The number of poles on the motor must be a whole multiple of the number of poles on the resolver. For example, a 6-pole

resolver will not operate with an 8-pole motor.

To obtain the best resolution, we recommend selecting a resolver with the same number of poles as the motor.

Procedure for measuring the phase-shift angle between the motor and the encoder

Preliminary remarks:

Select the [Angle setting type] (ASt) measuring mode according to the type of machine being driven:

• [Angle setting type] (ASt) = [W/o load] (nLd): Measurement with motion,if the rotation of the motor is free (no load, brake released) and safe. During measurement current flows through the motor, which may cause it to rotate one full revolution.

• [Angle setting type] (ASt) = [With load] (brC): Measurement without motion, motor with or without load, brake engaged or released. This mode is recommended for a lift, for example. You must adhere to the following instructions:

- The motor rotor must not move during measurement, otherwise the result will be incorrect.

- In some cases, the measurement current can cause tripping on an [Overcurrent](OCF) fault; if so, use [W/o load] (nLd) mode. This occurs when using low-inductance motors, high-speed motors, or motors in which the rated voltage is well below the supply voltage of the drive.

- In some cases, the measurement can cause tripping on an [Angle error](ASF) fault. This occurs if the motor rotor has moved during measurement (only detected in closed-loop mode), a motor phase is disconnected or if the motor inductance is too high, thus limiting the measurement current (in this case, use [W/o load] (nLd) mode).

• [Angle setting type] (ASt) = [Optimised] (brCO): measurement without motion, possible with or without load, brake engaged or released. Optimization of the angle detection time starting from the second detection request, even after a power off of the product. 1. First, follow the "Encoder check procedure" on page 74.

2. Set [Motor control type] (Ctt) = [Sync.CL](FSY).

3. If you have selected [Angle setting type] (ASt) = [W/o load] (nLd): measurement without motion, check that the motor is running safely and can turn freely without resistive or driving torque. If these conditions are not met, the resulting measurement will be

inaccurate.

4. Set [Angle auto-test] (ASA) = [Yes](YES). The measurement is performed and [Angle auto-test] (ASA) changes to[Done](dOnE).

The [Angle offset value] (ASU) parameter changes from [No](nO) to a numerical value proportional to the electrical angle measured (8191 = 360°).

5. If required, configure automatic measurements using [Angle setting activ.] (AtA). If [Angle setting type] (ASt) = [W/o load] (nLd), ensure that the safety conditions outlined earlier are met at all times.

If using a relative encoder (incremental or SinCos), it is recommended that you set [Angle setting activ.] (AtA) = [Power On] (POn) or

[Run order] (AUtO).

6. If an [Angle error](ASF) fault occurs, [Angle auto-test] (ASA) returns to [No](nO).

- Check that the parameters and instructions relating to this procedure have been carried out correctly and perform the measurement again.

Comments

The phase-shift angle must be re-measured each time: • The motor is changed

• The encoder is changed

• The coupling between the motor and encoder is removed • The [Output Ph rotation](PHr) parameter is modified • The [Coder rotation inv.](EnRI) parameter is modified

If a relative encoder (incremental or SinCos) is used, measurement must be repeated each time the motor is turned off/on. It is therefore recommended that you set [Angle setting activ.] (AtA) = [Power On] (POn) or [Run order] (AUtO).

WARNING

UNINTENDED EQUIPMENT OPERATION

Check that the rotation of the motor will not cause any dangerous movements.

84

[1.4 MOTOR CONTROL]

(drC-)

Code Name/Description Adjustment range

ASA-

b [ANGLE TEST SETTING]

Can only be accessed if [Motor control type] (Ctt) page 70 = [Sync.CL] (FSY)

ASt

M [Angle setting type]

[With load] (brC)

brC nLd brCO

Mode for measuring the phase-shift angle between the motor and the encoder.

v

[With load]

(brC): Measurement without motion, possible with or without load, brake engaged or released.

v

[W/o load]

(nLd): Measurement with motion, only for free motors (brake released), without load.

v

[Optimised]

(brCO): Measurement without motion, possible with or without load, brake engaged or released. Optimization of the angle detection time starting from the second detection request, even after a power off of the product.

Note: If [Angle setting type] (ASt) = [W/o load] (nLd), the motor may rotate one full revolution during measurement.

ASA

M [Angle auto-test]

[No] (nO)

nO YES dOnE

Measurement of the phase-shift angle between the motor and the encoder.

v

[No]

(nO): Measurement not performed or has failed, or [Output Ph rotation](PHr) has been modified, or

[Coder rotation inv.](EnRI) parameter has been modified.

v

[Yes]

(YES): Measurement is performed as soon as possible, then the parameter automatically changes to

[Done] (dOnE).

v

[Done]

(dOnE): Use of the value given the last time the measurement was performed.

Important:

• It is essential that all the motor parameters are configured correctly before performing measurements: - [Nominal I sync] (nCrS), [Current Limitation] (CLI), [Nom motor spdsync] (nSPS), [Pole pairs.] (PPnS),

[Syn. EMF constant] (PHS), [Autotune L d-axis] (LdS), [IAutotune L q-axis] (LqS), [Cust. stator R syn]

(rSAS).

• Measurement is only performed if no stop command has been activated. If a "freewheel stop" or "fast stop" function has been assigned to a logic input, this input must be set to 1 (active at 0).

• Measurement takes priority over any run commands, which will be taken into account after the measurement sequence.

