• No se han encontrado resultados

Si bé el tancament de les escoles suposava que els

In document LA METRÒPOLI (POST)-COVID (página 29-32)

Description

The main condensate system, as part of the steam generating cycle, is the section concerned with the circulation of boiler feed water from the atmospheric condenser via the observation tank and cascade/filter tank to the main feed pumps.

The drains from the steam services are normally led to the atmospheric condenser , which in turn drains to the observation tank and then to the cascade/filter tank. The level of the cascade tank is maintained by a float switch that operates a solenoid valve providing make up water from the storage tank. The condition of the condensate is monitored by a high salinity alarm.

The oil detecting alarm detects hydrocarbon contamination and the returns can be manually diverted to the waste oil tank. Any floating sediment can be drained through a scum line to the waste oil tank or the observation tank can be drained to the bilge holding tank. A weir in the observation tank outlet to the cascade tank prevents oil being carried over . The tank has a high and low level alarm.

Water from the cascade/filter tank provides the main feed pumps with a positive inlet head of pressure to the pump suctions.

The condensate outlet temperature from the atmospheric condenser should be maintained between 75°C and 90°C. This can be done by manipulating some of the drains to bypass the condenser and dischar ge directly to the cascade tank. A steam heating coil is provided in the cascade tank should extra heating be required.

Procedure for Preparing the Main Condensate System for Operation:

See illustrations 2.3.2a, 2.3.3a and 2.4.5a for valve positions mentioned below . a) Ensure that the pressure gauge and instrumentation valves are

open.

b) Fill the cascade tank from the distilled tank.

c) Check the correct operation of the level control valve.

d) Set up the valves as in the following table.

Position Description Valve

Open Outlet V alve from Atmospheric Condenser SL3 Closed Atmospheric Condenser Bypass V alves SL10, SL12

& SL13

Closed Observation T ank Drain V alve RL45

Open F.W. Make Up V alves to the Cascade T ank QG51

Open Run Down V alve from Distilled T ank QG24

Closed Observation T ank Scum V alve to Waste Oil T ank SL5

Open Outlet to Feed Pumps RL1

The feed pumps and boiler can now be put into operation.

Oil Contamination

If oil contamination occurs, divert the returns to the waste oil tank. Check the drain on the drain traps on all the steam services until the defective service is located, then isolate for repair .

After repair , flush the drain line of the defective service and clean drain trap.

Clean the observation tank and the oil content monitor probe.

2.3.2 Heating Drains Systems

Description

Condensate from the auxiliary steam services is returned to the cascade tank, through a seawater cooled atmospheric condenser and observation tank. The condensate is then returned to the feed water system. As there is a possibility of contamination from hydrocarbons from oil heating services, the drains are segregated and checked in the observation tanks before returning to the system.

All services can return to the cascade tank through the atmospheric condenser . In the interest of ef ficiency some drains can be fed directly to the observation tank or cascade tank to maintain the operating temperature. The condenser can be bypassed during maintenance, where oil heating drains are led to the observation tank and other services to the cascade tank.

Procedure for Preparing the Drains System for Operation

a) Ensure that the pressure gauges and instrumentation valves are open.

b) Set up the valves for the services required as in the following table:

Position Description Valve

Open Atmospheric Condenser Outlet V alve SL3

Open Drain V alve from Boiler Heating SL45

Open Drain V alve from Accommodation A.C. SL44 Open Drain V alve from Boiler F .O. and T ank Heating SL12

Open Drain V alve from Deck Seal SL48

Open Drain V alve from Car go Tank Heating SL1 Open Drain V alve from T ank Cleaning Heater SL07 Open Drain V alve from Purifier Heaters,

Double Bottom T anks and F .O. Storage T anks SL11 Open Drain Valve from M.E. F .O. and Auxiliary ServicesSL54 Open Atmospheric Condenser Cooling W ater Inlet V alveQA12 Open Atmospheric Condenser Cooling W ater Outlet V alveQA13 c) The various services can now be put into operation as required, by

opening the associated drain trap inlet and outlet valves.

Excessive temperature at the cascade tank would indicate a defective drain trap. Services should be isolated in turn until the defective trap is located.

P

Feed Water Cascade Tank

To Bilge Water Tank

To Bilge Water Tank From Atmospheric

Condenser

LAH

TI LAL SL5 LI

Main Feed Water Pump

13kg/cm2 Auxiliary Feed

Water Pump 11kg/cm2

P

P

PS P

No.2 No.1

P P

P P

No.2 No.1

From Chemical Dosing Station From Chemical

Dosing Station

Oil-Fired Boiler 25000 kg/h Exhaust Gas

Boiler 900 kg/h

Illustration 2.3.3a Boiler Feed Water System

Key

Feed Water

RL28

RL29

RL14

RL11 RL10

RL9 RL8 RL3 RL2

RL7

RL20

RL15 RL42

RL16

RL6

RL4

RL5

SL3

RL1

RL45

Fresh Water

2.3.3 Boiler Feed System

Description

The boiler feed system is the section of the steam generating plant which circulates feed water from the cascade tank into the steam drum of the boiler via the boiler feed water pumps and the feed water regulator.

