Operating noises are undesirable, in particu-lar, if the system is installed indoors. For this reason, the deltachiller® Turbo is equipped with a magnetically suspended and touch-free compressor technology. This way, noteworthy mechanical vibrations are not created. As a result, the sound level is extremely low – and additional constructional measures for sound protection can usually be dispensed with in their entirety.

Project-specific plant manager

The integrated control system having the form of an industry-adjusted control unit ensuring the efficient opera-tion of the refrigerating unit forms the core of the deltachil-ler Turbo.

A superior control unit in a separate control cabinet is required for interconnected operation on the part of the refrigerating machine. The cold manager has the task of controlling the optimum operating point for group-focused and partial load-optimised refrigerating machine operation for the best possible energy efficiency. To this end, it calcu-lates the optimum values on the basis of the internal control algorithms and adjusts the operating conditions to these.

As an option, controlling of the overall system can be taken over. In this case, system segments, such as re-cooling, pumps for the cold- and cooling-water-side media circula-tion or the free cooling funccircula-tion can be integrated into performance optimisation –and the overall system works even more energy efficiently with a project-specific plant manager.

Oil free is carefree

A special feature of the deltachiller® Turbo is its oil-free op-eration. This form of operation entails several advantages.

Of course, it reduces the maintenance effort required, which saves times and money. This is due to the simple fact that oil does not have to be provided and, as a result, disposed of. Moreover, compared with refrigerating systems using oil, such as e.g. screw compressor units, the annual efficiency is better without an oil pump. And, finally, the strict rules of the German Water Resources Act do not apply if the system is oil-free.

deltachiller® Turbo (water-cooled unit)

Modular maintenance during operation

A modular structure was consciously selected for the del-tachiller® Turbo: This saves time and money. The modular design on the basis of marketable components ensures direct availability, short delivery times and a trouble-free installation. Moreover, there is no need to build an exces-sive stock of spare parts.

Furthermore, this design permits the compressors to be replaced while the system is in operation without interfer-ing in the refrigeration cycle. This ensures the refrigeration supply at all times. The operating and/or industrial process-es are not affected in any way.

Ready for even the highest temperatures

The intelligently designed heat exchanges and the oil-free turbo compressor work absolutely reliably even at maximum operating temperatures. The intrinsically safe design ensures safe operation since the maximum operat-ing pressures of the heat exchangers cannot be exceeded.

As a result, the deltachiller® Turbo is significantly more leak-proof. It fulfils all valid EU guidelines and is ready for operation without safety valves.

Protection against power outages

On request, Weiss can equip the deltachiller® Turbo for operation using an uninterruptible power supply to be provided by the customer. This ensures the refrigeration supply even in the event of a potential power outage. The Turbo automatically switches to emergency operation and maintains all functions. The refrigeration supply remains stable and in line with the individual design of the plant or with the capacity of the upstream UPS system at all times.

Refrigerant monitoring

Pursuant to EN 842, leakage and leak tests are required by law up to four times per year depending on the filling quantity of the refrigerant. Weiss uses leakage detection systems in the deltachiller® Turbo. They are used to detect leakages early on and reduce the costs for the required tests.

Leakage detection systems are prescribed for all refriger-ants with filling levels >25 kg, OPD>0 and GWP>0, on principle. Even though these systems are not required for smaller filling quantities, they significantly extend the prescribed testing intervals.

The deltachiller® Turbo as a heat pump

As a special feature of the deltachiller® Turbo, it can be operated as a heat pump: In this form of operation, it produces heat instead of refrigerating.

The system optionally withdraws energy from the soil, the ground water or the outside air and, e.g., converts it into useful thermal energy through the optional double condenser. In addition to the so-called dissipation circuit, thermal energy created in the process can be recovered directly via a closed heating circuit.

Therefore, as a heat pump, the deltachiller® Turbo provides an interesting alternative to the usual heating systems, e.g. in order to heat buildings, industrial facili-ties or swimming pools.

Compressor

evaporator condenser

expansion element (throttle)

energy drain

Energy source

deltachiller® Turbo

Overview of a heat pump

Model WT_.3 250 400 550 Cooling capacity with 20 % Antifrogen N 16/10 °C 20/14 °C 16/10 °C 20/14 °C 16/10 °C 20/14 °C

