• No se han encontrado resultados

PROTOCOLO DE ACCIDENTES ESCOLARES

In document Colegio San Pedro Valle Grande (página 51-63)

24

A new Multiplex intelligent fire alarm system shall be installed within the Stadium. This building shall be 25

provided with a minimum of one fire Alarm Control Panel (FACP).

26 27

The control Panel shall be modular, expandable with solid state, microprocessor-based electronics. It shall 28

display through the front viewing window only those primary controls and displays essential to operation 29

during a fire alarm condition.

30 31

The fire alarm system shall allow for loading and editing special instructions and operating sequences as 32

required. Software programming shall allow for full flexibility for selective input/output control functions 33

based on the Boolean programming functions AND, OR, NOT, as well as timing, and special coded 34

operations. The system shall be able to use all of the above programming functions in combination with any 35

number of inputs and outputs. The systems shall be capable of on-site programming to accommodate system 36

expansion and facilitate changes in operation. All software operations shall be stored in a non-volatile 37

programmable memory within the fire alarm control panel. Loss of primary and secondary power shall not 38

erase the instructions stored in memory.

39 40

Simple Addressable systems, which do not support Analog Addressable or Intelligent Addressable detection 41

technology, shall be unacceptable.

42 43

The control panel shall provide the following as standards:

44

Analog Addressable or Intelligent Addressable Detection, supporting the following:

45

Drift compensation 46

Sensitivity display in % 47

Sensitivity adjustment 48

Day/night sensitivity adjustment 49

Auto Detector test to meet NFPA 72 50

Alarm verification with tally counter 51

Maintenance alerts 52

53

The number of Signaling Line Circuits (SLCs) required for the specified quantity of addressable 54

field devices and peripherals, plus one (1) spare loop (SLC) for each five (5) active loops. Each 55

active loop shall include 10% spare capacity or a minimum of 10 additional devices.

56 57

The number of Audible Notification Appliance Circuits (Speaker NACs) required for the specified 58

quantity of speakers plus one (1) spare circuit for each ten (10) active circuits. Each active circuit 59

shall include 25% spare capacity.

60 61

The number of Visual Notification Appliance Circuits (Strobe NACs) required for the specified 62

quantity of strobes plus one (1) spare circuit for each ten (10) active circuits. Each active circuit 63

shall include 25% spare capacity or a minimum of (4) 110 cd devices that can be added in the future.

64

1

80-character liquid crystal display.

2

History log file with a minimum of 800 events 3

Field programmability 4

Silent walk test 5

6

The multiplex/intelligent system shall provide the ability to recall alarms and trouble conditions in 7

chronological order for the purpose of recreating an event history.

8 9

The LCD shall display the following information relative to the abnormal condition of a point in the system 10

prior to acknowledgement:

11 12

40 characters for:

13

Point address and loop number (i.e. 555-L5) 14

Type of device (i.e. smoke sensor, pull station, water-flow) 15

Point status (i.e. alarm, trouble) 16

17

40 characters for:

18

Custom location label (i.e. 4th Floor - Room 444) 19

20

Keyboards or keypads shall not be required to operate the system during fire alarm conditions.

21 22

The following software functions shall be provided, from the built-in system keyboard / display:

23

Setting of time and date 24

LED testing 25

Alarm, trouble, and abnormal condition listing 26

Enabling and disabling of each monitor point separately 27

Activation and deactivation of each control point separately 28

Changing operator access levels 29

Walk Test enable / disable 30

Running diagnostic functions 31

Displaying historical logs 32

Point listing 33

34

The following hardware control switches/functions shall be provided within the main panel enclosure, though 35

may not all be utilized immediately:

36

Acknowledge alarm or trouble 37

Silence alarm or trouble 38

Reset system after alarm 39

Connect/disconnect Central Monitoring tie 40

Provide manual evacuation (drill) 41

Provide manual ALERT message(s) activation 42

Provide manual audio selection switches (if select voice is specified) 43

Bypass elevator interface 44

Bypass AHU / Fan Interface 45

Bypass speakers 46

Bypass strobes 47

(4) Future programmable switches 48

49

Switches mentioned above but not applicable to this building shall still be provided in the stated 50

quantity. These unused switches shall not be initially programmed and would be labeled as SPARE 51

or UNUSED.

