Setting values in: Secondary value description

P R I N T - C O N T E N T S

2.1 Group Device, General Settings; Group General

...4 3 Power System Data 1

...4 3.1 Group Power System Data 1; Group Power System

...4 3.2 Group Power System Data 1; Group Prot.Op. quant.

...4 3.3 Group Power System Data 1; Group CT's

...5 3.4 Group Power System Data 1; Group VT's

...5 3.5 Group Power System Data 1; Group Breaker

...5 3.6 Group Power System Data 1; Group Threshold BI

...6 4 Settings groups

...6 4.1 Group Power System Data 2; Group General

...6 4.2 Group 50/51 Phase/Ground Overcurrent; Group General

...6 4.3 Group 50/51 Phase/Ground Overcurrent; Group 50

...7 4.4 Group 50/51 Phase/Ground Overcurrent; Group 51

...7 4.5 Group 50/51 Phase/Ground Overcurrent; Group 50N

...8 4.6 Group 50/51 Phase/Ground Overcurrent; Group 51N

...8 4.7 Group 67 Directional Phase/Ground Overcurrent; Group General

...8 4.8 Group 67 Directional Phase/Ground Overcurrent; Group 67

...9 4.9 Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC

...9 4.10 Group 67 Directional Phase/Ground Overcurrent; Group 67N

...9 4.11 Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC

...10 4.12 Group Measurement Supervision; Group General

...10 4.13 Group Measurement Supervision; Group MeasSupervision

...10 4.14 Group Measurement Supervision; Group Fuse Fail Mon.

...11 4.15 Group Measurement Supervision; Group VT broken wire

...11 4.16 Group Energy; Group Measurement

Page 1 of 11

1

Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled 0104 Oscillographic Fault Records Enabled

0112 50/51 Time Overcurrent Curve IEC

0113 50N/51N Time Overcurrent Curve IEC

0115 67, 67-TOC Time Overcurrent Curve IEC

0116 67N, 67N-TOC Time Overcurrent Curve IEC

0117 Cold Load Pickup Disabled

0122 2nd Harmonic Inrush Restraint Disabled

0131 (sensitive) Ground fault Disabled

0130 (sens.) Ground fault dir. characteristic cos phi / sin phi measurement (standard) 0140 46 Negative Sequence Protection Disabled

0142 49 Thermal Overload Protection Disabled 0150 27, 59 Under/Overvoltage Protection Disabled 0154 81 Over/Underfrequency Protection Disabled 0170 50BF Breaker Failure Protection Disabled 0172 52 Breaker Wear Monitoring Disabled 0182 74TC Trip Circuit Supervision Disabled 0192 Capacitive voltage measurement NO

Flexible Function

Page 2 of 11

2

General Device Settings

2.1

Group Device, General Settings; Group General

Group Device, General Settings; Group General

No. Settings Value Group

0610 Fault Display on LED / LCD Display Targets on every Pickup All

0611 Spontaneous display of flt.annunciations NO All

0640 Start image Default Display image 1 All

Page 3 of 11

3

Power System Data 1

3.1

Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System

No. Settings Value Group

0214 Rated Frequency 50 Hz All

0209 Phase Sequence A B C All

0201 CT Starpoint towards Line All

0280 Holmgreen-conn. (for fast sum-i-monit.) NO All

0251A CT Connection Ia, Ib, Ic, (IGnd) All

0213 VT Connection, three-phase Van, Vbn, Vcn All

0235A Storage of th. Replicas w/o Power Supply YES All

3.2

Group Power System Data 1; Group Prot.Op. quant.

Group Power System Data 1; Group Prot.Op. quant.

No. Settings Value Group

0250A 50, 51 Time Overcurrent with 2ph. prot. OFF All 0613A Ground Overcurrent protection with Ignd (measured) All

3.3

Group Power System Data 1; Group CT's

Group Power System Data 1; Group CT's

No. Settings Value Group

0204 CT Rated Primary Current 400 A All 0205 CT Rated Secondary Current 1A All 0217 Ignd-CT rated primary current 400 A All 0218 Ignd-CT rated secondary current 1A All