Cooling capacity kW 250 280 400 460 550 620

Heat exchanger 40/45 °C

Condenser output kW 310 339 493 552 684 755

Volume flow m³/h 56 63 91 103 127 130

Pressure drop kPa 48 56 30 36 53 55

Connection DN 80 80 125 125 125 125

Free cooling capacity upon ingress of water 16 °C 20 °C 16 °C 20 °C 16 °C 20 °C

Outside temperature 10 °C kW 270 340 540

Outside temperature 5 °C kW 325 420 650

Refrigerating circuit

Type TURBO compressor

Number of compressors Qty. 1 1 2 2 2 2

Refrigerating circuit Qty. 1 1 1 1 1 1

Refrigerant R134a

Connection voltage V/Ph/Hz 400/3/50

Compressor power consumption, total kW 60 59 93 92 134 135

Operating current, max. A 95 94 150 149 212 213

COP 4.8 4.8 4.3 5.0 4.1 4.6

Cold water circuit

Water quantity m³/h 36 40 57 66 79 89

Pressure loss kPa 43 49 26 31 40 45

Connection DN 80 80 125 125 125 125

Heat exchanger blowers

Type Axial blowers

Number Qty. 8 8 12 12 16 16

Connection voltage V/Ph/Hz 400/3/50

Power consumption per blower kW 1.9 1.9 1.8 1.8 1.9 1.9

Operating current, max., per blower A 2.9 2.9 2.8 2.8 2.9 2.9

Sound data refrigerating machine

Sound power level +/- 3 dB dB (A) 86 86 89 89 89 89

Free field sound power level (1 m distance) dB (A) 68 68 71 71 71 71

Sound data heat exchanger

Sound power level dB (A) 89 89 91 91 92 92

Free field sound power level (10 m

dis-tance) dB (A) 61 61 63 63 64 64

Base unit refrigeration

Length mm 2,600 2,600 3,700 3,700 3,700 3,700

Depth mm 990 990 1,130 1,130 1,130 1,130

Height mm 1,950 1,950 2,000 2,000 2,000 2,000

Weight kg 2,050 2,050 3,015 3,015 3,015 3,015

Heat exchanger

Length mm 5,565 5,565 7,935 7,935 2 x 5,565 2 x 5,565

Depth mm 2,300 2,300 2,300 2,300 2 x 2,300 2 x 2,300

Height mm 2,850 2,850 2,850 2,850 2 x 2,850 2 x 2,850

Weight kg 2,600 2,600 3,540 3,540 2 x 2,600 2 x 2,600

Technical data

deltachiller® Turbo

Model WT_.3 850 900 1.100

Cooling capacity with 20 % Antifrogen N 16/10 °C 20/14 °C 16/10 °C 20/14 °C 16/10 °C 20/14 °C

Cooling capacity kW 850 960 900 1.030 1.100 1.250

Heat exchanger capacity 40/45 °C

Condenser capacity kW 1.058 1.168 1.105 1.234 1.359 1.509

Volume flow m³/h 197 217 205 229 252 280

Pressure drop kPa 49 59 34 41 49 59

Connection DN 150 150 200 200 200 200

Free cooling capacity upon ingress of water 16 °C 20 °C 16 °C 20 °C 16 °C 20 °C

Outside temperature 10 °C kW 810 810 1.370

Outside temperature 5 °C kW 975 975 1.260

Refrigerating circuit

Type TURBO compressor

Number of compressors Qty. 3 3 4 4 4 4

Refrigerating circuit Qty. 1 1 1 1 1 1

Refrigerant R134a

Connection voltage V/Ph/Hz 400/3/50

Compressor power consumption, total kW 208 208 205 204 259 259

Operating current, max. A 329 329 329 327 410 410

COP 4.1 4.6 4.4 5.1 4.2 4.8

Cold water circuit

Water quantity m³/h 121.7 137.7 128.9 147.8 157.5 179.3

Pressure loss kPa 34 40 29 34 38 44

Connection DN 125 125 150 150 150 150

Heat exchanger blower

Type Axial blowers

Number Qty. 24 24 24 24 48 48

Connection voltage V/Ph/Hz 400/3/50

Power consumption per blower kW 1.9 1.9 1.9 1.9 1.8 1.8

Operating current, max., per blower A 2.9 2.9 2.9 2.9 2.8 2.8

Sound data refrigerating machine

Sound power level +/- 3 dB dB (A) 90 90 91 91 91 91

Free field sound power level (1 m distance) dB (A) 71 71 72 72 72 72

Sound data heat exchanger

Sound power level dB (A) 94 94 94 94 96 96

Free field sound power level (10 m distance) dB (A) 66 66 66 66 68 68

Base unit refrigeration

Length mm 4,270 4,270 4,270 4,270 4,270 4,270

Depth mm 1,461 1,461 2,210 2,210 2,210 2,210

Height mm 2,400 2,400 2,050 2,050 2,050 2,050

Weight kg 4,695 4,695 5,865 5,865 5,865 5,865

Heat exchanger

Length mm 3 x 5,565 3 x 5,565 3 x 5,565 3 x 5,565 4 x 7,935 4 x 7,935

Depth mm 3 x 2,300 3 x 2,300 3 x 2,300 3 x 2,300 4 x 2,300 4 x 2,300

Height mm 3 x 2,850 3 x 2,850 3 x 2,850 3 x 2,850 4 x 2,850 4 x 2,850

Weight kg 3 x 2,600 3 x 2,600 3 x 2,600 3 x 2,600 4 x 3,540 4 x 3,540

We reserve the right to make technical improvements.