Setting and display of the EC fan load
Master/slave switching (up to 8 units)
Continuous redundancy with automatic activation
Automatic reactivation of the unit with adjustable time delay
UPS operation (without heating and humidification)
Manual operation level
Recording of alarms with date and time
Alarm indications: air flow failure, filter soiling, temperature and humidity limit alarms, heater and humidifier fault (if present)
Minimum supply air limit via cascade
The deltaclima® FC TELCO LINE compact systems are equipped with a SAIA PCD control system as a standard. In addition to the usual exhaust/intake cascade regulation, the opti-mised software makes a whole host of other functions possible, for example:
BeOperating console
5.7 ‘‘ TFT display
VGA 640 x 480
65536 colours
Front installation
Protection class IP65
Controller
Microprocessor, Motorola CF 5272, 66 MHz
1 MB RAM
Battery-backed, clock
Ethernet interface deltaclima® FC TELCO LINE
FC
Accessories and equipment options
With the following equipment options, deltaclima® FC TELCO LINE can be optimally adapted to different climate control and installation situations:
Digital-Scroll compressor (DX)
3-way valve (CW)
Fan protection grid (CW+DX)
Filter class F7 (CW+DX)
deltaclima® FC TELCO LINE – The advantages at a glance
Specifically designed for IT rooms with direct access to the outside air
Direct use of outside air through additional housing structure
Low installation efforts
Mechanical cooling can be integrated as needed
Double supply USP operation
Steam humidifier (CW+DX)
Electrical re-heater (CW+DX)
Smoke, fire and water detectors (CW+DX)
Maximum humidity sensor (CW+DX)
Housing
High housing rigidity, thanks to the welded and painted design of the frame sections
Housing casing removable all round (thickness of side and rear walls of 1.25 mm each)
Door wall thickness 1.5 mm
Immersion prime coating and powder coating, RAL 9005 structure
Foamed-in PU gasket
Transportation with crane eyelets possible
Innovative design
Controller/Regulator
Electrical section and controller are sealed off from the air-treatment section on the air side
This allows inspection and maintenance work to be carried out while the unit is in operation
Mains switch accessible from the outside
Encoded plug connections for fan and sensors
Separation of power supply A and B possible
Filter
G4 cassette air circulation filter, F7 optional
Installed directly on the heat exchanger
Filter changed from the front
Filter seal replaced when filter is changed
Fiberplast frame
Continuous filter monitoring via differential pressure sensor
Cooling DX
Large-surface Cu/Al direct evaporator with hydrophilic coating
Slat spacing is greater than 2 mm, allowing easy access for cleaning work
Low passage speed, which results in reduced pressure loss
Aluminium condensate pan is easy to remove and clean
Includes self-filling, closable siphon
Cold circuit with SCROLL compressors, incl. Rotalock valves and oil sight glass
Refrigerant dryer with screw connections, no soldering required when replacing the dryer
Easy connection by customer
Cooling CW
Large-surface Cu/Al direct evaporator with hydrophilic coating
Slat spacing is greater than 2 mm, allowing easy access for cleaning work.
Low passage speed, which results in reduced pressure loss
Aluminium condensate pan is easy to remove and clean
Includes self-filling, closable siphon
Cooling circuit with internal piping, including continuous 2-way valve, optional 3-way valve
Material: Brass or red brass
Easy connection by customer
Electronic expansion valve
Optimum injection of the respective coolant quantity
Exact and precise overheating regulation saves energy
COP is increased during partial-load operation
Dehumidification switching via EEV with constant air volume
Fan
High-performance radial fan optimised for efficiency, no spiral housing, features backward-curved blades, one-sided intake
Drive motor integrated as EC external rotor in wheel
The fan speed is set according to the individual volume flow via the EC regulator.
The fan motor unit is installed in the base frame and can easily be pulled out from the front.