52 53

STATUS INDICATORS AND DISPLAYS 54

A local audible device shall sound during Alarm, Trouble or Supervisory conditions. This audible device 55

shall also sound during each keypress to provide an audible feedback to ensure that the key has been pressed 56

properly.

57 58

The 2-line by 40-character liquid crystal display shall be backlit for enhanced readability.

59 60

A cursor shall be visible on the LCD when entering information.

61 62

Scrolling through menu options or lists shall be accomplished in a self-directing manner in which 63

prompting messages shall direct the user.

64

1

LED SUPERVISION 2

All slave modules LEDs shall be supervised for burnout or disarrangement.

3

depending on the NFPA requirements.

7 8

First method - Acknowledge one event at a time from an unacknowledged list of events:

9 10

Pressing the appropriate acknowledge button shall display the first unacknowledged condition in the 11

appropriate list (either alarm, supervisory or trouble), and require another acknowledge button. Press to 12

acknowledge only the displayed point.

13 14

After all points have been acknowledged, the LEDs shall glow steadily and the audible alert will be silenced.

15

The total number of alarms, supervisory and trouble conditions shall be displayed along with a prompt to 16

review each list chronologically. The end of the list shall be indicated by an end of list message "END of 17

LIST".

18 19

Second method- Pressing the appropriate acknowledge button shall globally acknowledge all points.

20 21

SILENCING 22

If an alarm condition exists and the "Alarm Silence" button is pressed, all alarm audio and visual notifications 23

appliances shall cease operation.

24 25

If trouble conditions exist in the system and the "Trouble Silence" button has been pressed, the aural trouble 26

signal shall cease, but shall resound at time intervals to act as a reminder that the fire alarm system is not in 27

a normal operating mode. Both the time interval and the trouble reminder signal shall be programmable to 28

suit the Owner's application.

29 30

RESET 31

The SYSTEM RESET button shall be used to return the system to its normal state after an alarm condition 32

has been remedied.

33 34

Should the Alarm Silence Inhibit function be active, the system shall ignore all key presses. An indication of 35

enabling and disabling the inhibit state shall be provided as a feedback to the operator.

36 37

BYPASS FUNCTIONS 38

Provide a switch for each item as shown below. Switches not applicable to this building would be provided, 39

but left unprogrammed and labeled and unused.

40 41

Bypass Switches shall be configured such that whenever any bypass function is active, a Trouble status 42

condition shall be reported by the system, per the Trouble Sequence. The trouble message shall indicate the 43

active function(s). Bypass LEDs shall be configured such that LEDs corresponding to the active function(s) 44

shall illuminate and shall remain lit until the associated bypass function is de-activated (until the system is 45

restored to normal operating status). Switches and LEDs shall be provided for the following functions:

46

Central Monitoring Bypass - When this bypass function is active; reporting of various status 47

conditions to the reporting system shall be disabled.

48 49

Elevator Interface bypass - When this bypass function is active; actuation of the Control Modules 50

or Supervised Relays, which interface to the Elevator Controls and to the Shunt-Trip Circuit 51

Breaker(s) shall be prevented.

52 53

HVAC / Fan Interface bypass - When this bypass function is active; actuation of the Control 54

Modules or Supervised Relays, which interface to the AHU / Fan starters / Temperature Controls, 55

and to any Smoke Dampers shall be prevented. (Smoke Control System bypass shall be 56

accomplished via the separate, previously specified manual controls).

57 58

ACCESS TO OPERATOR FUNCTIONS:

59

The following Operator Function Access Restrictions shall be adhered to as closely as possible. Where 60

system limitations do not allow for the restrictions to be configured exactly as listed, alternate methods will 61

be considered, and shall be brought to the attention of the Engineer prior to bidding:

62 63

ACCESS LEVEL 1 - BASIC OPERATOR FUNCTIONS:

64

ACKNOWLEDGE – allows Basic Operators to acknowledge ALARM, TROUBLE, and 1

SUPERVISORY conditions, and to view the lists / logs associated with these functions.

2 3

SIGNAL SILENCE – allows Basic Operators to silence the audible and visual signals. The 4 system shall not permit signals to be silenced during “alarm silence inhibit mode” (if

5 “Inhibit Mode” is utilized).