Page 4 of 11

3.4

Group Power System Data 1; Group VT's

Group Power System Data 1; Group VT's

No. Settings Value Group

0202 Rated Primary Voltage 33.00 kV All

0203 Rated Secondary Voltage (L-L) 110 V All

0206A Matching ratio Phase-VT To Open-Delta-VT 1.73 All

3.5

Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker

No. Settings Value Group

0210A Minimum TRIP Command Duration 0.15 sec All 0211A Maximum Close Command Duration 1.00 sec All 0212 Closed Breaker Min. Current Threshold 0.04 A All

3.6

Group Power System Data 1; Group Threshold BI

Group Power System Data 1; Group Threshold BI

No. Settings Value Group

0220 Threshold for Binary Input 1 Threshold for Binary Input: 88V All 0221 Threshold for Binary Input 2 Threshold for Binary Input: 88V All 0222 Threshold for Binary Input 3 Threshold for Binary Input: 88V All 0223 Threshold for Binary Input 4 Threshold for Binary Input: 88V All 0224 Threshold for Binary Input 5 Threshold for Binary Input: 88V All 0225 Threshold for Binary Input 6 Threshold for Binary Input: 88V All 0226 Threshold for Binary Input 7 Threshold for Binary Input: 88V All

Page 5 of 11

4

Settings groups

4.1

Group Power System Data 2; Group General

Group Power System Data 2; Group General

No. Settings Value Group

1101 Measurem:FullScaleVoltage(Equipm.rating) 33.00 kV A 1102 Measurem:FullScaleCurrent(Equipm.rating) 400 A A 1108 P,Q operational measured values sign not reversed A

4.2

Group 50/51 Phase/Ground Overcurrent; Group General

Group 50/51 Phase/Ground Overcurrent; Group General

No. Settings Value Group

1201 50, 51 Phase Time Overcurrent ON A

1213A Manual Close Mode 50-2 instantaneously A

1215A 50 Drop-Out Time Delay 0.00 sec A

1301 50N, 51N Ground Time Overcurrent ON A

1313A Manual Close Mode 50N-2 instantaneously A

1315A 50N Drop-Out Time Delay 0.00 sec A

4.3

Group 50/51 Phase/Ground Overcurrent; Group 50

Group 50/51 Phase/Ground Overcurrent; Group 50

No. Settings Value Group

1219A 50-3 measurement of Fundamental component A

1216A 50-3 active Always A

1217 50-3 Pickup oo A A

1218 50-3 Time Delay 0.00 sec A

1220A 50-2 measurement of Fundamental component A

1214A 50-2 active Always A

1202 50-2 Pickup oo A A

1203 50-2 Time Delay 0.00 sec A

1221A 50-1 measurement of Fundamental component A

1204 50-1 Pickup oo A A

Page 6 of 11

Group 50/51 Phase/Ground Overcurrent; Group 50(2)

