10.3.1 Location. Central heating furnace and lowpressure boiler installations in bedrooms or bathrooms shall comply with one of the following:
(1) Central heating furnaces and lowpressure boilers shall be installed in a closet located in the bedroom or bathroom, the closet shall have a weatherstripped solid door with a selfclosing device, and all combustion air shall be obtained from the outdoors.
(2) Central heating furnaces and lowpressure boilers shall be of the direct vent type.
10.3.2 Clearance.
10.3.2.1 Listed central heating furnaces and lowpressure boilers installed in a room large in comparison with the size of the appliance shall be installed with clearances in accordance with the manufacturer’s instructions. (See 3.3.88, Room Large in Comparison with Size of Equipment.)
10.3.2.2 Central heating furnaces and lowpressure boilers installed in rooms that are NOT large (such as alcoves and closets) in comparison with the size of the appliance shall be listed for such installations. Listed clearances shall not be reduced by the protection methods described in Table 10.2.3(b) and illustrated in Figure 10.3.2.2(a) through Figure 10.3.2.2(c), regardless of whether the enclosure is of combustible or noncombustible material.
FIGURE 10.3.2.2(a) Extent of Protection Necessary to Reduce Clearances from Gas Appliance or Vent Connectors.
FIGURE 10.3.2.2(b) Wall Protector Clearance Reduction System.
FIGURE 10.3.2.2(c) Masonry Clearance Reduction System.
10.3.2.3 Unlisted central heating furnaces and lowpressure boilers installed in rooms that are large in comparison with the size of the appliance shall be installed with clearances not less than those specified in Table 10.2.3(a).
10.3.2.4 Central heating furnaces and lowpressure boilers (listed and unlisted) installed in rooms that are large in comparison with the size of the appliance shall be permitted to be installed with reduced clearances to combustible material provided the combustible material or appliance is protected as described in Table 10.2.3(b) (see 10.3.2).
10.3.2.5 Front clearance shall be sufficient for servicing the burner and the furnace or boiler.
10.3.2.6 Where the furnace plenum is adjacent to plaster on metal lath or noncombustible material attached to combustible material, the clearance shall be measured to the surface of the plaster or other noncombustible finish where the clearance specified is 2 in. (50 mm) or less.
10.3.2.7 The clearances to these appliances shall not interfere with combustion air, draft hood clearance and relief, and accessibility for servicing. (See 9.2.1, Section 9.3, and 12.13.7.)
10.3.2.8 Listed central heating furnaces shall have the clearance from supply ducts within 3 ft (0.9 m) of the furnace plenum be not less than that specified from the furnace plenum. No clearance is necessary beyond this distance.
10.3.2.9 Unlisted central heating furnaces with temperature limit controls that cannot be set higher than 250°F (121°C) shall have the clearance from supply ducts within 6 ft (1.8 m) of the furnace plenum be not less than 6 in. (150 mm). No clearance is necessary beyond this distance.
10.3.2.10 Central heating furnaces other than those listed in 10.3.2.8 or 10.3.2.9 shall have clearances from the supply ducts of not less than 18 in. (460 mm) from the furnace plenum for the first 3 ft (0.9 m), then 6 in. (150 mm) for the next 3 ft (0.9 m), and 1 in. (25 mm)
beyond 6 ft (1.8 m).
10.3.3 Assembly and Installation. A central heating boiler or furnace shall be installed in accordance with the manufacturer’s instructions and shall be installed on a floor of
noncombustible construction with noncombustible flooring and surface finish and with no combustible material against the underside thereof, or on fireresistive slabs or arches having no combustible material against the underside thereof.
Exception No. 1: Appliances listed for installation on a combustible floor.
Exception No. 2: Installation on a floor protected in an approved manner.
10.3.4 Temperature or PressureLimiting Devices. Steam and hot water boilers, respectively, shall be provided with approved automatic limiting devices for shutting down the burner(s) to prevent boiler steam pressure or boiler water temperature from exceeding the maximum allowable working pressure or temperature. Safety limit controls shall not be used as operating controls.
10.3.5 Low Water Cutoff. Hot water boilers installed above the radiation level and all steam boilers shall be provided with an automatic means to shut off the fuel supply to the burner(s) if the boiler water level drops to the lowest safe water line.
10.3.6* Steam Safety and Pressure Relief Valves. Steam and hot water boilers shall be equipped, respectively, with listed or approved steam safety or pressure relief valves of appropriate discharge capacity and conforming with ASME requirements. A shutoff valve shall not be placed between the relief valve and the boiler or on discharge pipes between such valves and the atmosphere.
10.3.6.1 Relief valves shall be piped to discharge near the floor.
10.3.6.2 The entire discharged piping shall be at least the same size as the relief valve discharge piping.
10.3.6.3 Discharge piping shall not contain threaded end connection at its termination point.
10.3.7 Furnace Plenums and Air Ducts.
10.3.7.1 Furnace plenums and air ducts shall be installed in accordance with NFPA 90A, Standard for the Installation of AirConditioning and Ventilating Systems, or NFPA 90B, Standard for the Installation of Warm Air Heating and AirConditioning Systems.
10.3.7.2 A furnace plenum supplied as a part of a furnace shall be installed in accordance with the manufacturer’s instructions.
10.3.7.3* Where a furnace plenum is not supplied with the furnace, any fabrication and installation instructions provided by the manufacturer shall be followed. The method of connecting supply and return ducts shall facilitate proper circulation of air.
10.3.7.4 Where a furnace is installed so supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
10.3.8 Refrigeration Coils. The installation of refrigeration coils shall comply with the
following requirements:
(1) A refrigeration coil shall not be installed in conjunction with a forced air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duct system and cooling coil and the air throughput necessary for heating or cooling, whichever is greater.
(2) Furnaces shall not be located upstream from cooling units, unless the cooling unit is designed or equipped so as not to develop excessive temperature or pressure.
(3) Refrigeration coils shall be installed in parallel with or on the downstream side of central furnaces to avoid condensation in the heating element, unless the furnace has been specifically listed for downstream installation. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be sufficiently tight to prevent any circulation of cooled air through the furnace.
(4) Means shall be provided for disposal of condensate and to prevent dripping of condensate on the heating element.
10.3.9 Cooling Units Used with Heating Boilers.
10.3.9.1 Boilers, where used in conjunction with refrigeration systems, shall be installed so that the chilled medium is piped in parallel with the heating boiler with appropriate valves to prevent the chilled medium from entering the heating boiler.
10.3.9.2 Where hot water heating boilers are connected to heating coils located in airhandling units where they can be exposed to refrigerated air circulation, such boiler piping systems shall be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.