(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2
Special Features on Request:
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
Note:
Conductor Shape
50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
50 - 95 sqmm supplied in wooden drum @ 1000 meters
120 - 400 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
Construction Data
Nom
Cross Section Overall
Diameter Cable
Weight
Area approx. approx.
mm² mm kg/km
50 42.5 2,210
70 47.0 2,675
95 50.5 3,150
120 54.5 3,705
150 57.5 4,195
185 61.0 4,795
240 66.0 5,660
300 74.0 7,060
400 81.0 8,590
Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
Electrical Data
Conductor Inductance Current - Carrying
Capacity at at 30 °C *
Short Circuit Current at 1 second CrossNom
Section mm²Area
ResistanceDC at 20 °C (Ω/km)Max.
ResistanceAC at 90 °C
(Ω/km)Max. (mH/km)
in air Max.(A)
in ground Max.(A)
Conductor Max.(kA)
Screen Max.(kA)
50 0.641 0.822 0.359 158 140 4.91 1.03
70 0.443 0.568 0.330 196 171 6.87 1.03
95 0.320 0.411 0.316 236 203 9.32 1.03
120 0.253 0.325 0.305 273 232 11.77 1.03
150 0.206 0.265 0.295 309 260 14.72 1.03
185 0.164 0.212 0.287 355 294 18.15 1.03
240 0.125 0.162 0.279 415 340 23.55 1.37
300 0.100 0.130 0.268 475 384 29.44 1.37
400 0.0778 0.102 0.260 552 438 39.25 1.37
NA2X SEY 3 C ORE 6- 10 kV CT S
NA2XSEY 3 x (50 - 400) mm 2 6/10 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2
Special Features on Request:
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
Note:
Conductor Shape
50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
50 - 95 sqmm supplied in wooden drum @ 1000 meters
120 - 400 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
Construction Data
Nom
Cross Section Overall
Diameter Cable
Weight
Area approx. approx.
mm² mm kg/km
50 47.0 2,595
70 51.0 3,090
95 55.5 3,650
120 59.0 4,185
150 62.0 4,695
185 65.0 5,325
240 70.0 6,165
300 76.0 7,480
400 83.0 8,895
Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
Electrical Data
Conductor Inductance Current - Carrying
Capacity at at 30 °C *
Short Circuit Current at 1 second CrossNom
Section mm²Area
ResistanceDC at 20 °C (Ω/km)Max.
ResistanceAC at 90 °C
(Ω/km)Max. (mH/km)
in air Max.(A)
in ground Max.(A)
Conductor Max.(kA)
Screen Max.(kA)
50 0.641 0.822 0.383 158 140 4.91 1.03
70 0.443 0.568 0.352 196 171 6.87 1.03
95 0.320 0.411 0.337 236 203 9.32 1.03
120 0.253 0.325 0.324 273 232 11.77 1.03
150 0.206 0.265 0.313 309 260 14.72 1.03
185 0.164 0.212 0.304 355 294 18.15 1.03
240 0.125 0.162 0.295 415 340 23.55 1.37
300 0.100 0.130 0.281 475 384 29.44 1.37
400 0.0778 0.102 0.273 552 438 39.25 1.37
NA2X SEY 3 C ORE 8. 7- 15 kV CT S
NA2XSEY 3 x (50 - 400) mm 2 8.7/15 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2
Special Features on Request:
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
Note:
Conductor Shape
50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
50 - 70 sqmm supplied in wooden drum @ 1000 meters
95 - 400 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
Construction Data
Nom
Cross Section Overall
Diameter Cable
Weight
Area approx. approx.
mm² mm kg/km
50 53.0 3,155
70 57.5 3,750
95 61.0 4,300
120 64.5 4,870
150 67.5 5,415
185 71.5 6,150
240 76.0 7,045
300 82.5 8,355
400 88.5 9,835
Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
Electrical Data
Conductor Inductance Current - Carrying
Capacity at at 30 °C *
Short Circuit Current at 1 second CrossNom
Section mm²Area
ResistanceDC at 20 °C (Ω/km)Max.
