The input can be delinearized by configuring an intermediate point on the input/output curve of this input: For range 0 V 100%
Note: For [Interm. point X], 0% corresponds to [Min value] and 100% to [Max value]
For range -100% V 100% Reference 100% 0% [Min value] (0%) [Interm. point X] [Max value] (100%) Current or voltage input [Interm. point Y] 20 mA or 10 V Reference 100% 0% [Min value] (- 100%) [Interm. point X] [Max value] (100%) Current or voltage input [Interm. point Y] - [Interm. point Y] - 100% - [Interm. point X] 0% 20 mA or 10 V
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code Name/Description Adjustment range Factory setting
AI1 -
b [AI1 CONFIGURATION]
AI1A
M [AI1 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI1 in order to check, for example, for compatibility problems.
AI1t
M [AI1 Type]
[Voltage] (10U)10U n10U
v
[Voltage]
(10U): Positive voltage input (negative values are interpreted as zero: the input is unidirectional).v
[Voltage +/-]
(n10U): Positive and negative voltage input (the input is bidirectional).UIL1
M [AI1 min value]
0 to 10.0 V 0 VUIH1
M [AI1 max value]
0 to 10.0 V 10.0 VAI1F
M [AI1 filter]
0 to 10.00 s 0 sInterference filtering.
AI1E
M [AI1 Interm. point X]
0 to 100% 0%Input delinearization point coordinate. • 0% corresponds to [AI1 min value] (UIL1). • 100% corresponds to [AI1 max value] (UIH1).
AI1S
M [AI1 Interm. point Y]
0 to 100% 0%108
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code Name/Description Adjustment range Factory setting
AI2-
b [AI2 CONFIGURATION]
AI2AM [AI2 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI2 in order to check, for example, for compatibility problems.
AI2t
M [AI2 Type]
[Current] (0 A)10U 0A
v
[Voltage]
(10U): Voltage inputv
[Current]
(0 A): Current inputCrL2
M [AI2 min value]
0 to 20.0 mA 0 mAThe parameter can be accessed if [AI2 Type] (AI2t) = [Current] (0 A)
UIL2
M [AI2 min value]
0 to 10.0 V 0 VThe parameter can be accessed if [AI2 Type] (AI2t) = [Voltage] (10U)
CrH2
M [AI2 max. value]
0 to 20.0 mA 20.0 mAThe parameter can be accessed if [AI2 Type] (AI2t) = [Current] (0 A)
UIH2
M [AI2 max. value]
0 to 10.0 V 10.0 VThe parameter can be accessed if [AI2 Type] (AI2t) = [Voltage] (10U)
AI2F
M [AI2 filter]
0 to 10.00 s 0 sInterference filtering.
AI2L
M [AI2 range]
[0 - 100%] (POS)POS nEG
v
[0 - 100%]
(POS): Unidirectional inputv
[+/- 100%]
(nEG): Bidirectional input Example: On a 0/10 V input- 0 V corresponds to reference -100% - 5 V corresponds to reference 0% - 10 V corresponds to reference + 100%
AI2E
M [AI2 Interm. point X]
0 to 100% 0%Input delinearization point coordinate.
• 0% corresponds to [Min value] if the range is 0 V 100%.
• 0% corresponds to if the range is -100% V + 100%. • 100% corresponds to [Max value].
AI2S
M [AI2 Interm. point Y]
0 to 100% 0%Output delinearization point coordinate (frequency reference).
[Max value] + [Min value]
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code Name/Description Adjustment range Factory setting
AI3 -
b [AI3 CONFIGURATION]
Can be accessed if a VW3A3202 option card has been inserted
AI3A
M [AI3 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI3 in order to check, for example, for compatibility problems.
AI3t
M [AI3 Type]
[Current] (0 A)0A
Read-only parameter, cannot be configured.
v
[Current]
(0 A): Current inputCrL3
M [AI3 min. value]
0 to 20.0 mA 0 mACrH3
M [AI3 max. value]
0 to 20.0 mA 20.0 mAAI3F
M [AI3 filter]
0 to 10.00 s 0 sInterference filtering.
