• No se han encontrado resultados

Formulación del problema

I. INTRODUCCIÓN

1.4 Formulación del problema

Ideally the change to MDO should be undertaken whilst the main engine is running but under some circumstances it may be necessary to flush the fuel system with MDO whilst the engine is stopped. It should be remembered that the main engine is normally manoeuvred on HFO with HFO still remaining in the fuel system whilst the engine is stopped. Heavy fuel oil is recirculated from the main engine fuel manifold outlet back to the fuel mixing unit from where the FO booster pump takes suction. When changing from HFO to MDO during

engine standstill, the HFO in the fuel lines must be replaced by MDO and the HFO is flushed back to the HFO service tank, or the LSHFO service tank if the engine is operating on LSHFO, as it is replaced by MDO.

The procedure described below assumes that the fuel system is still circulated with hot HFO supplied from the HFO service tank.

a) Shut off the steam supply to the FO heaters.

b) Shut off the trace heating steam.

c) Sludge the MDO service tank to remove any water.

Regarding temperature levels before changeover, see ‘Changeover from Heavy Fuel to Diesel Oil during Running’.

d) Open the MDO service tank quick-closing outlet valve F-103V.

This valve will always be left open to supply MDO to the generator engines in the event of a blackout.

e) Open the MDO supply cross connection valve F-142V to supply MDO and close the HFO line supply valve F-141V to shut off HFO.

f) Close the operating HFO service tank quick-closing valve, either valve F-101V (or the LSHFO service tank valve F-102V).

g) Close the fuel mixing unit inlet valve F-128V. Ensure that there is sufficient ullage in the HFO service tank or the LSHFO service tank to accommodate the oil displaced from the fuel system. Ensure that the return 3-way control valve (F-139V) is positioned to the HFO service tank return. When operating on LSHFO position the 3-way valve to the LSHFO service tank.

h) The fuel oil feed booster pumps will pump MDO into the fuel system and displace the HFO.

i) When the HFO is replaced by MDO, open the inlet valve to the fuel mixing unit F-128V. It will take about 10 minutes for all of the HFO in the system to be displaced by MDO; a check can be made on the temperature of the inlet line to the fuel mixing unit as a drop in temperature will indicate the return of MDO rather than heated HFO. Some MDO will be pumped to the HFO service tank (or the LSHFO service tank if that has been operating) but the quantity will be small and the MDO will be diluted in the HFO in the tank.

j) When the system is filled with MDO the viscosity controller may be shut down if required.

Maersk Seletar Machinery Operating Manual

k) When convenient, the FO feed and booster pumps may be stopped.

g) Close the HFO service tank quick-closing valve F-101V (or the LSHFO service tank valve F-102V if LSHFO is being supplied).

The return valves on the HFO or LSHFO tank must be left open as there is no provision for return of fuel to the MDO service tank.

note: If, after the changeover, the temperature at the heater suddenly drops considerably, the transition must be moderated by supplying a small amount of steam to the heater.

note: The generator engines will be changed to MDO operation at the same time as the main engine and the operation of the generator engines must also be monitored during this changeover period. In order to prevent generator engine instability problems occurring at the same time it is preferable to change the generator engines to MDO operation separately: see section 2.6.2 of this machinery operating manual.

Maersk Seletar Machinery Operating Manual

To Oily Bilge Tank (Dirty Side) To Oily Bilge Tank (Dirty Side) To Overflow

Tank

TI

TI DPS

PI

DPAHMC MS

Illustration 2.6.2a Generator Engines Fuel Oil Service System

Key Fuel Oil Marine Diesel Compressed Air Steam Condensate Waste Oil Electric Signal Heavy Fuel

Oil Service Tank (188.3m3)

Heavy Fuel Oil Settling Tank (157.6m3)

Low Sulphur Heavy Fuel Oil Service Tank (157.6m3)

Low Sulphur Heavy Fuel Oil Settling Tank (157.1m3)

F-102V F-110V F-101V F-104V

F-227V F-140V

F-141V F-142V

AuxiliaryTo Boiler Marine Diesel

Oil Service Tank (162.4m3)

F-103V

To Fuel Oil Overflow Tank F-105V

F-107V

F-112V F-113V F-249V

F-241V

F-114V Fuel Oil Feed Pumps

(18.5m3/h x 5kg/cm2) PI F-106V

F-109V

F-108V

Fuel Oil Booster Pumps (33.9m3/h x 12kg/cm2)

Fuel Oil Auto Backflushing Filter Bypass Filter

PI

F-185V F-139V F-130V

F-184V

F-226V Set at 6.5kg/cm2 Set at 5.5kg/cm2

MixingFuel Unit

TI

PI F-186V

F-228V

No.1 Fuel Oil Heater

No.2 Fuel Oil Heater

F-120V FromMain

Engine

CI PI

Generator Engine Marine Diesel Oil Service Pumps

(4.8m3/h x 8kg/cm2) PS

CI F-231V PI

F-229V

Generator Engine Emergency Marine Diesel Oil Pump

(1.26m3/h x 6kg/cm2)

Starting Air

F-206V S

To Main Engine

TIAHL MC TX PIALMC

PX LAHMC LS

DPS DPAHMC No.4 Generator Engine

F-155V PIALMC

PX LAHMC LS

DPS DPAH MC No.3 Generator Engine

F-154V PIALMC

PX LAHMC LS

DPS DPAHMC No.2 Generator Engine

F-153V PIALMC

PX LAHMC LS

DPS DPAHMC No.1 Generator Engine

F155V Return Flow Meter

Supply Flow Meter

Flow Meter

Control Air

Control Air

Control Air

Maersk Seletar Machinery Operating Manual

2.6.2 Generator enGines fueL oiL serViCe systeM diesel oil service pump (electrically powered)

Manufacturer: Taiko Kikai Industries Co. Ltd..

No. of sets: 2

Type: Screw Type NHGH-5MTB

Capacity: 4.8m³/h at 8kg/cm²

emergency diesel oil pump (pneumatically powered)

Manufacturer: XX

No. of sets: 1

Type: Screw

Capacity: 1.26m³/h at 6kg/cm²

introduction

generator engines and this is set to maintain the oil pressure at 8.0kg/cm2. Fuel oil from the main FO line passes through a flow meter to the generator engine supply manifold and then to the individual generator engines.

The HFO line to the generator engines is fitted with a spill valve (set at 10.0kg/

cm2) and this prevents excess pressure building up in the generator engine fuel supply manifolds. The fuel released by this valve flows to the return fuel line and back to the fuel mixing unit via a flow meter.

There are supply and return connections to the generator engines from the generator engine MDO service pumps for flushing and for operation on MDO when required. Individual generator engines may be changed to MDO operation with the other engines operating on HFO. The MDO common return line from the generator engines is fitted with a pressure regulating valve (set to 2.0kg/cm2) and this maintains the desired backpressure in the generator engine fuel manifolds when operating on MDO. Return MDO flows back to the MDO service tank. The supply pressure in the MDO manifold from the generator engine MDO service pump is maintained by a pressure release valve set at a pressure of 6.0kg/cm2.

Each generator engine fuel main inlet is fitted with a quick-closing valve which is operated from a control station outside the generator room concerned.

The high pressure fuel injection lines on the engine are sheathed and any leakage from the annular spaces formed by the sheathing is led to the leakage alarm tank on the engine and then to the dirty section of the oily bilge tank.

procedure for the operation of the Generator engine fuel oil

Documento similar