(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2

Special Features on Request:

• Oil Resistance

• UV Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

• Heat Resistance

• Anti Termite

Note:

Conductor Shape

50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing

50 - 95 sqmm supplied in wooden drum @ 1000 meters

120 - 400 sqmm supplied in wooden drum on available length

Length Tolerance per drum ± 2%

Construction Data

Nom

Cross Section Overall

Diameter Cable

Weight

Area approx. approx.

mm² mm kg/km

50 42.5 2,210

70 47.0 2,675

95 50.5 3,150

120 54.5 3,705

150 57.5 4,195

185 61.0 4,795

240 66.0 5,660

300 74.0 7,060

400 81.0 8,590

Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler

Application:

Indoors, cable trunking, outdoors and in ground;

For power stations, industry and switchgear.

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information

Electrical Data

Conductor Inductance Current - Carrying

Capacity at at 30 °C *

Short Circuit Current at 1 second CrossNom

Section mm²Area

ResistanceDC at 20 °C (Ω/km)Max.

ResistanceAC at 90 °C

(Ω/km)Max. (mH/km)

in air Max.(A)

in ground Max.(A)

Conductor Max.(kA)

Screen Max.(kA)

50 0.641 0.822 0.359 158 140 4.91 1.03

70 0.443 0.568 0.330 196 171 6.87 1.03

95 0.320 0.411 0.316 236 203 9.32 1.03

120 0.253 0.325 0.305 273 232 11.77 1.03

150 0.206 0.265 0.295 309 260 14.72 1.03

185 0.164 0.212 0.287 355 294 18.15 1.03

240 0.125 0.162 0.279 415 340 23.55 1.37

300 0.100 0.130 0.268 475 384 29.44 1.37

400 0.0778 0.102 0.260 552 438 39.25 1.37

NA2X SEY 3 C ORE 6- 10 kV CT S

NA2XSEY 3 x (50 - 400) mm 2 6/10 kV

AL / XLPE / CTS / PVC

(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2

Special Features on Request:

• Oil Resistance

• UV Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

• Heat Resistance

• Anti Termite

Note:

Conductor Shape

50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing

50 - 95 sqmm supplied in wooden drum @ 1000 meters

120 - 400 sqmm supplied in wooden drum on available length

Length Tolerance per drum ± 2%

Construction Data

Nom

Cross Section Overall

Diameter Cable

Weight

Area approx. approx.

mm² mm kg/km

50 47.0 2,595

70 51.0 3,090

95 55.5 3,650

120 59.0 4,185

150 62.0 4,695

185 65.0 5,325

240 70.0 6,165

300 76.0 7,480

400 83.0 8,895

Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler

Application:

Indoors, cable trunking, outdoors and in ground;

For power stations, industry and switchgear.

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information

Electrical Data

Conductor Inductance Current - Carrying

Capacity at at 30 °C *

Short Circuit Current at 1 second CrossNom

Section mm²Area

ResistanceDC at 20 °C (Ω/km)Max.

ResistanceAC at 90 °C

(Ω/km)Max. (mH/km)

in air Max.(A)

in ground Max.(A)

Conductor Max.(kA)

Screen Max.(kA)

50 0.641 0.822 0.383 158 140 4.91 1.03

70 0.443 0.568 0.352 196 171 6.87 1.03

95 0.320 0.411 0.337 236 203 9.32 1.03

120 0.253 0.325 0.324 273 232 11.77 1.03

150 0.206 0.265 0.313 309 260 14.72 1.03

185 0.164 0.212 0.304 355 294 18.15 1.03

240 0.125 0.162 0.295 415 340 23.55 1.37

300 0.100 0.130 0.281 475 384 29.44 1.37

400 0.0778 0.102 0.273 552 438 39.25 1.37

NA2X SEY 3 C ORE 8. 7- 15 kV CT S

NA2XSEY 3 x (50 - 400) mm 2 8.7/15 kV

AL / XLPE / CTS / PVC

(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2

Special Features on Request:

• Oil Resistance

• UV Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

• Heat Resistance

• Anti Termite

Note:

Conductor Shape

50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing

50 - 70 sqmm supplied in wooden drum @ 1000 meters

95 - 400 sqmm supplied in wooden drum on available length

Length Tolerance per drum ± 2%

Construction Data

Nom

Cross Section Overall

Diameter Cable

Weight

Area approx. approx.

mm² mm kg/km

50 53.0 3,155

70 57.5 3,750

95 61.0 4,300

120 64.5 4,870

150 67.5 5,415

185 71.5 6,150

240 76.0 7,045

300 82.5 8,355

400 88.5 9,835

Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler

Application:

Indoors, cable trunking, outdoors and in ground;

For power stations, industry and switchgear.

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information

Electrical Data

Conductor Inductance Current - Carrying

Capacity at at 30 °C *

Short Circuit Current at 1 second CrossNom

Section mm²Area

ResistanceDC at 20 °C (Ω/km)Max.

