• No se han encontrado resultados

Ecuación del cálculo de la eficiencia total de distribución

In document FACULTAD DE INGENIERÍA (página 23-33)

CAPÍTULO IV. DISCUSIÓN Y CONCLUSIONES

Ecuación 6: Ecuación del cálculo de la eficiencia total de distribución

The following steps are an example of how to choose the system units and indicates the way to decide on the model best suited to your own specific needs:

We recommend that you choose the AquaFREE system according to the heating load.

4.1.1. How to use the data in this chapter

Define the installation requirements: load, operating temperature and special installation needs. Then select the most suitable units. Decide on where to put the outdoor unit to allow easy maintenance and service.

Use the following information to calculate the most suitable units:

Relevant sections of Chapter 4:

Heating capacity curves: Section 4.2

Piping length and correction factors: Section 4.5 Noise-related data: Section 4.6

In addition, use the following information from the technical catalogue:

General data: Chapter 2 Hydraulic circuit: Section 7.4

Setting and function of DIP switches for AquaFREE indoor units: Section 9.3

4.1.2. Example of choosing units by heating load

We suggest the following method to determine the characteristics of the system units:

System requirements

Wet bulb temperature of the outside air inlet: -5 ºC

Temperature of the water outlet: 35 ºC

Temperature of the water inlet: 30 ºC

Thermal Load: 8.00 kW

Type of installation: Heating floor

Installation restrictions:

Power supply: 230 V, 1~, 50 Hz

AquaFREE module lower than the outdoor

unit: 15 m

Total equivalent distance between the

AquaFREE module and the outdoor unit: 20 m

Type of AquaFREE module:

AquaFREE RWM modules needed

Step 1:

NOTE:

The calculation methods for thermal loads in the building should comply with the regulations applicable in each country.

Heating load:

TCGB0042 rev.1 - 12/2007 pag 41

Capacities and selection data

4

Select the units

Select the units to make up the AquaFREE system according to the thermal load needed.

The system chosen should have a load capacity greater than the thermal load required by the installation.

Use section 4.2 to calculate your choice Unit chosen:

The total heating load is 8.00 kW, and the choice of system depends on the table of capacities (section 4.2) for heating floor (35/30ºC)

Heating floor

AquaFREE UNITS Outside air inlet temperature

WB (ºC)

Water outlet/inlet temperature (35/30ºC)

Max. CAP

RWM-4FSN1E

-6 9.20

-5 9.40

-3 9.30

Apply a correction factor according to the length and height of the piping (section 4.5) and the heating capacity given in Table 1:

The outdoor unit most suitable for your system requirements is:

Unit chosen RAS-4HVRNE/RWM-4FSN1E

Step 2:

Table 1:

Heating capacity data

NOTE:

The defrosting factor is included in Table 1.

Heating capacity of the system (THA) = heating capacity (TH) x correction factor for

piping length (F) = 9.40 x 0.99 = 9.30 kW

TCGB0042 rev.1 - 12/2007 pag 42

Capacities and selection data

Select units with electrical resistance

It is a geographical area where the 8.00 kW load is required at given moments.

Therefore, a 3 HP unit with supporting electrical resistance can be selected.

Wet bulb temperature of the outside air inlet: -5 ºC

Temperature of the water outlet: 35 ºC

Temperature of the water inlet: 30 ºC

Thermal load: 8.00 kW

Type of installation: Heating floor

Installation restrictions:

Power supply: 230 V, 1~, 50 Hz

AquaFREE module lower than the outdoor

unit: 15 m

Total equivalent distance between the

AquaFREE module and the outdoor unit: 20 m

Total heating load: 8.00 kW

The total heating load is 8.00 kW, and the choice of system depends on the table of capacities (section 4.2) for heating floor (35/30ºC)

Heating floor

AquaFREE UNITS Outside air inlet temperature

WB (ºC)

Water outlet/inlet temperature (35/30ºC)

As can be seen, the Total heating load > Capacity of the unit. These conditions require the use of additional electrical elements.

The capacity of the electrical elements required can be checked in Chapter 2 (General Data).

In the table and chapter 2 (General Data), select the unit with electrical resistance, which is model RWM-3FSN1E-6H1, with a total power of (6.70 x 0.98) + 4.50 kW of electrical resistance.

Unit with selected electrical

element. RWM-3FSN1E-6H1

Heating capacity data

NOTE:

We advise using support heaters rather than overloading the selected unit.

TCGB0042 rev.1 - 12/2007 pag 43

Capacities and selection data

4

Choice of units for installations with radiators or mixed installations (radiators + heating floor)

In the case of installations with radiators, use the same process as the heating floor method.

Choose the values in the table of water outlet/inlet temperature (45/40ºC) For mixed installations, use the graphs corresponding to the radiator installations.

4.1.3. Example of selecting cooling load

We suggest the following method to determine the characteristics of the system units:

System requirements

Dry bulb temperature for outside air inlet: 30 ºC

Temperature of the water outlet: 7 ºC

Temperature of the water inlet: 12 ºC

Thermal Load: 7.00 kW

Type of installation: Fan-coil

Installation restrictions:

Power supply: 230 V, 1~, 50 Hz

AquaFREE module lower than the outdoor unit: 15 m Total equivalent distance between the AquaFREE

module and the outdoor unit: 20 m

Type of AquaFREE module:

AquaFREE RWM modules needed

Step 4:

Step 1:

Cooling load:

TCGB0042 rev.1 - 12/2007 pag 44

Capacities and selection data

Select the units

Select the units to make up the AquaFREE system according to the thermal load needed.

The system chosen should have a load capacity greater than the thermal load required by the installation.

Use section 4.3 to calculate your choice Unit chosen:

The total cooling load is 7.00 kW, and the choice of system depends on the table of capacities (section 4.3) for fan-coil heating (7/12ºC)

Heating floor

AquaFREE UNITS Outside air inlet temperature

DB (ºC)

Water outlet/inlet temperature (7/12ºC)

Max. CAP

RWM-4FSN1E

25 9.40

30 8.70

35 8.20

Apply a correction factor according to the length and height of the piping (section 4.5) and the cooling capacity given in Table 1:

The outdoor unit most suitable for your system requirements is:

Unit chosen RAS-4HVRNE/RWM-4FSN1E

If you want to use heating floor for cold applications, please take the following points into account:

The water temperatures to be used for this type of installation vary between 19ºC and 21ºC depending on the ambient humidity.

The use of temperatures at 7ºC for this type of installation could cause condensation.

Step 2:

Step 3:

Cooling capacity of the system (TCA) = cooling capacity (TC) x correction factor for

piping length (F) = 8.70 x 0.96 = 8.35 kW

TCGB0042 rev.1 - 12/2007 pag 45

Capacities and selection data

In document FACULTAD DE INGENIERÍA (página 23-33)

Documento similar