6 7

SYSTEM RESET – allows Basic Operators to Reset the Fire Alarm System. The "System 8

Reset" button shall be used to return the system to its normal state after an alarm condition 9

has been remedied. The LCD display shall step the user through the reset process with 10

simple English language messages.

11 12 13

ACCESS LEVEL 2 - HIGH SECURITY FUNCTIONS:

14

Changes to the linkage of Operator Functions to Access Level / Pass-Code Profiles may affect the 15

ability of individuals to access required functions. Because of this, access to this linking function 16

shall also be appropriately secured.

17 18

ACCESS LEVEL 3 - OTHER FUNCTIONS:

19

These functions shall include, but shall not be limited to:

20

Enable / Disable Points

21 Perform “Override” Functions / Features 22

Generate PDF Reports 23

Add / Delete / Change Pass codes, and associated links to system features 24

Set / Change System Clock 25

Set / Change Sensitivity of Detectors 26

Clear History Logs 27

28

POINT LISTING 29

All points list by address 30

Monitor point list 31

Signal/speaker list 32

Auxiliary control list 33

Feedback point list 34

35

HISTORY LOGGING 36

The system shall be capable of logging and storing the last 800 events (alarm & trouble) in a history log.

37

These events shall be stored in a battery protected random access memory.

38 39

The following historical alarm/trouble log events shall be stored:

40

Alarm Historical log cleared 45

Alarm Verification tallies 50

Walk Test results 51

Trouble Historical log cleared 52

53

SILENT WALK TEST WITH HISTORY LOGGING 54

The system shall be capable of being tested by one person. While in testing mode the alarm activation of an 55

alarm-initiating device shall be silently logged as an alarm condition in the historical data file. The panel 56

shall automatically reset itself after the logging of the alarm.

57 58

The momentary disconnection of an initiating or indicating device circuit shall be silently logged as a trouble 59

1

The panel shall have the capability of dividing the system into distinctive walk test groups, a minimum of (8) 2

After testing is considered complete, testing data may be retrieved from the system in chronological order to 8

ensure device/circuit activation.

9 10

WATCH-DOG TIMERS 11

The system shall include independent "Watch-Dog" timers to detect and report failure of any microprocessor 12

circuit, memory, or software.

13

special tools or PROM programmers and shall not require replacement of memory IC's. All programming 17

may be accomplished through the standard control panel keyboard or a keyboard at the FCC, or the use of a 18

PC. All programs shall be stored in non-volatile memory.

19 20

All programming or reprogramming shall be done by the supplier at no charge until the owner accepts the 21

allowing programming to be downloaded via portable computer from any node on the network.

26 27

Provide the services of a factory trained and authorized Technician to perform all system software 28

modifications, upgrades, or changes. Response time of the Technician to the site shall not exceed 2 hours for 29

an emergency situation.

30 31

Should the Owner have a factory trained and authorized technician on staff, provide all hardware, software, 32

programming tools, access codes, and documentation necessary to modify the fire alarm system on site.

33

Modification includes addition and deletion of devices, circuits, zones, and changes to system operation and 34

custom label changes for devices or zones. The system structure and software shall place no limit on the type 35

or extent of software modifications on-site. Modification of software shall not require power-down of the 36

system or loss of system fire protection while modifications are being made.

37 38

If the system access code is either a hardware key or a software key, the Contractor/Vendor shall provide the 39

proper key to meet the above requirements."

40 41

SIGNALING LINE CIRCUITS:

42

The system must provide communications with intelligent addressable initiating and control devices 43

individually. These devices shall be individually annunciated at the control panel, FAAP, and FCC.

44

Annunciation shall include the following conditions for each point:

45

All intelligent addressable initiation and control devices shall have the capability of being disabled or enabled 52

individually.

53 54

Systems that require factory pre-programming or EPROMs to add or delete devices shall be unacceptable.

55 56

The communication format must be a completely digital poll/response protocol to allow t-tapping of the 57

Signaling Line Circuit wiring. Systems that do not utilize full digital transmission protocol are not acceptable.

58

performing this function:

63

Isolator Modules – Field Mounted.

64

1

OPERATION: MULTIPLEX/INTELLIGENT FIRE ALARM SYSTEM

In document Colegio San Pedro Valle Grande (página 51-63)