ResistanceAC at 90 °C
(Ω/km)Max. (mH/km)
in air Max.(A)
in ground Max.(A)
Conductor Max.(kA)
Screen Max.(kA)
50 0.641 0.822 0.403 158 140 4.91 1.03
70 0.443 0.568 0.370 196 171 6.87 1.03
95 0.320 0.411 0.353 236 203 9.32 1.03
120 0.253 0.325 0.340 273 232 11.77 1.03
150 0.206 0.265 0.328 309 260 14.72 1.03
185 0.164 0.212 0.319 355 294 18.15 1.03
240 0.125 0.162 0.308 415 340 23.55 1.37
300 0.100 0.130 0.294 475 384 29.44 1.37
400 0.0778 0.102 0.285 552 438 39.25 1.37
NA2X SEY 3 C ORE 12-20 kV CT S
NA2XSEY 3 x (50 - 400) mm 2 12/20 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2
Special Features on Request:
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
Note:
Conductor Shape
50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
50 sqmm supplied in wooden drum @ 1000 meters 70 - 400 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
Construction Data
Nom
Cross Section Overall
Diameter Cable
Weight
Area approx. approx.
mm² mm kg/km
50 58.0 3,730
70 62.0 4,315
95 66.0 4,895
120 69.5 5,495
150 72.5 6,135
185 76.0 6,835
240 81.0 7,765
300 87.5 9,135
400 94.0 10,765
Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
Electrical Data
Conductor Inductance Current - Carrying
Capacity at at 30 °C *
Short Circuit Current at 1 second CrossNom
Section mm²Area
ResistanceDC at 20 °C (Ω/km)Max.
ResistanceAC at 90 °C
(Ω/km)Max. (mH/km)
in air Max.(A)
in ground Max.(A)
Conductor Max.(kA)
Screen Max.(kA)
50 0.641 0.822 0.445 158 140 4.91 1.03
70 0.443 0.568 0.409 196 171 6.87 1.03
95 0.320 0.411 0.390 236 203 9.32 1.03
120 0.253 0.325 0.376 273 232 11.77 1.03
150 0.206 0.265 0.362 309 260 14.72 1.03
185 0.164 0.212 0.351 355 294 18.15 1.03
240 0.125 0.162 0.338 415 340 23.55 1.37
300 0.100 0.130 0.322 475 384 29.44 1.37
400 0.0778 0.102 0.310 552 438 39.25 1.37
NA2X SEY 3 C ORE 18- 30 kV CT S
NA2XSEY 3 x (50 - 400) mm 2 18/30 kV
AL / XLPE / CTS / PVC
(Aluminium Conductor, PVC Insulated, Copper Tape Screen, PVC Sheathed) Standard Specification : IEC 60502 - 2
Special Features on Request:
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
Note:
Conductor Shape
50 - 400 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
50 - 400 sqmm supplied in wooden drum on available length
Length Tolerance per drum ± 2%
Construction Data
Nom
Cross Section Overall
Diameter Cable
Weight
Area approx. approx.
mm² mm kg/km
50 70.0 5,165
70 74.5 5,905
95 78.0 6,565
120 81.5 7,245
150 84.5 7,885
185 88.0 8,655
240 93.0 9,775
300 99.5 11,285
400 105.5 12,965
Red PVC Outer sheath PVC inner sheath (Fully extruded) ID tape (Red, Yellow & Blue) Copper Tape Screen Insulation screen XLPE insulation Conductor screen Aluminium conductor Rope filler
Application:
Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.
* Further information about rating factor for certain cable arrangement can be found on supplementary technical information
Electrical Data
Conductor Inductance Current - Carrying
Capacity at at 30 °C *
Short Circuit Current at 1 second CrossNom
Section mm²Area
ResistanceDC at 20 °C (Ω/km)Max.
ResistanceAC at 90 °C
(Ω/km)Max. (mH/km)
in air Max.(A)
in ground Max.(A)
Conductor Max.(kA)
Screen Max.(kA)
50 0.641 0.822 0.373 158 140 4.91 2.85
70 0.443 0.568 0.343 196 171 6.87 2.85
95 0.320 0.411 0.328 236 203 9.32 2.85
120 0.253 0.325 0.317 273 232 11.77 2.85
150 0.206 0.265 0.306 309 260 14.72 2.85
185 0.164 0.212 0.297 355 294 18.15 4.45
240 0.125 0.162 0.289 415 340 23.55 4.45
300 0.100 0.130 0.280 475 384 29.44 4.45
400 0.0778 0.102 0.274 552 438 39.25 6.23