AI3L
M [AI3 range]
[0 - 100%] (POS)POS nEG
v
[0 - 100%]
(POS): Unidirectional inputv
[+/- 100%]
(nEG): Bidirectional input Example: On a 4 - 20 mA input- 4 mA corresponds to reference -100% - 12 mA corresponds to reference 0% - 20 mA corresponds to reference + 100%
Since AI3 is, in physical terms, a bidirectional input, the [+/- 100%] (nEG) configuration must only be used if the signal applied is unidirectional. A bidirectional signal is not compatible with a bidirectional
configuration.
AI3E
M [AI3 Interm. point X]
0 to 100% 0%Input delinearization point coordinate.
• 0% corresponds to [Min value] (CrL3) if the range is 0 V 100%.
• 0% corresponds to if the range is -100% V +100%.
• 100% corresponds to [AI3 max. value] (CrH3).
AI3S
M [AI3 Interm. point Y]
0 to 100% 0%Output delinearization point coordinate (frequency reference).
[AI3 max. value] (CrH3) - [AI3 min. value] (CrL3)
110
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code Name/Description Adjustment range Factory setting
AI4-
b [AI4 CONFIGURATION]
Can be accessed if a VW3A3202 option card has been inserted
AI4A
M [AI4 assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with input AI4 in order to check, for example, for compatibility problems.
AI4t
M [AI4 Type]
[Voltage] (10U)10U 0A
v
[Voltage]
(10U): Voltage inputv
[Current]
(0 A): Current inputCrL4
M [AI4 min value]
0 to 20.0 mA 0 mAThe parameter can be accessed if [AI4 Type] (AI4t) = [Current] (0 A)
UIL4
M [AI4 min value]
0 to 10.0 V 0 VThe parameter can be accessed if [AI4 Type] (AI4t) = [Voltage] (10U)
CrH4
M [AI4 max value]
0 to 20.0 mA 20.0 mAThe parameter can be accessed if [AI4 Type] (AI4t) = [Current] (0 A)
UIH4
M [AI4 max value]
0 to 10.0 V 10.0 VThe parameter can be accessed if [AI4 Type] (AI4t) = [Voltage] (10U)
AI4F
M [AI4 filter]
0 to 10.00 s 0 sInterference filtering.
AI4L
M [AI4 range]
[0 - 100%] (POS)POS nEG
v
[0 - 100%]
(POS): Unidirectional inputv
[+/- 100%]
(nEG): Bidirectional input Example: On a 0/10 V input- 0 V corresponds to reference -100% - 5 V corresponds to reference 0% - 10 V corresponds to reference + 100%
AI4E
M [AI4 Interm.point X]
0 to 100% 0%Input delinearization point coordinate.
• 0% corresponds to [Min value] if the range is 0 V 100%.
• 0% corresponds to if the range is -100% V + 100%. • 100% corresponds to [Max value].
AI4S
M [AI4 Interm.point Y]
0 to 100% 0%Output delinearization point coordinate (frequency reference).
[Max value] + [Min value]
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code Name/Description Adjustment range Factory setting
AU1-
b [VIRTUAL AI1]
AIC1
M [AI net. channel]
[No] (nO)nO Mdb CAn nEt APP Virtual input.
This parameter can also be accessed in the [PID REGULATOR] (PId-) submenu page 193.
[No]
(nO): Not assigned (in this case, the virtual input does not appear in the analog input assignment parameters for the functions)v
[Modbus]
(Mdb): Integrated Modbusv
[CANopen]
(CAn): Integrated CANopenv
[Com. card]
(nEt): Communication card (if inserted)v
[C.Insid. card]
(APP): Controller Inside card (if inserted)Scale: the value 8192 transmitted by this input is equivalent to 10 V on a 10 V input.
WARNING
UNINTENDED EQUIPMENT OPERATION
If the equipment switches to forced local mode (see page 260), the virtual input remains fixed at the last value transmitted.
Do not use the virtual input and forced local mode in the same configuration.
112
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
Code Name/Description Adjustment range Factory setting
PLI-
b [RP CONFIGURATION]
Can be accessed if a VW3A3202 option card has been inserted
PIA
M [RP assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with the Pulse In input in order to check, for example, for compatibility problems.
PIL
M [RP min value]
- 30.00 to 30.00 kHz 0Frequency corresponding to the minimum speed
PFr
M [RP max value]
0 to 30.00 kHz 30.00 kHzFrequency corresponding to the maximum speed
PFI