9.6.1 Connecting Appliances and Equipment. Appliances and equipment shall be  connected to the building piping in compliance with 9.6.4 through 9.6.6 by one of the  following: 

(1)  Rigid metallic pipe and fittings. 

(2)  Semirigid metallic tubing and metallic fittings. Aluminum alloy tubing shall not be  used in exterior locations. 

(3)  A listed connector in compliance with ANSI Z21.24, Standard for Connectors for  Gas Appliances. The connector shall be used in accordance with the manufacturer's  installation instructions and shall be in the same room as the appliance. Only one  connector shall be used per appliance. 

(4)  A listed connector in compliance with ANSI Z21.75, Connectors for Outdoor Gas  Appliances and Manufactured Homes. Only one connector shall be used per  appliance. 

(5)  CSST where installed in accordance with the manufacturer’s installation instructions. 

(6)  Listed nonmetallic gas hose connectors in accordance with 9.6.2. 

(7)  In 9.6.1(2), 9.6.1(3), 9.6.1(4), 9.6.1(5), and 9.6.1(6), the connector or tubing shall be  installed so as to be protected against physical and thermal damage. Aluminum alloy  tubing and connectors shall be coated to protect against external corrosion where  they are in contact with masonry, plaster, or insulation or are subject to repeated

wettings by such liquids as water (except rain water), detergents, or sewage. 

(8)  Materials addressed in 9.6.1(2), 9.6.1(3), 9.6.1(4), 9.6.1(5), and 9.6.1(6) shall not be  installed through an opening in an appliance housing, cabinet, or casing, unless the  tubing or connector is protected against damage. 

9.6.1.1 Commercial Cooking Appliances. Commercial cooking appliances that are moved  for cleaning and sanitation purposes shall be connected in accordance with the connector  manufacturer’s installation instructions using a listed appliance connector complying with  ANSI Z21.69, Connectors for Movable Gas Appliances. 

9.6.2 Use of Nonmetallic Gas Hose Connectors. Listed gas hose connectors shall be used  in accordance with the manufacturer's installation instructions and as follows: 

(1)  Indoor. Indoor gas hose connectors shall be used only to connect laboratory, shop,  and ironing appliances requiring mobility during operation. 

(a)  An appliance shutoff valve shall be installed where the connector is attached to  the building piping. 

(b)  The connector shall be of minimum length and shall not exceed 6 ft (1.8 m). 

(c)  The connector shall not be concealed and shall not extend from one room to  another or pass through wall partitions, ceilings, or floors. 

(2)  Outdoor. Outdoor gas hose connectors are permitted to connect portable outdoor  appliances. 

(a)  An appliance shutoff valve, a listed quick­disconnect device, or a listed gas  convenience outlet shall be installed where the connector is attached to the  supply piping and in such a manner so as to prevent the accumulation of water  or foreign matter. 

(b)  This connection shall be made only in the outdoor area where the appliance is to  be used. 

9.6.3 Connection of Portable and Mobile Industrial Appliances. 

9.6.3.1 Where portable industrial appliances or appliances requiring mobility or subject to  vibration are connected to the building gas piping system by the use of a flexible hose, the  hose shall be suitable and safe for the conditions under which it can be used. 

9.6.3.2 Where industrial appliances requiring mobility are connected to the rigid piping by  the use of swivel joints or couplings, the swivel joints or couplings shall be suitable for the  service required and only the minimum number required shall be installed. 

9.6.3.3 Where industrial appliances subject to vibration are connected to the building piping  system by the use of all metal flexible connectors, the connectors shall be suitable for the  service required. 

9.6.3.4 Where flexible connections are used, they shall be of the minimum practical length  and shall not extend from one room to another or pass through any walls, partitions, ceilings,  or floors. Flexible connections shall not be used in any concealed location. They shall be

protected against physical or thermal damage and shall be provided with gas shutoff valves in  readily accessible locations in rigid piping upstream from the flexible connections. 

9.6.4 Appliance Shutoff Valves and Connections. Each appliance connected to a piping  system shall have an accessible, approved manual shutoff valve with a nondisplaceable valve  member, or a listed gas convenience outlet. Appliance shutoff valves and convenience outlets  shall serve a single appliance only and shall be installed in accordance with 9.6.4.1. 

9.6.4.1 The shutoff valve shall be located within 6 ft (1.8 m) of the appliance it serves  except as permitted in 9.6.4.2 or 9.6.4.3. 

(1)  Where a connector is used, the valve shall be installed upstream of the connector. A  union or flanged connection shall be provided downstream from the valve to permit  removal of appliance controls. 

(2)  Shutoff valves serving decorative appliances shall be permitted to be installed in  fireplaces if listed for such use. 

9.6.4.2 Shutoff valves serving appliances installed in vented fireplaces and ventless firebox  enclosures shall not be required to be located within 6 ft (1.8 m) of the appliance where such  valves are readily accessible and permanently identified. The piping from the shutoff valve to  within 6 ft (1.8 m) of the appliance shall be designed, sized and installed in accordance with  Chapters 5, 6, and 7. 

9.6.4.3 Where installed at a manifold,  the appliance shutoff valve shall be located within  50  ft (15 m) of the appliance served and shall be readily accessible and permanently identified. 

The piping from the manifold to within 6 ft of the appliance shall be designed, sized and  installed in accordance with Chapters 5, 6, and 7. 

9.6.5 Quick­Disconnect Devices. 

9.6.5.1 Quick­disconnect devices used to connect appliances to the building piping shall be  listed to ANSI Z21.41/CSA 6.9, Quick­Disconnect Devices for Use with Gas Fuel 

Appliances. 

9.6.5.2 Where installed indoors, an approved manual shutoff valve with a nondisplaceable  valve member shall be installed upstream of the quick­disconnect device. 

9.6.6* Gas Convenience Outlets. Appliances shall be permitted to be connected to the  building piping by means of a listed gas convenience outlet, in conjunction with a listed  appliance connector, used in accordance with the manufacturer's installation instructions. 

9.6.7 Sediment Trap. Where a sediment trap is not incorporated as a part of the appliance,  a sediment trap shall be installed as close to the inlet of the appliance as practicable at the  time of appliance installation. The sediment trap shall be either a tee fitting with a capped  nipple in the bottom outlet as illustrated in Figure 9.6.7 or other device recognized as an  effective sediment trap. Illuminating appliances, ranges, clothes dryers, decorative appliances  for installation in vented fireplaces, gas fireplaces, and outdoor grills shall not be required to  be so equipped.

FIGURE 9.6.7  Method of Installing a Tee Fitting Sediment Trap. 

9.6.8 Installation of Piping. Piping shall be installed in a manner not to interfere with  inspection, maintenance, or servicing of the appliances. 

9.7 Electrical. 

9.7.1 Electrical Connections. Electrical connections between appliances and the building  wiring, including the grounding of the appliances, shall conform to NFPA 70, National  Electrical Code. 

9.7.2 Electrical Ignition and Control Devices. Electrical ignition, burner control, and  electrical vent damper devices shall not permit unsafe operation of the appliance in the event  of electrical power interruption or when the power is restored. 

9.7.3 Electrical Circuit. The electrical circuit employed for operating the automatic main  gas­control valve, automatic pilot, room temperature thermostat, limit control, or other  electrical devices used with the appliances shall be in accordance with the wiring diagrams  certified or approved by the original appliance manufacturer. 

9.7.4 Continuous Power. All appliances using electrical controls shall have the controls  connected into a permanently live electrical circuit — that is, one that is not controlled by a  light switch. Central heating appliances shall be provided with a separate electrical circuit. 