A CEE block is created automatically when a C300 Controller function block is added to the Project tab.
Prerequisites
• Control Builder is running
• Tree windows are open
Considerations
All illustrations used in the procedure are for example purposes only.
To configure a CEEC300 function block
Step Action Result
Step Action Result 1 In the Project window, right-click on
the CEEC300_BLK block icon.
Calls up shortcut menu.
2 Click Module Properties... Calls up CEEC300 Block configuration form.
The Tag name field is highlighted.
Step Action Result
3 Key in desired name of up to 16 characters or accept the default.
Press <Tab>.
Moves cursor to Item Name field
4 Enter Item Name. Press <Tab>. Moves cursor to Base Execution Period field.
Step Action Result 5 Select the Base Execution Period
from the drop down list. Press <Tab>.
Note: Prior to select the IOLINK configuration for the controller, the base execution period must be selected. Otherwise, an error message appears as follows: "CEE BASEPERIOD can not be changed because IOLINK TYPE of at least one IOLINK of this C300 has been configured.”
For Honeywell Turbine Control Solutions, select the Base Execution Period as 20 ms.
Moves cursor to User Lock for CEE Run field.
Note that CEE Command field is available only in Monitor mode.
Once the Base Execution Period is selected, and configuration is configured and loaded to the C300 – 20, the Base Execution Period cannot be modified.
To modify it, refer to Control Hardware and I/O Modules Planning Guide.
6
Accept the default or click down-arrow button and select desired user.
Press <Tab>.
Moves cursor to User Lock for CEE Idle field.
7 Accept the default or click down-arrow button and select desired user.
Press <Tab>.
Moves cursor to Program Access may command CEE from Idle to Run check box.
8 Add a check to the box if you want to enable access. Press <Tab>.
Moves cursor to Program Access may command CEE from Run to Idle check box.
9 Add a check to the box if you want to enable access. Press <Tab>.
Moves cursor to the Alarming Enabled check box.
10 Accept the default (Alarming Enabled), or uncheck the box to disable alarming function. Press
<Tab>.
Moves cursor to the Enable Memory Limit Exceeded Alarm check box.
Step Action Result 11 Accept the default (Memory Limit
Exceeded Alarm enabled), or uncheck the box to disable alarming function.
Press <Tab>.
Moves cursor to the Powerup Restart Settings for CEE State.
12 Accept the default or click down-arrow button and select desired state.
Note that if you select LASTTIMEOUT state, then the Warm Timeout field is active.
13 If the Warm Timeout field is active, accept the default or key in desired timeout value. Press <Tab>.
Moves cursor to the Time Zone field.
14 Enter the appropriate value for the time zone of the controller location.
Press <Tab>.
Moves cursor to the Daylight Savings Time check box.
15 Add a check to the box if Daylight Savings Time is in effect for this location. Press <Tab>.
Note: The Daylight Savings Time check box is selected/cleared by default at the start/end of DST respectively if you have enabled the Automatically apply DST option.
Moves cursor to the Year Format field.
16
Accept the default or click down-arrow button and select desired format. Press <Tab>.
Moves cursor to the Weekday Format.
17
Accept the default or click down-arrow button and select desired format.
Click on the Peer Configuration tab.
The Store Expiration Time Field is highlighted in the Peer Defaults box.
18 Accept the default or key in desired value. Press <Tab>.
Moves cursor to Subscription Period field.
Step Action Result 19
Accept the default or click down-arrow button and select desired period. Press <Tab>.
Moves cursor to Number of Peer Environments field.
TIP
The Number of Peer Environments and Peer Environment Table are interactive. The value entered for the Number of Peer Environments determines how many rows appear in the Peer Environment Table.
20 Key in number of peer environments for this controller. Press <Tab>.
Or, skip this field, if no peer environments will be used. Click Server History tab and go to Step 25.
If peer environments will be used, cursor moves to the Peer Environment Name of column in the Peer Environment Table.
21 Key in valid name for existing peer environment.
Press <Tab>.
Moves cursor to Peer Subscription Period column.
22 Accept default or click down-arrow button to select another value specific to the given environment.
Press <Tab>.
Moves cursor to Store Expiration Time column.
23 Accept the default or key in desired value. Click Batch tab.
Moves cursor to Batch Events Memory field.
24
Accept the default or click down-arrow button and select desired state.
Click Server History tab.
Calls up the Server History configuration form.
Step Action Result 25 Use the on-line help as a guide to
complete the configuration entries on this tab. Click on the Server Displays tab.
Calls up the Server Displays configuration form.
26 Use the on-line help as a guide to complete the configuration entries on this tab. Click the OK button.
Closes the form.
This completes the configuration procedure for CEEC300 block.
REFERENCE - INTERNAL
See the Experion Control Builder Components Reference, Component Categories and Types and the Experion Planning Guide.