Setting values in: Secondary value description
P R I N T - C O N T E N T S
2.1 Group Device, General Settings; Group General...4 3 Power System Data 1
...4 3.1 Group Power System Data 1; Group Power System
...4 3.2 Group Power System Data 1; Group Prot.Op. quant.
...4 3.3 Group Power System Data 1; Group CT's
...5 3.4 Group Power System Data 1; Group VT's
...5 3.5 Group Power System Data 1; Group Breaker
...5 3.6 Group Power System Data 1; Group Threshold BI
...6 4 Settings groups
...6 4.1 Group Power System Data 2; Group General
...6 4.2 Group 50/51 Phase/Ground Overcurrent; Group General
...6 4.3 Group 50/51 Phase/Ground Overcurrent; Group 50
...7 4.4 Group 50/51 Phase/Ground Overcurrent; Group 51
...7 4.5 Group 50/51 Phase/Ground Overcurrent; Group 50N
...8 4.6 Group 50/51 Phase/Ground Overcurrent; Group 51N
...8 4.7 Group 67 Directional Phase/Ground Overcurrent; Group General
...8 4.8 Group 67 Directional Phase/Ground Overcurrent; Group 67
...9 4.9 Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC
...9 4.10 Group 67 Directional Phase/Ground Overcurrent; Group 67N
...9 4.11 Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC
...10 4.12 Group Measurement Supervision; Group General
...10 4.13 Group Measurement Supervision; Group MeasSupervision
...10 4.14 Group Measurement Supervision; Group Fuse Fail Mon.
...11 4.15 Group Measurement Supervision; Group VT broken wire
...11 4.16 Group Energy; Group Measurement
Page 1 of 11
1
Device Configuration
No. Function Scope
0103 Setting Group Change Option Disabled 0104 Oscillographic Fault Records Enabled
0112 50/51 Time Overcurrent Curve IEC
0113 50N/51N Time Overcurrent Curve IEC
0115 67, 67-TOC Time Overcurrent Curve IEC
0116 67N, 67N-TOC Time Overcurrent Curve IEC
0117 Cold Load Pickup Disabled
0122 2nd Harmonic Inrush Restraint Disabled
0131 (sensitive) Ground fault Disabled
0130 (sens.) Ground fault dir. characteristic cos phi / sin phi measurement (standard) 0140 46 Negative Sequence Protection Disabled
0142 49 Thermal Overload Protection Disabled 0150 27, 59 Under/Overvoltage Protection Disabled 0154 81 Over/Underfrequency Protection Disabled 0170 50BF Breaker Failure Protection Disabled 0172 52 Breaker Wear Monitoring Disabled 0182 74TC Trip Circuit Supervision Disabled 0192 Capacitive voltage measurement NO
Flexible Function
Page 2 of 11
2
General Device Settings
2.1
Group Device, General Settings; Group General
Group Device, General Settings; Group General
No. Settings Value Group
0610 Fault Display on LED / LCD Display Targets on every Pickup All
0611 Spontaneous display of flt.annunciations NO All
0640 Start image Default Display image 1 All
Page 3 of 11
3
Power System Data 1
3.1
Group Power System Data 1; Group Power System
Group Power System Data 1; Group Power System
No. Settings Value Group
0214 Rated Frequency 50 Hz All
0209 Phase Sequence A B C All
0201 CT Starpoint towards Line All
0280 Holmgreen-conn. (for fast sum-i-monit.) NO All
0251A CT Connection Ia, Ib, Ic, (IGnd) All
0213 VT Connection, three-phase Van, Vbn, Vcn All
0235A Storage of th. Replicas w/o Power Supply YES All
3.2
Group Power System Data 1; Group Prot.Op. quant.
Group Power System Data 1; Group Prot.Op. quant.
