement

0

0 300 600 900 1200 1500 1800

Speed rpm

Torque Nm

Motor Nominal Torque (4 pole, 4kW) Nm

Required full flow torque not available w ith standard PWM therefore need to use 5.5kW frequency inverter and motor to give required full flow torque = increased cost

Welcome to Danfoss Drives

Enhanced PWM

Example of available 4kW and 5.5kW motor shaft torque

0

0 300 600 900 1200 1500 1800

Speed rpm

Torque Nm

Motor Nominal Torque (4 pole, 4kW) Nm Motor Nominal Torque (4 pole, 5.5kW) Nm

Motor Torque available (4 pole, 4kW) with Enhanced PWM Frequency Inverter Nm (Supplier B) Motor Torque available (4 pole, 5.5kW) with Enhanced PWM Frequency Inverter Nm (Supplier B)

Full torque at full speed/full load is available w ith Enhanced PWM frequency inverters (especially if DC reactors used for harmonic reduction)

Welcome to Danfoss Drives

Enhanced PWM

Centrifugal Pump or Fan Application

Same motor as for fixed speed application (4kW) and 4kW frequency inverter required

0

0 300 600 900 1200 1500 1800

Speed rpm

Torque Nm

Required full flow torque is available w ith enhanced PWM therefore can use same 4kW motor as for fixed speed application, w ith 4kW frequency inverter = low est cost + best performance

Welcome to Danfoss Drives

By selecting or specifying a frequency inverter which uses an enhanced PWM switching pattern (e.g. VVCplus) and using DC reactors instead of AC input reactors you can be sure the motor will get it’s nameplate rated voltage when operating at full

speed, full load and therefore be able to provide full motor shaft torque and power without overloading the motor, or reducing it’s lifetime

This ensures compatibility with the motor and ensures it operates from the frequency inverter, just as it would if connected to the mains supply

Inverter duty rated motors, oversized (de-rated) motors are NOT required

For centrifugal pump and fan HVAC applications – enhanced PWM + DC reactors = standard motors can always be used no matter what the speed/flow range

Welcome to Danfoss Drives

Another important factor to consider is whether the motor’s insulation is compatible with the voltage supply from a

frequency inverter

The voltage supply from a PWM frequency inverter can be very different to the voltage from the mains supply

Motor Insulation – Peak Voltage and Rise Time

Welcome to Danfoss Drives

This is generally NOT a problem with “good” quality standard motors and frequency inverters on mains supplies <500V AC

It can be a problem on higher voltage mains supplies, with “low cost” motors and on special applications – for these special

precautions can be taken to prevent problems

However, for 220V/380V/480V mains supplies, using motors

complying with IEC60034-17 and “good” quality frequency inverters, there should be no problems and no need to use inverter rated

motors

Following slides, explain why potentially there can be problems and how to avoid these problems

Motor Insulation – Peak Voltage and Rise Time

* Following information comes Danfoss internal studies, studies at Dresden University, Germany and from a study into this topic by GAMBICA (UK drives industry association) and REMA (UK motor manufacturers association)

Welcome to Danfoss Drives

It is a fact that motor winding insulation experiences higher voltage stresses when supplied by a frequency inverter than when connected to sinusoidal AC mains supply

These higher stresses are dependant on motor cable length and are caused by the interaction of the fast rising voltage pulses of the frequency inverter and transmission line effects in the cable

To ensure compatibility with a motor, it is necessary to ensure the motor terminal peak voltage (voltage and rise time) are below the levels that the motor insulation is immune to

Motor Insulation – Peak Voltage and Rise Time

Welcome to Danfoss Drives

PWM frequency inverters use fast switching IGBTs to create the PWM voltage waveform

A series of square wave voltage pulses are applied to the motor cable

The motor draws current and due to the large inductance of the motor this consists of mainly a sinusoidal current waveform at the required frequency of operation

Motor Insulation – Peak Voltage and Rise Time

Welcome to Danfoss Drives

Each pulse of the PWM waveform created by the fast switching IGBTs has a fast rise time (at the output of a typical frequency inverter this could be approx 100 – 300 ns)

Rise times are so fast that as it travels along length of the

motor cable to the motor it can change the shape of the pulse and may produce voltage overshoot (and change the rise time)

At the motor, one pulse of the PWM waveform can look very different to the square wave at the frequency inverter output

Motor Insulation – Peak Voltage and Rise Time

Welcome to Danfoss Drives

To understand this effect, due to the fast rising pulse, it is necessary to consider the motor cable as a transmission line

Transmission line effects can then be considered = pulse travels along the cable and is reflected at the motor like a wave

A transmission line consists of a long string of

inductor/capacitor sections as shown below (only one phase is considered here):

Motor Insulation – Peak Voltage and Rise Time

Welcome to Danfoss Drives

At each fast rising pulse edge the frequency inverter has to charge the inductance and capacitance of the cable so a pulse of energy is delivered into the cable

Transmission line theory shows pulse travels at velocity

= [1 / √(LC)] m/s

L and C = inductance (Henries) and capacitance (Farads) per metre

Velocity of a pulse in typical PVC insulated cable

= approx 1.7 x 108 m/s

= in 100ns the pulse travels 17m

Different cable types give slightly different velocities, but generally the differences are only small

Motor Insulation – Peak Voltage and Rise Time

Welcome to Danfoss Drives

In this theoretical/ideal explanation:

tr = rise time of pulse at frequency inverter output

tp = time taken for pulse to travel length of cable

tr < tp (which is typical for cable lengths >30m)

Time t = tr

Pulse enters cable at t = 0 and rises to DC link voltage Ud in time tr

Motor Insulation – Peak Voltage and Rise Time

Time t = tr + tp

Pulse travels from inverter to motor

When reaches motor it is reflected because motor high frequency impedance is > cable impedance

Reflection causes pulse to rise towards 2 x original peak = 2 x U

Welcome to Danfoss Drives

Time t = 2tr + 2tp (i.e. after the pulse has traveled to the motor and back to the inverter)

Reflected pulse returns to inverter

Because inverter impedance is low pulse is reflected in a negative sense

Inverter clamps voltage to Ud resulting in negative pulse as it travels back along cable to motor

Motor Insulation – Peak Voltage and Rise Time

Time t = 2tr + 3tp (i.e. after the pulse has traveled to the motor, back to the inverter and back to the motor)

Negative pulse is reflected again at the motor and is doubled again = -2 x U

Welcome to Danfoss Drives

In ideal case of previous 2 slides reflections would cause voltage to oscillate continuously

In the “real world” voltage rise time is increased due to high

frequency losses in the cable and

In document info:eu-repo/semantics/bachelorthesis (página 32-0)

Documento similar