TORBERN1TA Y METATORBERN1TA
2.4 YACIMIENTOS.'()E MINERALES VE. URANIO
Demand in the network is usually expected to grow, but there are also areas where no electric load growth or even negative load growth is expected. As for generation, power generation growth normally means new generation connection in a lump sum rather than the growth of the existing generation. Hence, nodal existing generation growth rates are assumed to be zero.
These different load growth forecast throughout the whole network will lead to differ
ent types of circuit loading growth patterns, namely positive, negative and zero circuit loading growth. These growth patterns are results of different circuit loading growth rates, rℓ, and they are treated differently in LRIC pricing to give adequate economical signals for network users to act upon.
In addition to circuit loading growth patterns, the LRIC prices for demand and gener
ation are also dependent on whether the circuit is demand- or generation-dominated.
Demand will be charged if the supporting circuits are demand-dominated and will be rewarded otherwise. This also applies to generation where generation will be charged when the supporting circuits are generation-dominated.
A circuit can be either demand- or generation-dominated seen by customers at differ
ent locations. If a load withdrawal at a node results in a flow increase at a circuit, then the circuit is considered as demand-dominated seen by this load. However, this same circuit can be generation-dominated if a load injection at another node causes power flow decrease.
Figure 4.6. 2-bus test system
For instance, if the power is flowing from Bus 2 to Bus 1 in Figure 4.6, a load incre
ment at Bus 1 will cause the power flow at the circuit to increase. Hence, for the pricing purpose, the circuit is demand-dominated seen by the customers – both load and gen
eration at Bus 1. However, a load injection at Bus 2 will result in a counter flow at the circuit. Therefore, the circuit is generation-dominated seen by both the load and
Chapter 4 LRIC: Growth Rates
generation at Bus 1. Therefore, load at Bus 1 and generation at Bus 2 will be charged for using the line whilst load at Bus 2 and generation at Bus 1 will be rewarded.
4.3.1 Positive Circuit Loading Growth Pattern
A circuit with positive circuit loading growth means that the circuit loading level is increasing in the long term. These growth pattern is influence by the dynamic element DB and its growth rate rB. There are two possibilities where a circuit could have a
The positive growth patterns of these two positive and negative rB cases are shown in Figure 4.7. From the graph, it is shown that the loading level of the positive rB case grows exponentially, while the loading level of the negative rB grows logarithmically.
Chapter 4 LRIC: Growth Rates
For instance, in the Figure 4.6 example, if power flows from Bus 2 to Bus 1 and load at Bus 1 has a positive nodal growth rate, the positive exponential circuit loading growth pattern can be obtained. On the other hand, if power flows from Bus 1 to Bus 2 (i.e. the circuit is generation-dominated seen by customers at Bus 1) and the load at Bus 1 has a negative growth rate, the positive logarithmic circuit loading growth pattern can be achieved.
For the negative rB case the loading level will never reach the maximum allowed load
ing level and hence no reinforcement cost will be seen. Therefore, only the positive rB case will be considered for network pricing, and there will not be any investment cost for the negative rB case.
4.3.2 Negative Circuit Loading Growth Pattern
Negative circuit loading growth indicates that the loading level of the circuit is de
creasing. Similarly, there are two possibilities where a circuit could have a negative circuit loading growth:
• When DB is positive and rB is negative
• When DB is negative and rB is positive
The negative growth patterns of these two positive and negative rB cases are shown in Figure 4.8. From the graph, it is shown that the loading level of the negative rB case decreases exponentially. This also means that the loading level will decrease slower with time and will never reach zero. Hence, if a circuit loading level is diminishing and the rB is negative, the LRIC price is zero as no reinforcement is required.
On the other hand, for the positive rB case, the size of the loading level decrement grows with time. Therefore, at some point the loading level of the circuit will become zero and the flow on the circuit will ’flip’ to another direction (loading level becomes negative). The DB flow with the positive rℓ will continue grow until the loading level reaches the maximum allowed capacity. Reinforcement is then required.
In the Figure 4.6 example, if power flows from Bus 2 to Bus 1 and load at Bus 1 has a negative growth rate, the exponential negative circuit loading growth pattern is reached. If power flows from Bus 1 to Bus 2 (generation-dominated) and load at Bus 1 has a positive growth rate, then the loading level of the line will diminish until it reaches zero and ’grow’ exponentially at the different direction (load-dominated).
Chapter 4 LRIC: Growth Rates
Zero circuit loading growth will occur when demand is not growing or not decreasing, i.e. rB is zero. The loading levels of the corresponding circuits remain the same. This might happen at some remote areas where the domestic customers merely change their usage of electricity.
For zero circuit loading growth case, as there is no change in the loading level hence there is no need for investment. Therefore, there is no reinforcement cost for circuits