The feed water flow is automatically controlled by the feed water regulating valve in proportion to the variation in water level in the steam drum.

Two boiler feed pumps take suction from the cascade tank and supply the boiler at a rate of 31m3/h at 13 kg/cm2. Each pump returns a small proportion of the discharge back to the cascade tank through an orifice, which prevents pump overheating when the feed water regulator is closed and when the boiler is on low load.

Feed water is supplied to the boiler through the feed water regulator. Feed water can also be supplied to the boiler using a separate auxiliary line, which can be used in an emergency. The standby feed pump will cut in on the failure of a running unit.

Two exhaust gas boiler feed pumps take suction from the cascade tank and supply the exhaust gas boiler at a rate of 1.35m3/h at 11 kg/cm2.

Boiler water chemical treatment is administered by injecting direct to the boiler drum using a chemical dosing unit.

Procedure for Preparing the Main Boiler Feed System for Operation:

a) Ensure pressure gauge and instrumentation valves are open.

b) Set up the valves as in the following table.

Position Description Valve

Open Feed Pump Suction Valve from Cascade Tank RL01 Open No.1 Boiler Feed Pump Suction Valve RL02 Open No.2 Boiler Feed Pump Suction Valve RL03 Open No.1 Boiler Feed Pump Recirculating Valve RL04 Open No.2 Boiler Feed Pump Recirculating Valve RL05 Open No.1 Boiler Feed Pump Main Feed Discharge Valve RL06 Open No.2 Boiler Feed Pump Main Feed Discharge Valve RL07 Open Crossover Between Main and Auxiliary Feed Line RL20

Open Feed Regulator Inlet Valve RL16

Open Main Feed Check Valve Closed Auxiliary Feed Check Valve

c) For initial start only, shut the discharge valve of the selected feed pump.

d) Start the pump and slowly open the discharge valve until the discharge line reaches working pressure.

e) Check the operation of feed check valve.

f) Fill boiler to working level.

g) Check the operation of the salinometer.

h) Switch the remaining pump to standby.

The boiler can now be brought into operation.

Procedure for Preparing the Exhaust Gas Boiler Feed System for Operation

a) Ensure that the pressure gauge and instrumentation valves are open.

b) Set up the valves as in the following table.

Position Description Valve

Open Feed Pump Suction Valve from Cascade Tank RL01 Open No.1 Exhaust Gas Boiler Feed Pump Suction Valve RL08 Open No.2 Exhaust Gas Boiler Feed Pump Suction Valve RL09 Open No.1 Exhaust Gas Boiler Feed Pump Discharge Valve RL10 Open No.2 Exhaust Gas Boiler Feed Pump Discharge Valve RL11 Open Boiler Feed Inlet Valve

c) For initial start only, shut the discharge valve of the selected feed pump.

d) Start the pump and slowly open the discharge valve until the discharge line reaches working pressure.

e) Switch the remaining pump to standby.

Oil-Fired Boiler 25000 kg/h Exhaust Gas

Boiler 900 kg/h

Illustration 2.3.4a Water Sampling and Treatment System

Key

Blowdown Line

Feed Water From

Domestic Fresh

Water Supply Sample Cooler

Sample Cooler

Sink

To Bilge To

Bilge

Sink

Chemical Dosing Station

From Main Feed Water Pump Chemical

Dosing Station

From Auxiliary Feed

Water Pump RL27

RL14

RL38 RL38

RL15

RL40 RL30

RL25

RL13 RL12 Fresh Water

2.3.4 Water Sampling and Treatment System

The main boiler and exhaust gas boiler are each provided with a sample cooler where a representative sample of the boiler water is obtained. The sample is tested on a daily basis using the chemical supplier's test kit.

Two chemical dosing units are provided, one for each system. They inject into the feed pump discharge lines using a metering pump which takes suction from the self contained chemical tank. The tank is charged with chemicals on a daily basis depending upon the results of the daily boiler water test and according to the manufacturer's instructions.

Boiler Water Testing Cabinet

Chemical Dosage Pump

TI

Illustration 2.4.1a Main and Auxiliary Sea Water Cooling Systems

QA11

To Inert Gas and Collection System

From Bilge Ballast and Fire System To Inert Gas and

Vapour Collection

In document LA METRÒPOLI (POST)-COVID (página 29-32)

Documento similar