No. Settings Value Group
0250A 50, 51 Time Overcurrent with 2ph. prot. OFF All 0613A Ground Overcurrent protection with Ignd (measured) All
3.3
Group Power System Data 1; Group CT's
Group Power System Data 1; Group CT's
No. Settings Value Group
0204 CT Rated Primary Current 400 A All 0205 CT Rated Secondary Current 1A All 0217 Ignd-CT rated primary current 400 A All 0218 Ignd-CT rated secondary current 1A All
Page 4 of 11
3.4
Group Power System Data 1; Group VT's
Group Power System Data 1; Group VT's
No. Settings Value Group
0202 Rated Primary Voltage 33.00 kV All
0203 Rated Secondary Voltage (L-L) 110 V All
0206A Matching ratio Phase-VT To Open-Delta-VT 1.73 All
3.5
Group Power System Data 1; Group Breaker
Group Power System Data 1; Group Breaker
No. Settings Value Group
0210A Minimum TRIP Command Duration 0.15 sec All 0211A Maximum Close Command Duration 1.00 sec All 0212 Closed Breaker Min. Current Threshold 0.04 A All
3.6
Group Power System Data 1; Group Threshold BI
Group Power System Data 1; Group Threshold BI
No. Settings Value Group
0220 Threshold for Binary Input 1 Threshold for Binary Input: 88V All 0221 Threshold for Binary Input 2 Threshold for Binary Input: 88V All 0222 Threshold for Binary Input 3 Threshold for Binary Input: 88V All 0223 Threshold for Binary Input 4 Threshold for Binary Input: 88V All 0224 Threshold for Binary Input 5 Threshold for Binary Input: 88V All 0225 Threshold for Binary Input 6 Threshold for Binary Input: 88V All 0226 Threshold for Binary Input 7 Threshold for Binary Input: 88V All
Page 5 of 11
4
Settings groups
4.1
Group Power System Data 2; Group General
Group Power System Data 2; Group General
No. Settings Value Group
1101 Measurem:FullScaleVoltage(Equipm.rating) 33.00 kV A 1102 Measurem:FullScaleCurrent(Equipm.rating) 400 A A 1108 P,Q operational measured values sign not reversed A
4.2
Group 50/51 Phase/Ground Overcurrent; Group General
Group 50/51 Phase/Ground Overcurrent; Group General
No. Settings Value Group
1201 50, 51 Phase Time Overcurrent ON A
1213A Manual Close Mode 50-2 instantaneously A
1215A 50 Drop-Out Time Delay 0.00 sec A
1301 50N, 51N Ground Time Overcurrent ON A
1313A Manual Close Mode 50N-2 instantaneously A
1315A 50N Drop-Out Time Delay 0.00 sec A
4.3
Group 50/51 Phase/Ground Overcurrent; Group 50
Group 50/51 Phase/Ground Overcurrent; Group 50
No. Settings Value Group
1219A 50-3 measurement of Fundamental component A
1216A 50-3 active Always A
1217 50-3 Pickup oo A A
1218 50-3 Time Delay 0.00 sec A
1220A 50-2 measurement of Fundamental component A
1214A 50-2 active Always A
1202 50-2 Pickup oo A A
1203 50-2 Time Delay 0.00 sec A
1221A 50-1 measurement of Fundamental component A
1204 50-1 Pickup oo A A
Page 6 of 11
Group 50/51 Phase/Ground Overcurrent; Group 50(2)
No. Settings Value Group
1205 50-1 Time Delay 0.50 sec A
4.4
Group 50/51 Phase/Ground Overcurrent; Group 51
Group 50/51 Phase/Ground Overcurrent; Group 51
No. Settings Value Group
1222A 51 measurement of Fundamental component A
1207 51 Pickup 1.00 A A
1208 51 Time Dial 0.49 sec A
1210 Drop-out characteristic Disk Emulation A
1211 IEC Curve Normal Inverse A
4.5
Group 50/51 Phase/Ground Overcurrent; Group 50N
Group 50/51 Phase/Ground Overcurrent; Group 50N
No. Settings Value Group
1319A 50N-3 measurement of Fundamental component A
1317 50N-3 Pickup oo A A
1318 50N-3 Time Delay 0.05 sec A
1320A 50N-2 measurement of Fundamental component A
1302 50N-2 Pickup oo A A
1303 50N-2 Time Delay 0.10 sec A
1321A 50N-1 measurement of Fundamental component A
1304 50N-1 Pickup oo A A
1305 50N-1 Time Delay 0.50 sec A
1314A 50N-2 active Always A
1316A 50N-3 active Always A
Page 7 of 11
4.6
Group 50/51 Phase/Ground Overcurrent; Group 51N