One to three fans per unit
Base frame
Vibration-insulated unit feet
Height can be adjusted individually (adjustment range: 50 mm)
Technical data
Model TELCO LINE ∆T = 10 K 60.4 DX FC 85.4 DX FC 125.4 DX FC 160.4 DX FC
Size 11.9 11.9 14.9 18.9
General contract number - Unit 7000001440 7000001442 7000001445 7000001446
General contract number – Top part 7000001465 7000001466 7000001467 7000001468
Nominal volume flow
Air quantity m3/h 4,200 8,400 22,500 16,000
External pressing Pa 150 150 150 150
Max. external pressing Pa 240 420 170 420
Cooling DX – R407C Condensation temperature 50 °C and air intake 32 °C / 35 % rel. humidity
Type DIGITAL-SCROLL COMPRESSOR
Number of compressors Qty. 1 2 3 3
Coldness output, total kW 14.1 28.2 42.7 54.4
Coldness output, sensitive kW 14.1 28.2 42.7 54.4
SHR (Sensible Heat Ratio) 1.00 1.00 1.00 1.00
Power consumption, total kW 3.6 7.2 11.3 13.7
Max. current consumption A 10.3 20.6 38.4 39.3
Filter at intake
Type Cassette filter
Filter class as per DIN EN 779 F7 F7 F7 F7
Fan unit
Type EC motor, direct driven, free-wheeling
Number Qty. 1 1 1 2
Power consumption, total kW 0.4 1.18 2.14 2.38
Max. current consumption A 1.6 4.3 4.3 8.6
Sound data
Sound output level, low-pressure side dB (A) 57 65 71 68
Sound output level, high-pressure side dB (A) 68 75 82 78
Housing emission dB (A) 43 49 56 53
Free-field sound pressure level (2 m distance) dB (A) 40 48 54 51
Model TELCO LINE ∆T = 14 K 60.4 DX FC 110.4 DX FC 220.4 DX FC 330.4 DX FC
Size 11.9 11.9 14.9 18.9
General contract number - Unit 7000001441 7000001443 7000001446 7000001448
General contract number – Top part 7000001465 7000001466 7000001467 7000001468
Nominal volume flow
Air quantity m3/h 3,000 6,000 10,000 13,000
External pressing Pa 150 150 150 150
Max. external pressing Pa 310 540 380 500
Cooling DX – R407C Condensation temperature 50 °C and air intake 36 °C / 30 % rel. humidity
Type DIGITAL-SCROLL COMPRESSOR
Number of compressors Qty. 1 2 3 3
Coldness output, total kW 14.1 28.2 46.3 61.1
Coldness output, sensitive kW 14.1 28.2 46.3 61.1
SHR (Sensible Heat Ratio) 1.00 1.00 1.00 1.00
Power consumption, total kW 3.6 7.2 12 15.1
Max. current consumption A 10.3 20.6 38.4 39.3
Filter at intake
Type Cassette filter
Filter class as per DIN EN 779 F7 F7 F7 F7
Fan unit
Type EC motor, direct driven, free-wheeling
Number Qty. 1 1 1 2
Power consumption, total kW 0.27 0.68 1.35 1.66
Max. current consumption A 1.6 4.3 4.3 8.6
We reserve the right to make technical improvements.
deltaclima® DX FC TELCO LINE
Size W (width) H (height) D (depth) H1 H2 H3
60.4 DX FC 11.9 1,100 2,500 895 550 1,950 800
85.4 DX FC 11.9 1,100 2.550 895 600 1,950 800
125.4 DX FC 14.9 1,400 2,550 895 600 1,950 800
160.4 DX FC 18.9 1,800 2,550 895 600 1,950 800
T
B
H2 H3
H1 Unit view
Free-field sound pressure level (2 m distance) dB (A) 36 45 50 49
Base unit
Width mm 1,100 1,100 1,400 1,800
Depth mm 895 895 895 895
Height (above double floor) mm 1,950 1,950 1,950 1,950
Height (below double floor) mm 550 600 600 600
Min. double floor height mm 350 400 400 400
Footprint m2 0.98 0.98 1.25 1.61
Weight (incl. base frame and FC top) kg 560 621 720 1,071
Connection voltage V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50
Model TELCO LINE ∆T = 10 K 60.4 CW FC 110.4 CW FC 220.4 CW FC 330.4 CW FC
Size 11.7 11.9 18.9 26.9
General contract number - unit 7000001449 7000001451 7000001453 7000001455
General contract number - top 7000001469 7000001470 7000001471 7000001472
Nominal volume flow
Air quantity m3/h 4,200 7,000 14,000 25,200
External pressing Pa 150 150 150 150
Max. external pressing Pa 230 530 510 440
Cooling CW – Cold water 10 °C / 16 °C and air intake 32 °C / 35 % rel. humidity
Coldness, total kW 14.5 24.2 47.9 87.3
Coldness, sensitive kW 14,5 24,2 47,9 87,3
SHR (Sensible Heat Ratio) 1.00 1.00 1.00 1.00