• If measurement fails, the drive displays [No] (nO) and changes to [Angle Error] (ASF) fault mode. • Measurement may take several seconds. Do not interrupt the process. Wait for the display to change to

"[Done] (dOnE)" or "[No] (nO)".

Note: If a "line contactor" or "output contactor" function has been configured, the contactor closes

during measurement.

ASL

M [Angle auto test]

[No] (nO)

nO LI1 - - -

Measurement of the phase-shift angle between the motor and the encoder by means of a logic input or command bit.

v

[No]

(nO): Not assigned

v

[LI1]

(LI1)

: :

v

[...]

(...): See the assignment conditions on page 139.

Measurement is performed when the assigned bit or input changes to 1.

Note: If a "line contactor" or "output contactor" function has been configured, the contactor closes

[1.4 MOTOR CONTROL]

(drC-)

(1) Powering down causes a loss of measurement data in the following cases: • With a VW3 A3 401 to 407 card:

- Every time the power section is turned off, even if the drive control section has a separate power supply (for example, if the "line contactor" function has been configured).

• With a VW3 A3 409 card and a SinCos encoder:

- Every time the power section is turned off, if the drive control section does not have a separate power supply. - Only when the drive control section is turned off (if it has a separate power supply via the 0 and P24 terminals). - If the number of poles of the resolver is not a multiple of the number of poles of the motor.

Code Name/Description Adjustment range

ASA-

b [ANGLE TEST SETTING] (continued)

AtA

M [Angle setting activ.]

[No] (nO)

nO POn AUtO

Activation of automatic measurement of the phase-shift angle between the motor and encoder when using a relative encoder (incremental or SinCos).

v

[No]

(nO): Function inactive.

v

[Power On]

(POn): Measurement is performed on each power-up (1).

v

[Run order]

(AUtO): Measurement is performed on each run command if necessary, i.e., if parameter [Angle offset value](ASU) is set to [No] (nO).

This option is recommended for use with a VW3 A3 401 to 407 card or with VW3 A3 411 card, when the "line contactor" function has been configured (loss of angle on each stop) (1).

If [Angle setting activ.] (AtA) = [Power On] (POn) or [Run order] (AUtO), it is advisable to set [Angle setting type]

(ASt) = [With load] (brC).

Note: If a "line contactor" or "output contactor" function has been configured, the contactor closes

during measurement.

ASU

M [Angle offset value]

[No] (nO)

nO -

Phase-shift angle between the motor and the encoder.

v

[No]

(nO): Measurement has not been performed or has failed, or [Output Ph rotation](PHr) has been modified, or measurement has been lost due to powering down (1).

v

0 to 8191: Phase-shift angle. 8191 corresponds to 360°.

AStS

M [Angle setting status]

[Not done] (tAb)

tAb PEnd PrOG FAIL dOnE CUS

Information on the phase-shift angle measurement between the motor and the encoder (cannot be modified).

v

[Not done]

(tAb): Phase-shift angle not defined.

v

[Pending]

(PEnd): Measurement requested but not yet performed.

v

[In Progress]

(PrOG): Measurement in progress.

v

[Failed]

(FAIL): Measurement failed.

v

[Done]

(dOnE): Measurement performed successfully.

v

[Customized]

(CUS): The phase-shift angle value has been entered by the user via the display terminal or serial link.

86

[1.4 MOTOR CONTROL]

(drC-)

(1) Parameter can also be accessed in the [1.3 SETTINGS] (SEt-) menu.

Code Name/Description Adjustment range Factory setting

FLI-

b [FLUXING BY LI]

Cannot be accessed if [Motor control type] (Ctt) page 70 = [Sync.CL](FSY).

FLU

T

M [Motor fluxing]

(1) [No] (FnO) FnC FCt FnO

v

[Not cont.]

(FnC): Non-continuous mode

v

[Continuous]

(FCt): Continuous mode. This option is not possible if [Angle setting type](ASt) page 87 is [With load] (brC) or if [Auto DC injection] (AdC) page 158 is [Yes] (YES) or if [Type of stop] (Stt) page 156 is [Freewheel] (nSt).

v

[No]

(FnO): Function inactive. This option is not possible if [Motor control type] (Ctt) page 70 = [SVC I]

(CUC) or[FVC] (FUC).

If [Motor control type] (Ctt) page 70 = [SVC I] (CUC), [FVC] (FUC) or[Sync. mot.] (SYn), the factory setting is replaced by [Not cont.] (FnC).

If [Motor control type] (Ctt) page 70 = [SVC V] (UUC), the factory setting is replaced by [Not cont.] (FnC) at and above 55 kW (75 HP) for ATV71ppppM3X and at and above 90 kW (120 HP) for ATV71ppppN4. In order to obtain rapid high torque on startup, magnetic flux needs to already have been established in the motor.

• In [Continuous] (FCt) mode, the drive automatically builds up flux when it is powered up. • In [Not cont.] (FnC) mode, fluxing occurs when the motor starts up.

The flux current is greater than nCr (configured rated motor current) when the flux is established and is then adjusted to the motor magnetizing current.

If [Motor control type] (Ctt) page 70 = [Sync. mot.] (SYn), the [Motor fluxing](FLU) parameter must be

active ([No] (FnO) is not permitted); this parameter causes rotor angle detection or alignment (according to the configuration of [Angle setting type] (ASt) page 87) and not fluxing.

If [Brake assignment] (bLC) page 175 is not [No] (nO), the [Motor fluxing](FLU) parameter has no effect.

FLI

M [Fluxing assignment]

[No] (nO)

nO LI1 - - -