Group 50/51 Phase/Ground Overcurrent; Group 51N
No. Settings Value Group
1322A 51N measurement of Fundamental component A
1307 51N Pickup 0.20 A A
1308 51N Time Dial 0.48 sec A
1310 Drop-Out Characteristic Disk Emulation A
1311 IEC Curve Normal Inverse A
4.7
Group 67 Directional Phase/Ground Overcurrent; Group General
Group 67 Directional Phase/Ground Overcurrent; Group General
No. Settings Value Group
1501 67, 67-TOC Phase Time Overcurrent ON A
1513A Manual Close Mode 67-2 instantaneously A
1516 Phase Direction Forward A
1518A 67 Drop-Out Time Delay 0.00 sec A
1519A Rotation Angle of Reference Voltage 45 ° A
1601 67N, 67N-TOC Ground Time Overcurrent ON A
1613A Manual Close Mode 67N-2 instantaneously A
1616 Ground Direction Forward A
1617 Ground Polarization with VN and IN A
1618A 67N Drop-Out Time Delay 0.00 sec A
1619A Rotation Angle of Reference Voltage -45 ° A
4.8
Group 67 Directional Phase/Ground Overcurrent; Group 67
Group 67 Directional Phase/Ground Overcurrent; Group 67
No. Settings Value Group
1502 67-2 Pickup oo A A
1503 67-2 Time Delay 0.10 sec A
1520A 67-2 measurement of Fundamental component A
1504 67-1 Pickup oo A A
1505 67-1Time Delay 0.50 sec A
1521A 67-1 measurement of Fundamental component A
1514A 67-2 active always A
Page 8 of 11
4.9
Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC
Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC
No. Settings Value Group
1507 67-TOC Pickup 0.50 A A
1508 67-TOC Time Dial 0.05 sec A
1522A 67-TOC measurement of Fundamental component A 1510 Drop-Out Characteristic Disk Emulation A
1511 IEC Curve Normal Inverse A
4.10
Group 67 Directional Phase/Ground Overcurrent; Group 67N
Group 67 Directional Phase/Ground Overcurrent; Group 67N
No. Settings Value Group
1602 67N-2 Pickup oo A A
1603 67N-2 Time Delay 0.10 sec A
1620A 67N-2 measurement of Fundamental component A
1604 67N-1 Pickup oo A A
1605 67N-1 Time Delay 0.50 sec A
1621A 67N-1 measurement of Fundamental component A
1614A 67N-2 active always A
4.11
Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC
Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC
No. Settings Value Group
1607 67N-TOC Pickup 0.20 A A
1608 67N-TOC Time Dial 0.05 sec A
1622A 67N-TOC measurement of Fundamental component A
1610 Drop-Out Characteristic Disk Emulation A
1611 IEC Curve Normal Inverse A
Page 9 of 11
4.12
Group Measurement Supervision; Group General
Group Measurement Supervision; Group General
No. Settings Value Group
8101 Measurement Supervision ON A
5301 Fuse Fail Monitor OFF A
5310 Block protection by FFM YES A 5201 VT broken wire supervision OFF A
4.13
Group Measurement Supervision; Group MeasSupervision
Group Measurement Supervision; Group MeasSupervision
No. Settings Value Group
8102 Voltage Threshold for Balance Monitoring 50 V A 8103 Balance Factor for Voltage Monitor 0.75 A 8104 Current Threshold for Balance Monitoring 0.50 A A 8105 Balance Factor for Current Monitor 0.50 A
4.14
Group Measurement Supervision; Group Fuse Fail Mon.
Group Measurement Supervision; Group Fuse Fail Mon.
No. Settings Value Group
5302 Zero Sequence Voltage 30 V A 5303 Residual Current 0.10 A A 5307 I> Pickup for block FFM 1.00 A A
Page 10 of 11
4.15
Group Measurement Supervision; Group VT broken wire
Group Measurement Supervision; Group VT broken wire
No. Settings Value Group
5202 Threshold voltage sum 8.0 V A
5203 Maximum phase to phase voltage 16.0 V A 5204 Minimum phase to phase voltage 16.0 V A 5205 Symmetry phase to phase voltages 16.0 V A
5206 Minimum line current 0.04 A A
5208 Alarm delay time 1.25 sec A
4.16
Group Energy; Group Measurement
Group Energy; Group Measurement
No. Settings Value Group 8315 Meter resolution Standard A