Medium volume flow m³/h 2.09 3.47 6.87 12.52
Pressure loss of cooler kPa 13,7 14,9 15,5 18
Pressure loss of valve kPa 4.4 4.7 7.6 9.8
Connection Inch Rp 1 Rp 1 1/4 Rp 1 1/2 Rp 2
Filter at intake
Type Cassette filter
Filter class as per DIN EN 779 F7 F7 F7 F7
Fan unit
Type EC motor, direct driven, free-wheeling
Number Qty. 1 1 2 3
Power consumption, total kW 0.44 0.78 1.65 3.38
Max. current consumption A 1.6 4.3 8.6 12.9
Sound data
Sound output level, low-pressure side dB (A) 57 61 65 69
Sound output level, high-pressure side dB (A) 69 72 75 79
Housing emission dB (A) 43 46 50 54
Free-field sound pressure level (2 m distance) dB (A) 40 45 48 52
Model TELCO LINE ∆T = 14 K 60.4 DX FC 110.4 DX FC 220.4 DX FC 330.4 DX FC
Size 11.7 11.9 18.9 26.9
General contract number - unit 7000001450 7000001452 7000001454 7000001456
General contract number - top 7000001469 7000001470 7000001471 7000001472
Nominal volume flow
Air quantity m3/h 3,000 5,000 10,000 18,000
External pressing Pa 150 150 150 150
Max. external pressing Pa 290 580 570 550
Cooling CW – Cold water 10 °C / 16 °C and air intake 36 °C / 30 % rel. humidity
Coldness, total kW 14.1 23.4 46.5 84.6
Coldness, sensitive kW 14,1 23,4 46,5 84,6
SHR (Sensible Heat Ratio) 1.00 1.00 1.00 1.00
Medium volume flow m³/h 2.02 3.36 6.67 12.14
Pressure loss of cooler kPa 13 14,2 14,7 17
Pressure loss of valve kPa 4.1 4.4 7.1 9.2
Connection Inch Rp 1 Rp 1 1/4 Rp 1 1/2 Rp 2
Filter at intake
Type Cassette filter
Filter class as per DIN EN 779 F7 F7 F7 F7
Fan unit
Type EC motor, direct driven, free-wheeling
Number Qty. 1 1 2 3
Power consumption, total kW 0.28 0.49 1.03 1.95
Max. current consumption A 1.6 4.3 8.6 12.9
We reserve the right to make technical improvements.
deltaclima® CW FC TELCO LINE
Size W (width) H (height) D (depth) H1 H2 H3
60.4 CW FC 11.7 1.100 2.500 695 550 1.950 800
110.4 CW FC 11.9 1.100 2.550 895 600 1.950 800
220.4 CW FC 18.9 1.800 2.550 895 600 1.950 800
330.4 CW FC 26.9 2.600 2.550 895 600 1.950 800
T
B
H2 H3
H1 Unit view
Free-field sound pressure level (2 m distance) dB (A) 36 41 47 49
Base unit
Width mm 1,100 1,100 1,800 2,600
Depth mm 695 895 895 895
Height (above double floor) mm 1,950 1,950 1,950 1,950
Height (below double floor) mm 550 600 600 600
Min. double floor height mm 350 400 400 400
Footprint m2 0.76 0.98 1.61 2.33
Weight (incl. base frame and FC top) kg 460 520 790 1,138
Connection voltage V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50
Condensers
Condenser model KLDR 2.2 KLDR 3.2 KLDR 4.2 KLDR 5.2 KLDR 6.2 KLDR 7.2 Condensation temperature 50 °C and air intake 35 °C / 34 % rel. humidity
Unity types 30.4 DX 60.4 DX 85.4 DX 125.4 DX 160.4 DX
30.4 DX 60.4 DX 85.4 DX 125.4 DX 160.4 DX
Type Axial blower condenser
Number of fans Qty. 1 1 2 2 2 3
Max. air quantity m3/h 7,000 8,300 14,000 17,600 18,600 27,900
Condenser output kW 19.1 29.5 38.2 53.6 70.1 105.2
Max. power consumption kW 0.68 0.60 1.36 1.20 1.20 1.80
Max. current consumption A 3.0 2.6 6.0 5.2 5.2 7.9
Max. free field sound press
level (5 m distance) dB (A) 51 47 54 50 50 52
Width (A+C) mm 1,025 1,175 1,775 2,075 2,775 4,025
Depth, vertical (B1)* mm 750 900 1,500 1,800 2,500 3,750
Depth, horizontal (B2)* mm 842 1,130 842 1,130 1,130 1,130
Depth, horizontal (B3) mm 740 740 740 740 740 740
Depth, horizontal (B4)* mm 470 470 470 470 470 470
Height, vertical (D) mm 1,100 1,140 1,100 1,140 1,140 1,140
Height, horizontal (E) mm 840 1,130 840 1,130 1,130 1,130
Height, horizontal (F) mm 1,160 1,450 1,160 1,450 1,450 1,450
Weight kg 95 140 150 210 275 395
Connection voltage V/Ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
*Mounting holes
We reserve the right to make technical improvements.
Execution (V) – vertically blowing Execution (H) horizontally blowing
Execution (H) horizontally blowing