No. Settings Value Group

1205 50-1 Time Delay 0.50 sec A

4.4

Group 50/51 Phase/Ground Overcurrent; Group 51

Group 50/51 Phase/Ground Overcurrent; Group 51

No. Settings Value Group

1222A 51 measurement of Fundamental component A

1207 51 Pickup 1.00 A A

1208 51 Time Dial 0.49 sec A

1210 Drop-out characteristic Disk Emulation A

1211 IEC Curve Normal Inverse A

4.5

Group 50/51 Phase/Ground Overcurrent; Group 50N

Group 50/51 Phase/Ground Overcurrent; Group 50N

No. Settings Value Group

1319A 50N-3 measurement of Fundamental component A

1317 50N-3 Pickup oo A A

1318 50N-3 Time Delay 0.05 sec A

1320A 50N-2 measurement of Fundamental component A

1302 50N-2 Pickup oo A A

1303 50N-2 Time Delay 0.10 sec A

1321A 50N-1 measurement of Fundamental component A

1304 50N-1 Pickup oo A A

1305 50N-1 Time Delay 0.50 sec A

1314A 50N-2 active Always A

1316A 50N-3 active Always A

Page 7 of 11

4.6

Group 50/51 Phase/Ground Overcurrent; Group 51N

Group 50/51 Phase/Ground Overcurrent; Group 51N

No. Settings Value Group

1322A 51N measurement of Fundamental component A

1307 51N Pickup 0.20 A A

1308 51N Time Dial 0.48 sec A

1310 Drop-Out Characteristic Disk Emulation A

1311 IEC Curve Normal Inverse A

4.7

Group 67 Directional Phase/Ground Overcurrent; Group General

Group 67 Directional Phase/Ground Overcurrent; Group General

No. Settings Value Group

1501 67, 67-TOC Phase Time Overcurrent ON A

1513A Manual Close Mode 67-2 instantaneously A

1516 Phase Direction Forward A

1518A 67 Drop-Out Time Delay 0.00 sec A

1519A Rotation Angle of Reference Voltage 45 ° A

1601 67N, 67N-TOC Ground Time Overcurrent ON A

1613A Manual Close Mode 67N-2 instantaneously A

1616 Ground Direction Forward A

1617 Ground Polarization with VN and IN A

1618A 67N Drop-Out Time Delay 0.00 sec A

1619A Rotation Angle of Reference Voltage -45 ° A

4.8

Group 67 Directional Phase/Ground Overcurrent; Group 67

Group 67 Directional Phase/Ground Overcurrent; Group 67

No. Settings Value Group

1502 67-2 Pickup oo A A

1503 67-2 Time Delay 0.10 sec A

1520A 67-2 measurement of Fundamental component A

1504 67-1 Pickup oo A A

1505 67-1Time Delay 0.50 sec A

1521A 67-1 measurement of Fundamental component A

1514A 67-2 active always A

Page 8 of 11

4.9

Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC

Group 67 Directional Phase/Ground Overcurrent; Group 67-TOC

No. Settings Value Group

1507 67-TOC Pickup 0.50 A A

1508 67-TOC Time Dial 0.05 sec A

1522A 67-TOC measurement of Fundamental component A 1510 Drop-Out Characteristic Disk Emulation A

1511 IEC Curve Normal Inverse A

4.10

Group 67 Directional Phase/Ground Overcurrent; Group 67N

Group 67 Directional Phase/Ground Overcurrent; Group 67N

No. Settings Value Group

1602 67N-2 Pickup oo A A

1603 67N-2 Time Delay 0.10 sec A

1620A 67N-2 measurement of Fundamental component A

1604 67N-1 Pickup oo A A

1605 67N-1 Time Delay 0.50 sec A

1621A 67N-1 measurement of Fundamental component A

1614A 67N-2 active always A

4.11

Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC

Group 67 Directional Phase/Ground Overcurrent; Group 67N-TOC

No. Settings Value Group

1607 67N-TOC Pickup 0.20 A A

1608 67N-TOC Time Dial 0.05 sec A

1622A 67N-TOC measurement of Fundamental component A

1610 Drop-Out Characteristic Disk Emulation A

1611 IEC Curve Normal Inverse A

Page 9 of 11

4.12

Group Measurement Supervision; Group General

Group Measurement Supervision; Group General

No. Settings Value Group

8101 Measurement Supervision ON A

5301 Fuse Fail Monitor OFF A

5310 Block protection by FFM YES A 5201 VT broken wire supervision OFF A

4.13

Group Measurement Supervision; Group MeasSupervision

Group Measurement Supervision; Group MeasSupervision

No. Settings Value Group

8102 Voltage Threshold for Balance Monitoring 50 V A 8103 Balance Factor for Voltage Monitor 0.75 A 8104 Current Threshold for Balance Monitoring 0.50 A A 8105 Balance Factor for Current Monitor 0.50 A

4.14

Group Measurement Supervision; Group Fuse Fail Mon.

Group Measurement Supervision; Group Fuse Fail Mon.

No. Settings Value Group

5302 Zero Sequence Voltage 30 V A 5303 Residual Current 0.10 A A 5307 I> Pickup for block FFM 1.00 A A

Page 10 of 11

4.15

Group Measurement Supervision; Group VT broken wire

Group Measurement Supervision; Group VT broken wire

No. Settings Value Group

5202 Threshold voltage sum 8.0 V A

5203 Maximum phase to phase voltage 16.0 V A 5204 Minimum phase to phase voltage 16.0 V A 5205 Symmetry phase to phase voltages 16.0 V A

5206 Minimum line current 0.04 A A

5208 Alarm delay time 1.25 sec A

4.16

Group Energy; Group Measurement

Group Energy; Group Measurement

No. Settings Value Group 8315 Meter resolution Standard A

Page 11 of 11