INFORME TECNICO IT-O&M-2012-008

INFORME TECNICO IT-O&M-2012-008

PARA:

PARA: LILETH LILETH CUBAS CUBAS IBM IBM DEL DEL PERUPERU

ASUNTO:

ASUNTO: INFORME DEL MANTENIMIENTO PREVENTIVO DE 04 UPS LIEBERT NXAINFORME DEL MANTENIMIENTO PREVENTIVO DE 04 UPS LIEBERT NXA de 120KVA -

de 120KVA - SEDE LA MOLINASEDE LA MOLINA

CLIENTE:

CLIENTE: IBM IBM DEL DEL PERUPERU ELABORADO

ELABORADO POR:

POR: JAVIER JAVIER GONZALES GONZALES ESPECIALISTAS ESPECIALISTAS UPSUPS REVISADO

REVISADO POR: POR: EDWARD EDWARD GRANDEZ GRANDEZ BUSTAMANTE BUSTAMANTE SUPERVISOR SUPERVISOR O&MO&M APROBADO

APROBADO POR: POR: GREGORIO GREGORIO CASTRO CASTRO JEFE JEFE O&MO&M

FECHA DE TERMINO DEL INFORME (APROBADO):

FECHA DE TERMINO DEL INFORME (APROBADO): 06-12-1206-12-12

1.

1. DATOS

DATOS DE

DE EQUIPO:

EQUIPO:

Tipo

Tipo

Marca

Marca

Modelo

Modelo

Serie

Serie

Capacidad

Capacidad

UPS

UPS LIEBERT LIEBERT NXA NXA 21012001692081022101200169208102 0002 0002 120KVA120KVA UPS

UPS LIEBERT LIEBERT NXANXA 21012001692081020004 21012001692081020004 120KVA120KVA UPS

UPS LIEBERT LIEBERT NXANXA 21012001692081020003 21012001692081020003 120KVA120KVA UPS

UPS LIEBERT LIEBERT NXANXA 21012001692084070009 21012001692084070009 120KVA120KVA

Ubicación

Ubicación

DATA

DATA CENTER

CENTER

2. ANTECEDENTES:

2. ANTECEDENTES:

Con fecha 24 de noviembre del presente año 2012, se realizó el mantenimiento preventivo Con fecha 24 de noviembre del presente año 2012, se realizó el mantenimiento preventivo programado a 04 equipos UPS

programado a 04 equipos UPS

MARCA:

MARCA:

LiebertLiebert

MODELO:

MODELO:

NxaNxa

CAPACIDAD:

CAPACIDAD:

120 Kva y sus bancos de120 Kva y sus bancos de baterías, en las instalaciones de IBM - La Molina.

baterías, en las instalaciones de IBM - La Molina.

3.

3. DESCRIPCIÓN

DESCRIPCIÓN /

/ EVENTO

EVENTO /

/ HECHOS:

HECHOS:

INSPECCIÓN GENERAL DEL EQUIPO

INSPECCIÓN GENERAL DEL EQUIPO

Se revisan los UPS externa e internamente. Encontrándose estos en perfectas condiciones Se revisan los UPS externa e internamente. Encontrándose estos en perfectas condiciones de operatividad.

de operatividad.

INSPECCIÓN VISUAL DE COMPONENTES

INSPECCIÓN VISUAL DE COMPONENTES

Se realiza la inspección de componentes electrónicos, se comprobó que el equipo Se realiza la inspección de componentes electrónicos, se comprobó que el equipo presentaba polución en sus tarjet

(2)

1. ACTIVIDADES

Limpieza exterior e interior de los equipos UPS Liebert.

Limpieza de contactos y ajuste de borneras, conexiones eléctricas en el interior del UPS. Revisión de la unidad de control y potencia encontrándose en buen estado.

Revisión del módulo Heat Sink del inversor, Rectificador y Static Switch, encontrándose en buen estado.

Pruebas de arranque con carga y toma de parámetros eléctricos respectivos.

Inspección general del estado, conexión del banco de baterías y toma de medidas de tensión de cada una de ellas.

2. TOMA DE PARÁMETROS UPS

Se realizó la toma de parámetros tanto del equipos UPS así como del banco de baterías obteniendo la siguiente tabla detallada a continuación:

PARAMETROS MEDIDOS

UPS-1

UPS-2

UPS-3

UPS-4

VOLTAJE DE ENTRADA L1 385.1 385.1 388.9 388.7 VOLTAJE DE ENTRADA L2 381,7 383.4 388.2 388.7 VOLTAJE DE ENTRADA L3 387.1 386.3 388.8 387.5 VOLTAJE DE ENTRADA L1-N 223.1 222.0 224.4 223.5 VOLTAJE DE ENTRADA L2-N 218.2 221.9 224.5 223.6 VOLTAJE DE ENTRADA L3-N 221.9 222.4 224.7 224.7 CORRIENTE DE ENTRADA

 –

L1 103.5 102.1 101.3 100.7 CORRIENTE DE ENTRADA

 –

L2 104.1 99.6 100.5 101.5 CORRIENTE DE ENTRADA

 –

L3 103.9 99.8 100.7 101.3 TENSION DE SALIDA L1-N 218.1 216.5 217.4 218.9 TENSION DE SALIDA L2-N 218.4 219.5 218.5 217.5 TENSION DE SALIDA L3-N 218.5 218.9 218.6 217.6 TENSION DE SALIDA L1 378.1 377.6 377.2 378.4 TENSION DE SALIDA L2 378.4 379.3 378.5 378.5 TENSION DE SALIDA L3 378.3 377.6 378.0 378.8 CORRIENTE DE SALIDA