ResistanceAC at 90 °C

(Ω/km)Max. (mH/km)

in air Max.(A)

in ground Max.(A)

Conductor Max.(kA)

Screen Max.(kA)

50 0.641 0.822 0.403 158 140 4.91 1.03

70 0.443 0.568 0.370 196 171 6.87 1.03

95 0.320 0.411 0.353 236 203 9.32 1.03

120 0.253 0.325 0.340 273 232 11.77 1.03

150 0.206 0.265 0.328 309 260 14.72 1.03

185 0.164 0.212 0.319 355 294 18.15 1.03

240 0.125 0.162 0.308 415 340 23.55 1.37

300 0.100 0.130 0.294 475 384 29.44 1.37

400 0.0778 0.102 0.285 552 438 39.25 1.37

NA2X SEY 3 C ORE 12-20 kV CT S

NA2XSEY 3 x (50 - 400) mm 2 12/20 kV

AL / XLPE / CTS / PVC

(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2

Special Features on Request:

• Oil Resistance

• UV Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

• Heat Resistance

• Anti Termite

Note:

Conductor Shape

50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing

50 sqmm supplied in wooden drum @ 1000 meters 70 - 400 sqmm supplied in wooden drum on available length

Length Tolerance per drum ± 2%

Construction Data

Nom

Cross Section Overall

Diameter Cable

Weight

Area approx. approx.

mm² mm kg/km

50 58.0 3,730

70 62.0 4,315

95 66.0 4,895

120 69.5 5,495

150 72.5 6,135

185 76.0 6,835

240 81.0 7,765

300 87.5 9,135

400 94.0 10,765

Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler

Application:

Indoors, cable trunking, outdoors and in ground;

For power stations, industry and switchgear.

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information

Electrical Data

Conductor Inductance Current - Carrying

Capacity at at 30 °C *

Short Circuit Current at 1 second CrossNom

Section mm²Area

ResistanceDC at 20 °C (Ω/km)Max.

ResistanceAC at 90 °C

(Ω/km)Max. (mH/km)

in air Max.(A)

in ground Max.(A)

Conductor Max.(kA)

Screen Max.(kA)

50 0.641 0.822 0.445 158 140 4.91 1.03

70 0.443 0.568 0.409 196 171 6.87 1.03

95 0.320 0.411 0.390 236 203 9.32 1.03

120 0.253 0.325 0.376 273 232 11.77 1.03

150 0.206 0.265 0.362 309 260 14.72 1.03

185 0.164 0.212 0.351 355 294 18.15 1.03

240 0.125 0.162 0.338 415 340 23.55 1.37

300 0.100 0.130 0.322 475 384 29.44 1.37

400 0.0778 0.102 0.310 552 438 39.25 1.37

NA2X SEY 3 C ORE 18- 30 kV CT S

NA2XSEY 3 x (50 - 400) mm 2 18/30 kV

AL / XLPE / CTS / PVC

(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2

Special Features on Request:

• Oil Resistance

• UV Resistance

• Flame Retardant Cat. A, B, C

• Flame Retardant Non Category

• Heat Resistance

• Anti Termite

Note:

Conductor Shape

50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing

50 - 400 sqmm supplied in wooden drum on available length

Length Tolerance per drum ± 2%

Construction Data

Nom

Cross Section Overall

Diameter Cable

Weight

Area approx. approx.

mm² mm kg/km

50 70.0 5,165

70 74.5 5,905

95 78.0 6,565

120 81.5 7,245

150 84.5 7,885

185 88.0 8,655

240 93.0 9,775

300 99.5 11,285

400 105.5 12,965

Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler

Application:

Indoors, cable trunking, outdoors and in ground;

For power stations, industry and switchgear.

* Further information about rating factor for certain cable arrangement can be found on supplementary technical information

Electrical Data

Conductor Inductance Current - Carrying

Capacity at at 30 °C *

Short Circuit Current at 1 second CrossNom

Section mm²Area

ResistanceDC at 20 °C (Ω/km)Max.

ResistanceAC at 90 °C

(Ω/km)Max. (mH/km)

in air Max.(A)

in ground Max.(A)

Conductor Max.(kA)

Screen Max.(kA)

50 0.641 0.822 0.373 158 140 4.91 2.85

70 0.443 0.568 0.343 196 171 6.87 2.85

95 0.320 0.411 0.328 236 203 9.32 2.85

120 0.253 0.325 0.317 273 232 11.77 2.85

150 0.206 0.265 0.306 309 260 14.72 2.85

185 0.164 0.212 0.297 355 294 18.15 4.45

240 0.125 0.162 0.289 415 340 23.55 4.45

300 0.100 0.130 0.280 475 384 29.44 4.45

400 0.0778 0.102 0.274 552 438 39.25 6.23

NA2X SEY 3 C ORE 3.6-6 kV

NA2XSEY 3 x (50 - 400) mm 2 3.6/6 kV

In document PARTE I PRESENTACIÓN DE LA INVESTIGACIÓN (página 191-194)