 –

L1 101.4 95.3 98.3 97.9 CORRIENTE DE SALIDA

 –

L2 106.4 103.6 104.7 103.4 CORRIENTE DE SALIDA

 –

L3 105.2 100.7 101.5 101.5 % CARGA

 –

L1 62.4 67.1 60.1 60.0 % CARGA

 –

L2 63.2 64.1 64.6 63.8 % CARGA

 –

L3 63.5 66.6 64.2 63.9

(3)

3. TOMA DE PARÁMETROS UPS BANCO DE BATERIAS

Marca:

Emerson

Modelo:

H12V 500/A

Capacidad:

140 AH

Cantidad: 38

Unid.

(4)

TOMA DE PARAMETROS: BANCO DE BATERIAS

Banco Baterías

CELDA UPS-1

UPS-2

UPS-3

UPS-4

CELDA

UPS-1

UPS-2

UPS-3

UPS-4

1

13.4 13.4 13.4 13.4

20

13.5 13.4 13.5 13.4

2

13.5 13.4 13.4 13.4

21

13.6 13.5 13.6 13.5

3

13.4 13.4 13.4 13.2

22

13.4 13.4 13.4 13.3

4

13.5 13.4 13.5 13.3

23

13.5 13.5 13.4 13.5

5

13.3 13.4 13.5 13.5

24

13.7 13.5 13.7 13.4

6

13.5 13.5 13.4 13.5

25

13.4 13.6 13.6 13.3

7

13.5 13.5 13.5 13.4

26

13.5 13.4 13.5 13.3

8

13.4 13.3 13.5 13.2

27

13.5 13.4 13.5 13.4

9

13.4 13.2 13.5 13.4

28

13.5 13.3 13.5 13.4

10

13.5 13.2 13.4 13.5

29

13.4 13.4 13.5 13.4

11

13.5 13.4 13.3 13.5

30

13.5 13.5 13.2 13.3

12

13.3 13.4 13.4 13.4

31

13.5 13.4 13.4 13.3

13

13.4 13.5 13.4 13.4

32

13.4 13.5 13.3 13.5

14

13.4 13.5 13.5 13.4

33

13.6 13.6 13.3 13.4

15

13.5 13.4 13.6 13.5

34

13.6 13.4 13.2 13.4

16

13.5 13.4 13.7 13.3

35

13.7 13.4 13.4 13.5

17

13.6 13.5 13.5 13.3

36

13.5 13.5 13.5 13.4

18

13.5 13.2 13.4 13.4

37

13.5 13.2 13.5 13.2

19

13.4 13.3 13.4 13.4

38

13.5 13.2 13.5 13.5

4. CONCLUSIONES / RECOMENDACIONES:

Los equipos UPS se encuentran operativos y sin alarmas.

Para garantizar la operatividad y disponibilidad del sistema se recomienda el reemplazo total del banco de baterías del UPS Liebert a corto plazo por tiempo de servicio ya que con el tiempo las baterías disminuye la capacidad de retención de energía, así como también la pérdida gradual de almacenamiento debido al proceso normal de envejecimiento.

.

Expectativa de vida de la batería.- Es el cálculo teórico (de diseño) que puede durar una batería estimada por fábrica en condiciones 100 % ideales. Es decir climatizadas y con un número limitado de ciclos de descarga.

Vida útil ó Vida de Servicio.- Es el tiempo real que dura las baterías bajo las condiciones reales del medio ambiente que lo alberga y de los ciclos de descarga. Los fabricantes estiman que a partir del tercer a quinto año se debe de realizar el cambio total del banco de baterías dado que a partir de dicho límite entran a la zona donde se produce un envejecimiento acelerado de la celda (manifestado en pérdida de capacidad y celdas abiertas o cortocircuitadas) y por ende producirse una desernegización del sistema que respalda. Lo esbozado en éste párrafo lo sustenta el Gráfico debajo:

(5)

Referencias

Documento similar

Admitir a trámite, trasladar al Gobierno a los efectos del artículo 126 del Reglamento, publicar en el Boletín Oficial de las Cortes Generales y notificar al autor de la

Búsqueda de información Según Kotler y Armstrong (2008, p. 142), en esta etapa el consumidor según el tipo de necesidad o problema que manifieste podría o no buscar mayor

Las previsiones económicas de otoño de la Comisión Europea confirman que el cuadro macroeconómico del Gobierno con el que ha elaborado los presupuestos de este año y el que viene

-Tiene varias cosas positivas, el campeonato adquiriría más valor, conseguiríamos que acudieran más tiradores, la representación en el mundial sería directamente proporcional al

Página 1 de 11 Fecha de revisión: Noviembre del 2012 MSDS de acuerdo con SGA versión 2011.. Material Safety Data

Fundamento Legal para dispensar la lectura: artículos, 39 fracción I inciso e) de la Ley Orgánica Poder Legislativo del Estado de San Luis Potosí; y 75 fracción IV del Reglamento

Representantes de la Consejería de Salud y Familias de la Junta de Andalucía, de la Agencia Española de Medicamentos y Productos Sanitarios (AEMPS) y Presidente

Los datos de carácter personal de los participantes necesarios para gestionar su participación en el concurso serán objeto de tratamiento automatizado de conformidad a la